background image

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers 
Installation Instructions 

17

Smart Fan Mode (smart):

 Energizes the fan all 

the time for Occupied states, and only on a call for 
heating or cooling in Unoccupied states. This is the 
default setting for the T606MSP-4 and 
T606MSP-4+PIR models.

To select the fan mode, follow the steps in Table 7: 

Programming the Daily Schedule – Two-Event 
(T606MSP-4 and T606MSP-4+PIR Models)

The schedule-setting menu is used to enter the 
Occupied or Unoccupied states for each day of the 
week. The schedule-setting menu reflects either a 
two- or a four-event schedule per day, based on what 
was selected in the 

2/4event

 parameter during the 

configuration process. If the schedule-setting menu 
does not reflect a two-event schedule, select two 
events in the 

2/4event

 parameter of the Installer 

Configuration Menu.

When changing the time, press and release the 

UP/DOWN

 arrow keys to change the time in 1-minute 

increments; press and hold down the keys to change 
the time in 30-minute increments.

Note:

Programming one of the digital inputs to remote 

NSB disables the menu.

To set the time schedule for a two-event schedule, 
follow the steps in Table 8. See Table 10, Events 1 
and 2, for an example of a two-event office schedule. 

Table 7:  Selecting the Fan Mode

Controller 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key for all prompts 

until the fan mode prompt appears 
on the display. Press the 

YES

 key to 

enter the fan mode setting menu.

Press the 

UP/DOWN

 arrow keys to 

locate the desired fan mode. Press 
the 

YES

 key to select the desired 

system mode (example for smart 
mode shown)

Press the 

YES

 key to return to 

the Status Display Menu or press 
the 

NO

 key to return to the 

system mode selection menu.

RoomTemp 
75.0 

°

F

 

Fan mode 
set? Y/N 

Fan mode
Smart

Exit? 
 Y/N 

Table 8:  Programming the Daily Schedule – 

Two-Event (Part 1 of 2)

Controller 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key for all prompts until 

the schedule set prompt appears on 
the display. Press the 

YES

 key to 

enter the scheduling menu.

Press the 

YES

 key to set the 

schedule for Monday or press the 

NO

key to advance to Tuesday.

Press the 

YES

 key to set the 

Occupied start time for Monday or 
press the 

NO

 key to advance to 

Tuesday. Selecting 

NO

 leaves the 

controller in the Unoccupied state for 
the entire day.

Press the 

UP/DOWN

 arrow keys to 

set the Occupied start time. Press the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the Unoccupied start time. Press 
the 

YES

 key to enter the time.

Press the 

YES

 key to set the 

schedule for Tuesday or press the 

NO

 key to advance to Wednesday.

Press the 

YES

 key to copy the 

schedule from the previous day. 
Press the 

NO

 key to set a different 

schedule.

If the 

YES

 key was pressed, the next 

prompt is for Wednesday. Repeat the 
procedure for the rest of the days of 
the week.

RoomTemp
75.0

°

F

 

Schedule
set? Y/N 

Monday
set? Y/N 

Occupied
day? Y/N 

Occupied
12:00 AM 

Unoccup
12:00 AM 

Tuesday
set? Y/N 

Copy Y/N
previous 

Wednesda
set? Y/N 

Summary of Contents for T606MSN-4

Page 1: ...er and open the controller as illustrated in Figure 1 IMPORTANT The T606MSx 4 and T606MSx 4 PIR Series Temperature and Humidity Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designe...

Page 2: ...controller Note If you need to install the thermostat on an electrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bol...

Page 3: ...re making electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the T606...

Page 4: ...ccupancy of the electronic control card inside the equipment configure the relay parameter Aux Cont to the Normally Open N O setting A second relay can be added for additional occupancy input functions 3 The humidifier output uses a half bridge rectifier The control signal reference is the controller power supply common terminal C 4 Electromechanical contacts are used with the digital input Electr...

Page 5: ... is on The cool LED is on when cooling is on Integrated PIR Sensor T606MSx 4 PIR Series Controllers The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied Programming Overview Three menus ...

Page 6: ... includes a high limit sequence This sequence allows the use of a remote 0 to 10 VDC humidity sensor to keep the humidifier from saturating the supply air The remote sensor throttles the output of the Proportional plus Integral plus Derivative PID loop if the high limit sensor measures humidity in the duct over the high limit value 85 less the proportional band of the high limit PID loop If no sen...

Page 7: ...ed strategy If the controller is programmed to be Unoccupied the PIR function does not have an effect on the occupancy strategy The controller automatically switches the occupancy level between Occupied and Unoccupied as required when local movement is sensed In the Occupied mode if no movement is detected beyond the Unocc TM parameter setting the mode changes to Unoccupied Once movement is detect...

Page 8: ...splay Menu and when the message is displayed the backlight momentarily lights up The input can be configured to the Selection Options included in Table 2 Table 2 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unauthorized access to the Installer Configuration Menu Default 0 Note ...

Page 9: ...ccess Clock Setting2 Access Access Access Permanent Hold2 Access No Access No Access Pwr del3 Sets the delay time period at controller powerup or each time power is removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Frost pr Provides a minimum heating set...

Page 10: ...er of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cycles per hour Deadband Sets the minimum deadband between the heating and cooling setpoints Default 2 0F 1 0C Range 2 0F 1 0C to 4 0F 2 0C adjustable in 1 0F 0 5C increments Fan cont Determines how the fan is activated in response to a...

Page 11: ...5 0F 2 5C adjustable in 1 0F 0 5C increments H stage Reverts the operation of a two stage controller to a single stage controller when the second heating stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation of a two stage controller to a single stage controller when the second cooling stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages H lock Disables...

Page 12: ...cupied temperature at the start of the Occupied schedule off Disabled provides the desired occupied temperature after the Occupied schedule begins RH LT5 Sets minimum outside air temperature for RH setpoint reset Default 20 F 29 C Range 40 F 40 C to 15 F 9 5 C RH HT Sets maximum outside air temperature for RH setpoint reset Default 32 F 0 C Range 20 F 6 5 C to 55 F 13 C HL Sp Sets high humidity le...

Page 13: ...chedule menu display Any other setting enables schedules and the Schedule menu T606MSP 4 and T606MSP 4 PIR models 2 T606MSP 4 and T606MSP 4 PIR models 3 When adjusting the numeric value press the UP DOWN arrow key to change the value by single increments press and hold the UP DOWN arrow key to change the numeric value in increments of ten 4 When adjusting the temperature press the UP DOWN arrow ke...

Page 14: ... Main User Menu 1 Press the NO key for all prompts until the Cancel ovrd prompt appears If the controller is in the override state this is the first prompt 2 Press the YES key to resume the programmed schedule The controller returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User Menu of the controller when in the Occupied state sets ...

Page 15: ...ss the NO key for all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES key to change the Occupied cooling setpoint Press the NO key to advance to the Occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to store the value and advance t...

Page 16: ...te The setting for the Fan cont parameter may affect the fan operation on a call for heating Table 5 Entering Humidity Setpoints Controller Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key for all prompts until the humidity setpoint prompt appears on the display Press the YES key to enter the humidity setting menu Press the YES ke...

Page 17: ...he fan mode prompt appears on the display Press the YES key to enter the fan mode setting menu Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the desired system mode example for smart mode shown Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu RoomTemp 75 0 F Fan mode set Y N Fan mode Sma...

Page 18: ...s on the display Press the YES key to enter the scheduling menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Table 8 Programming the Daily Schedule Two Event Part 2 of 2 Controller Display Description Exit Y N RoomTemp 75 0 F Schedule set Y N Monday set Y N Press the YES key to set the Occupied start time for Monday or press the NO key to advance to Tu...

Page 19: ...P M 1 Sunday 12 00 P M 1 12 00 P M 1 12 00 P M 1 12 00 P M 1 1 Programming different events to the same time for that day cancels those events and leaves the controller in the Unoccupied state Table 11 Setting the Day and Time Part 1 of 2 Controller Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key for all prompts until the clock s...

Page 20: ...edule hold menu has the following selections Permanent Occupied Hold occ hold This selection puts the controller into a permanent Occupied state via the Occupied setpoints Occupied hold appears in the Status Display Menu when this selection is active Permanent Unoccupied Hold This selection puts the controller into a permanent Unoccupied state via the Unoccupied setpoints Unoccup hold appears in t...

Page 21: ...ted on the wall Remote duct mounted humidity sensor may be used for remote return air humidity sensing with the sensor mounted on the return air duct or as a supply air humidity sensor used as a high limit protection 2 Additional TE 636xx x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available refer to the TE 6300 Series Temperature Sensors Product Bulletin LIT 216320 for more d...

Page 22: ...ents Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Humidity 5 RH from 30 to 70 RH at 50 to 90 F 10 to 32 C Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Non...

Reviews: