background image

System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin

    5

Sensor Connection

Shielded cable is not generally required for sensor
wiring on runs of less than 50 ft (15.2 m), but is
recommended for lengths greater than 50 ft (15.2 m).
When using shielded cable, isolate and tape the shield
at the sensor. Connect the shield to the COM sensor
terminal on the A350A/B. (See Figure 2 for terminal
location.) The A99BA-200C sensor, which includes
shielded cable, is available if needed.

Note:

At the maximum cable lengths listed in Table 2,
no more than 1F° (0.6C°) error in the sensed
temperature will result due to wire resistance.

Table 2: Recommended Maximum Sensor
Cable Lengths

Wire

Shielded Cable Length

*

Gauge

Feet

Meters

14 AWG

800

244

16 AWG

500

152

18 AWG

310

94

20 AWG

200

61

22 AWG

124

38

* Values provided are for 2-wire stranded cable.

Various A99B Series Temperature Sensors and
mounting hardware are available for use with A350
Series Controls. See Tables 3 and 6. The sensor
must be connected to the COM and SEN terminals
on the four-position terminal strip located at the top
left of the printed circuit board (Refer to Figures 2,
4, and 5.). The sensors are not polarity sensitive.

  The sensor must be mounted so that it can

accurately sense the temperature of the controlled
medium.

Table 3: Sensors Included With A350A/B
Controls

Control

Sensor Included

Sensor lead length is 9-3/4 in. (0.25 m)

A350AA-1C

A99BB-25C; Range: -40 to 212°F
(-40 to 100°C)

A350AA-2C

A99BC-25C; Range: -40 to 248°F
(-40 to 120°C)

A350AA-3C

A99BB-25C; Range: -40 to 212°F
(-40 to 100°C)

A350AB-1C

No Sensor Included

A350AB-2C

No Sensor Included

A350AB-5C

No Sensor Included

A350BA-1C

A99BB-25C; Range: -40 to 212°F
(-40 to 100°C)

A350BA-2C

A99BC-25; Range: -40 to 248°F
(-40 to 120°C)

A350BB-1C

No Sensor Included

For more information regarding sensor options and
installation, refer to the

 A99B Series Temperature

Sensors Product/Technical Bulletin (LIT-125186).

A350A/B

S350A

S350A

D350

S350A

Load

Load

Load

Load

Y350R

120 VAC

Shield (Connect
to COM on A350)

Sensor

Figure 5: System 350 Powered by Y350R Module

Summary of Contents for System 350 A350A

Page 1: ...res and Benefits Modular Design Enables stage display and power modules to be purchased and installed as needed Plug together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules and reduces installation costs Two Standard Models Cover Wide Setpoint Ranges 30 to 130 F 34 to 55 C or 90 to 250 F 32 to 121 C Reduces inventory by encompassing temperature ranges required to support ...

Page 2: ...rvisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperature at which the A350A B s relay de energizes Use the Setpoint Dial on the front of the A350A B to adjust setpoint See Figure 2 Differential Adjustment Differential is defined as the change in sensor temperature between energization and de energization of the relay Adjustment of the A350A B differen...

Page 3: ... power and sensor input from the A350 control S350C Slave Stage Modules perform switching functions based upon the A350 s sensor information Setpoint and differential are selected independently at the S350C For more information on these modules refer to the System 350 TM S350C Temperature Slave Stage Module Product Technical Bulletin LIT 930084 S350P Proportional Stage Modules S350P Proportional S...

Page 4: ...into the right side of the A350A B control Note When mounting the System 350 modules to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure WARNING Risk of Electrical Shock Disconnect power supply before wiring connections are made to avoid electrical shock or damage to equipment All wiring must conform to the National Electrical Code and or local regulatio...

Page 5: ...with A350 Series Controls See Tables 3 and 6 The sensor must be connected to the COM and SEN terminals on the four position terminal strip located at the top left of the printed circuit board Refer to Figures 2 4 and 5 The sensors are not polarity sensitive The sensor must be mounted so that it can accurately sense the temperature of the controlled medium Table 3 Sensors Included With A350A B Cont...

Page 6: ... The A350A B setpoint is factory calibrated at midscale to a tolerance of 1F 0 6C Setpoint tolerance at the extreme ends of the setpoint ranges in relation to the printed scale can be 3F 1 7C The D350 Display Module is unaffected by this tolerance shift Use the D350 for the most accurate setpoint selection Checkout Procedure Follow this procedure to verify that the A350A B is connected and functio...

Page 7: ...etpoint Dial Setting Heating On Closed Ts Sp Diff Heating Off Open Ts Sp Cooling On Closed Ts Sp Diff Cooling Off Open Ts Sp Ts is sensed temperature and Sp is setpoint temperature Repairs and Replacement Do not make field repairs or perform calibration Replacement controls and A99B Temperature Sensors are available through the nearest Johnson Controls representative See Tables 5 and 6 for orderin...

Page 8: ...emperature Control Supply Voltage Y350R Power Module Input 120 240 VAC 50 60 Hz Output 24 VDC unfiltered 10 VA Class 2 External Source 24 VAC 50 60 Hz Class 2 20 30 VAC Note Only one supply voltage source may be used Power Consumption 1 4 VA Ambient Temperatures Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Humidity 0 to 95 RH non condensing maximum dew point 85 F 29 C Setpoint ...