3. Indoor unit Installation

1. Cutting A Hole and Mounting Installation Plate

Installation Plate and Its Measures

1. Install the installation plate horizontally on struct-
    ural Parts in the wall with the spaces provid-
    ed around the plate.
2. In  case  of  block, brick, concrete or similar type
    walls, make 5mmdia, holes in the wall. Insert clip
    anchors for appropriate mounting screws.
3. Fix the installation plate on the wall.

Determine the pipe hole position using

    the installation plate, and drill the pipe
    hole (  65mm) so it slants slightly dow-
    nward.

1. Pass the piping through the
    hole in the wall.
2. Put  the  upper claw  at  the
    back  of  the indoor unit  on
    the  upper  hook  of  the 
    installation plate, move the
    indoor unit from side to side
    to  see  that  it  is  securely 
    hooked.

Installation Plate

Upper hook

Floating Prevention
support

Low hook

NOTE:

1. Fix the installation plate.

2. Cutting a hole.

1. Drainage

2. Connective pipe

INDOOR UNIT INSTALLATION

1

.

.

.

.

.

.

.

. .

.

. .

.

. .

.

.

. .

.

.

. .

.

.. .

.

.

. .

.

.. .

.

. .

.

.

.

.

.

.

.

.. .

.

.

. .

.

.

.

.

.

. .

.

. . .

.

.

.

.

.

.

. .

.

.

.

.

.

.

. .

.

.

.. .

.

.

.

.

. .

.

.

.

. .

. .

.

.

.

.

..

.

.

. .

.

.

. .

.

.

.

.

.

. .

.

.

.

.

.

. .

. .

...

.

.

.

.

.

. ..

.

.

.

. . .

.

......

..

.

.

.

...

4

3

50

42

906

49

90

55

50

           65mm

Rear-right pipe
 hole

120mm or more to the wall

120mm or more to the wall

Shield pipe

Do not form a rise.

Do not put the drain
end into water.

Wall

Drain hose

Extension drainhose

Indoor unit outline

Connective pipe

Indoor unit outline

Installation plate

150mm or more
to the ceiling

           
Rear-left pipe 
hole   65mm

2. Connective Pipe and Drainage Installation

4. Electrical Work

1. Run the drain hose sloping downward. Do
    not  install  the  drain  hose  as  illustrated
    below.

1. For the left-hand  and rear-left-hand piping,
    install the piping as shown. Bend the conne-
    ctive pipe to be laid at 43mm height or less
    from the wall.

2. When  connection  extension  drain  hose
    insulate the connecting part of extension
    drain hose with a shield pipe.

Prepare the power source for exclusive with the air conditioner.
The supply voltage must be the same as the rated voltage of 
the air conditioner:

220-240V~50Hz

40A/30A

2

2.5mm

Wiring

Power
Source

Power switch
and Fuse
rating

A disconnection device having an air gap contact separation in 
all active conductors should be incorporated in  the fixed wiring 
according to the National Wiring Regulation.

Inside the room

CAUTION

2. Fix the end of the connective pipe.(Refer to
    Tightening connection in REFRIGERANT
    PIPING CONNECTION)

Connect the indoor unit first then the
outdoor unit.
Bend and arrange the pipe carefully.
Insulate both of the auxiliary piping.
Drainage can not annoy your neighbor.

CAUTION

Perform the wiring with sufficient capacity.
Installation places legally require a short circuit isolator to be 
attached to prevent electrical shock.
Do not extend the power cable code by cutting.
The  plug  of  the  air conditioner takes  a  grounding  leg,  so 
clients should use a grounding socket so that the air 
conditioner  can  be grounded efficiently.
Power voltage should in the range of 90% ~110% of  rated 
voltage
The cross section area of the wiring in the cable is based on 
the copper core inside plastics.

A

(Split Wall-Mounted Type)

For correct installation, read this manual before starting installation and save this manual in
a safe place for future reference.
Only trained and qualified service personnel should install, repair or service air conditioning
equipment. Users should not install the air conditioner by themselves.
All pictures are only sketches. If there is any difference between pictures in this manual and
the actual shape of the air conditioner you purchased, the actual shape shall prevail.

Installation in  the following places  may cause  trouble. If it  is  unavoidable,  please consult 
with the local dealer.
   A place full of machine oil.
   A saline place such as coast.
   A place full of sulfide gas such as hot-spring resort.
   Places where there  are high  frequency machines  such as  wireless  equipment, welding
   machine, and medical facility.
   A place there is no combustive gases and volatile matter.
   A place of special environmental conditions.

A place, which is convenient to installation
and not exposed  to a strong wind. A place 
that is dry and ventilated.
A place can bear the weight of the outdoor
unit and where the outdoor unit can be held
in the horizontal position.
A place  which does not  allow an increase
in noise level and vibration.
A place where the operation noise and dis-
charge air do not disturb your neighbor or 
animals.
A place  free of  a  leakage of combustible
gases.
An allowable  head  level at the connective
piping is  less  than  5m  and  length of the
connective piping is up less than 10m.
No any obstacle which block radiating air.
Unavailable to children.
A place, which provides the space around
the outdoor unit as required right in the 
diagram.

Indoor Unit

Outdoor Unit

INSTALLATION PRECAUTION

A place where is no obstacle near  the inlet
and outlet area.
A place which  can bear  the weight  of the
indoor unit.
A place which is convenient to maintenance.
A  place which provides  the  space  around 
the  indoor  unit  as  required  right  in  the 
diagram.
A place 1m or more to TV, radio instrument,
in the center of the room is perfect.
A  place which is far from heat, steam and
inflammable gas.

Please install the accessories attached with
unit correctly according to this installation
manual.

1.At least two of A,B,C aspects are free
   from blocking.
2.When the Outdoor Unit is higher
   than the Indoor Units,to prevent
   the rain from flowing into the indoor
   along the connection pipe, a 
   downward tipping arc should be
   made before the connection pipe
   entering the wall to indoor to ensure 
   the lowest point on the connection
   pipe is at outdoor.
3.The illustration above is only a 
   sketch. Different models would be 
   slightly different.

NOTE:

Before   installation,  operate   the  remote
controller  to  determine  its  location in  a
reception range.
Keep  the  remote  controller  at  least 1m
apart  from the  nearest  TV set  or stereo
equipment.
Do not  install  the  remote  controller in a
place exposed  to direct  sunlight or close
to a heating source, such as a  stove.
Note that the positive and negative poles
are right positions when loading batteries.

1

2

3

4

5

6

7

8

Installation plate

Plastic Expansion Pipe

Self-tapping screw ST3.9

25 

Connection   Liquid side     6.35

pipe Ass.       Gas side       12.7

Remote controller

Remote controller holder

Seal

Drain elbow

Model

530     290

560     335

The outdoor unit should not be exposed to

strong wind.

Fix the outdoor unit with  10 of     8 anchor

 

 bolts.

If need suspending installation, consults the

 corresponding requirement.

air outlet

air inlet

Air outlet

A

B

Remote 

Controller

Air filter

Loop the connective cable

a

a

b

b

Anchor bolts of out door unit installation

Accessories

45cm or more

6

0

cm o

mo

re

30cm or more

200cm

 or

 more

60cm

 or more

5

4

15cm or more 

12cm or mo

re

12cm or more

1

2

3

18000Btu/h

18000Btu/h

10mm

10mm

40mm

40mm

Cooling only
type.

Cooling & heating
type.

Code wire

Frame

Screw Cover

220-230V~60Hz

20A

2

1.5mm

Cushioning
material

INSTALLATION MANUAL FOR ROOM

AIR CONDITIONER

3. Piping can  easily be made  by lifting  the indoor unit

    with  a cushioning material  between the  indoor unit

    and the wall. Get it out after finish piping.

4. Push the lower part of the indoor unit up on the wall,

    Then move the indoor unit from side to side, up and

    down to check if it is hooked securely.

Part
No. 

Name of part

Parts lnstallation

Cautions on remote controller installation

5. Connecting Cables

1. Indoor/Outdoor connection cable should be H07RN-F5G type.
2. Remove the panel and Screw Covers (3), remove Screws 
    (4), then take out the Frame.
3. Connect cables according to their marks to terminals.
4. Wrap those cables not connected with terminals with
    insulation tapes, so that they will not touch any electrical
    components.
Note: Some models may be equipped with power cord,
          connecting cables according to the terminal block 
          with five terminals in the wiring diagram.

Panel

Terminal block of indoor unit

To outdoor unit

To outdoor unit

Cord clamp

1   2(N)   3   4

1   2(N)   3   4