5566020-JIM-C-1019
48
Johnson Controls Ducted Systems
Airflow performance
Table 20:Airflow performance - side duct application
J06ZF (6.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive
Standard 1.5 HP and drive
High static 2 HP and drive
1800
751
0.22
813
0.43
872
0.62
929
0.78
985
0.93
1040
1.07
1095
1.20
1150
1.33
1206
1.46
1265
1.59
2000
776
0.35
838
0.56
897
0.75
954
0.92
1010
1.07
1064
1.20
1119
1.33
1175
1.46
1231
1.59
1289
1.72
2200
804
0.50
866
0.71
925
0.90
982
1.06
1038
1.21
1092
1.35
1147
1.48
1203
1.61
1259
1.73
1317
1.87
2400
835
0.66
897
0.87
956
1.06
1013
1.22
1069
1.37
1124
1.51
1178
1.64
1234
1.77
1290
1.90
1348
2.03
2600
869
0.84
931
1.05
990
1.24
1047
1.40
1103
1.55
1158
1.69
1212
1.82
1268
1.95
1324
2.07
1382
2.21
2800
906
1.03
968
1.25
1027
1.43
1084
1.60
1139
1.75
1194
1.89
1249
2.02
1304
2.14
1361
2.27
-
-
3000
945
1.25
1007
1.46
1066
1.65
1123
1.81
1179
1.96
1234
2.10
1288
2.23
-
-
-
-
-
-
3200
987
1.48
1048
1.69
1107
1.88
1165
2.04
1220
2.19
-
-
-
-
-
-
-
-
-
-
3400
1030
1.73
1092
1.94
1151
2.12
1208
2.29
-
-
-
-
-
-
-
-
-
-
-
-
2 HP and field supplied drive
J07ZF (7.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive
Standard 1.5 HP and drive
High static 3 HP and drive
2000
776
0.35
838
0.56
897
0.75
954
0.92
1010
1.07
1064
1.20
1119
1.33
1175
1.46
1231
1.59
1289
1.72
2200
804
0.50
866
0.71
925
0.90
982
1.06
1038
1.21
1092
1.35
1147
1.48
1203
1.61
1259
1.73
1317
1.87
2400
835
0.66
897
0.87
956
1.06
1013
1.22
1069
1.37
1124
1.51
1178
1.64
1234
1.77
1290
1.90
1348
2.03
2600
869
0.84
931
1.05
990
1.24
1047
1.40
1103
1.55
1158
1.69
1212
1.82
1268
1.95
1324
2.07
1382
2.21
2800
906
1.03
968
1.25
1027
1.43
1084
1.60
1139
1.75
1194
1.89
1249
2.02
1304
2.14
1361
2.27
1419
2.40
3000
945
1.25
1007
1.46
1066
1.65
1123
1.81
1179
1.96
1234
2.10
1288
2.23
1344
2.36
1400
2.48
1458
2.62
3200
987
1.48
1048
1.69
1107
1.88
1165
2.04
1220
2.19
1275
2.33
1330
2.46
1385
2.59
1442
2.71
1500
2.85
3400
1030
1.73
1092
1.94
1151
2.12
1208
2.29
1264
2.44
1319
2.58
1374
2.71
1429
2.84
1485
2.96
1544
3.10
3600
1076
1.99
1138
2.20
1197
2.39
1254
2.56
1310
2.71
1364
2.84
1419
2.97
1475
3.10
1531
3.23
1589
3.36
3800
1124
2.27
1185
2.48
1245
2.67
1302
2.84
1357
2.99
1412
3.12
1467
3.25
1522
3.38
-
-
-
-
3 HP and field supplied drive
J08ZF (8.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive
Standard 2 HP and drive
High static 3 HP and drive
2600
628
0.56
678
0.76
730
0.93
781
1.09
833
1.25
883
1.41
933
1.59
980
1.80
1025
2.05
1068
2.35
2800
648
0.67
698
0.87
750
1.04
801
1.20
853
1.36
903
1.52
953
1.70
1000
1.91
1046
2.16
1088
2.46
3000
666
0.80
717
1.00
768
1.17
820
1.33
871
1.49
922
1.65
971
1.83
1019
2.04
1064
2.29
1106
2.59
3200
684
0.95
735
1.15
786
1.32
838
1.48
889
1.63
940
1.80
989
1.98
1037
2.19
1082
2.44
1124
2.74
3400
702
1.11
753
1.31
804
1.48
856
1.64
907
1.79
958
1.96
1007
2.14
1055
2.35
1100
2.60
1142
2.90
3600
721
1.28
772
1.48
824
1.65
875
1.81
927
1.97
977
2.13
1027
2.31
1074
2.52
1119
2.77
---
---
3800
742
1.47
793
1.67
844
1.84
896
2.00
947
2.15
998
2.32
1047
2.50
1095
2.71
1140
2.96
---
---
4000
765
1.67
815
1.86
867
2.04
918
2.19
970
2.35
1020
2.51
1070
2.70
1117
2.91
---
---
---
---
4200
789
1.87
840
2.07
891
2.24
943
2.40
995
2.56
1045
2.72
1094
2.90
---
---
---
---
---
---
3 HP and field supplied drive