Optional electric heat
The factory-installed heaters are wired for single point power
supply. You only need to bring the power supply into the single
point terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending in
to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. See the
table for minimum CFM limitations. See the
table for electrical data.
Table 15:Electric heat minimum supply air
Size (tons)
Model
Voltage
Minimum supply air (CFM)
Heater kW
9
18
24
36
54
J06
(6.5)
ZF
208/230-3-60
1950
1950
1950
1950
-
460-3-60
1950
1950
1950
1950
-
600-3-60
1950
1950
1950
1950
-
J07
(7.5)
ZF
208/230-3-60
2250
2250
2250
2250
-
460-3-60
2250
2250
2250
2250
-
600-3-60
2250
2250
2250
2250
-
J08
(8.5)
ZF
208/230-3-60
2550
2550
2550
2550
-
460-3-60
2550
2550
2550
2550
-
600-3-60
2550
2550
2550
2550
-
J10
(10)
ZF
208/230-3-60
-
3000
3000
3000
3500
460-3-60
-
3000
3000
3000
3000
600-3-60
-
3000
3000
3000
3500
J12
(12.5)
ZF
208/230-3-60
-
3750
3750
3750
4000
460-3-60
-
3750
3750
3750
3750
600-3-60
-
3750
3750
3750
3750