Operating manual – DualPAC with reciprocating compressors
0012201 en 2021.04
57/63
3.
Press
Arrow up
(no. 4) once to change the digit to 2.
4.
Press
Arrow right
(no. 1) again
→
passcode required
→
press the buttons: 1-2-3-4-1-2,
see Fig. 30.
Fig. 30
Example: how to change a parameter in the supervisor menu
Change of gas constant 2.5.3 to value according to the list in Fig. 38. If in doubt, choose the low-
est value belonging to the lower end of your operating range.
1.
Change the text in the upper line in the display to 2.5.3:
•
Press
Arrow right
(no. 1) – the second digit is marked, see Fig. 31.
Fig. 31
•
Press
Arrow up
(no. 4) until 1 has turned to 5.
•
Press
Arrow right
(no. 1) – the third digit is marked, see Fig. 32.
Fig. 32