background image

1010352-UUM-N-0121

Johnson Controls Ducted Systems

5

Call a certified dealer or servicing contractor to check or clean your fur-
nace, or for more information if you have questions about the operation
of your furnace.
If all components appear to be in good operating condition, replace the
furnace access panels/doors. Turn 

on

 the gas and electrical power sup-

plies to the furnace, and set the thermostat to the preferred tempera-
ture.

Cleaning your filter

High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow the fil-
ter to completely dry before re-installing the filter.
Replace throwaway filters with the same size new filters. Throwaway fil-
ters may be replaced with cleanable filters at this time. 

Blower care

Even with good filters properly in place, blower wheels and motors will
become dust laden after months of operation. The entire blower assem-
bly should be inspected annually. This service must be performed by a
qualified service agency.

Note: 

The  spring-loaded  safety  cut-off  switch,  mounted  at  the  blower

deck, automatically cuts off the electrical power supply to the furnace
when  the  furnace  blower  access  panel/door  is  removed. As  a  safety
precaution, all electrical power and the gas supply to the furnace must
be turned off before servicing.

Motor lubrication

The  motors  in  these  furnaces  are  permanently  lubricated  and  do  not
require periodic oiling.

SECTION V: SERVICE INFORMATION
Troubleshooting problems

If  your  furnace  is  not  operating  correctly,  make  the  following  visual
checks before contacting your local contractor, dealer, or service pro-
vider:
1. Check that electrical power to the furnace is turned on.
2. Check that the manual gas shut-off valve in the gas piping supply is

turned to the 

on

 position. See Figure 6.

3. Check that the 

on/off

 switch on the gas valve is turned to the 

on

position. See Figures 7 to 9.

4. Check that the furnace blower access panel/door is correctly posi-

tioned. The electrical power supply is cut off if this door is removed.

Furnace control diagnostics

The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED shows a fault code. The LED flashes red, green,
or amber to indicate various conditions. It is located behind a clear view
port in the blower compartment door.
The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED indicates the failure code. If
the failure is internal to the control, the light stays on continuously. In
this case, the entire control must be replaced, as the control is not field
repairable.
Flash sequence codes 1 through 10 are as follows: LED turns on for 
1/4 s and off for 1/4 s. This pattern repeats the number of times equal to
the code. For example, six 

on

 flashes equals a number 6 fault code. All

flash code sequences are broken by a 2-s 

off

 period.

Slow green flashes: 

Normal operation.

Double amber flashes:

 Normal heating operation - Modulating furnace

models only

Slow amber flashes:

 Normal operation with call for heat.

Rapid  red  flashes:

 There  is a  problem  with  the  operation  of  this  fur-

nace. Contact your local dealer, contractor, or service provider.

Furnace maintenance - dealer/contractor

The furnace must be cleaned and adjusted by a certified dealer or qual-
ified service contractor once a year or before the start of every heating
season. The following items must be cleaned and serviced or replaced
if there are signs of deterioration:

• The vent terminal.
• The  furnace  vent  and  combustion  air  intake  passageways.

Should it be necessary to service the vent/air intake system, this
service  must  be  conducted  by  a  qualified  service  agency.  The
operation of this appliance requires the reassembly and resealing
of the vent/air intake system.

• The furnace burners, ignitor, and flame sensor.
• The condensate collection and disposal system. If any disassem-

bly  of  components  containing  flue  or  vent  gases  is  required,  a
qualified service agency must perform the service.

• Heat exchanger assembly.
• Induced draft motor assembly.

Replacement parts list

All  components,  assemblies,  accessories,  and  replacement  parts  for
this furnace are available through qualified service agencies. The user
must not purchase, install, or replace any components of this furnace.
Contact  your  local  contactor,  dealer,  or  service  provider  for  additional
information.

Wiring diagram

The unit wiring diagram may be found on the inside of one of the access
panels  on  the  furnace.  It  is  intended  for  reference  only.  If  service  is
required, contact your local contactor, dealer, or service provider.

 WARNING

Make sure you do not move the clip on weight on the indoor
fan wheel when cleaning the wheel. This weight is used to
balance the wheel. Moving the weight causes the fan wheel
to vibrate.

!

Summary of Contents for RGF1L P Series

Page 1: ...or when insulation is added to be sure that the insulation material has been kept away from the furnace The following warning applies to horizontally vented furnaces only 3 The furnace needs air for c...

Page 2: ...ce agency Examine the furnace as outlined below in Steps 1 to 8 before each heat ing season See Figures 1 to 4 for visual reference Figure 1 Component Location 80 Single and Two Stage Models Figure 2...

Page 3: ...ens and ignition occurs A short time later the blower starts and dis tributes the warm air throughout the home When the temperature set ting on your thermostat is reached the gas valve closes the main...

Page 4: ...me the external air filters are changed the following items must be visually inspected Check combustion air and vent pipe for blockage or leakage Check all components to ensure they are in good condit...

Page 5: ...port in the blower compartment door The control continuously monitors its own operation and the operation of the system If a failure occurs the LED indicates the failure code If the failure is interna...

Page 6: ...1010352 UUM N 0121 6 Johnson Controls Ducted Systems Notes...

Page 7: ...m warm air temperature and or with out adequate air circulation 3 The product is installed so that combustion air is not contaminated by compounds of chlorine fluorine or other damaging chemical vapor...

Page 8: ...ct 5 Labor or other costs incurred for diagnosing repairing removing installing shipping servicing or handling of defective replacement parts 6 Products removed from their original location for reinst...

Reviews: