1. Thread the swivel adapters into the female pipe
thread fittings projecting through the top of the
compressor compartment access cover. To prevent
twisting of the copper water piping in the chassis
assembly, always use a backup wrench.
To minimize the possibility of damage to
the chassis or cabinet and for maximum
ease of installation, the use of a two-
wheeled dolly is strongly recommended.
Do not contact the finned coil face. Dam
-
age to the fins will result.
2. Lift chassis from the front of chassis (see
).
3. Align chassis with the opening of the cabinet. Tilt
the chassis sufficiently for the base of the chassis
to clear the mounting rails on the cabinet drain
).
4. Insert the chassis midway into the opening of the
cabinet. Lower the rear of the chassis until the
base of the chassis touches the formed mounting
rails in the cabinet drain pan (see
).
LD23564
FIGURE 25 -
LIFT THE CHASSIS FRONT
LD23565
FIGURE 26 -
TILT THE CHASSIS
LD23566
FIGURE 27 -
INSERT THE CHASSIS
Before fully inserting chassis, ensure
wiring harness and or water hoses will
not be pinched.
5. Pivot the chassis base on the front edge of the
drain pan rails. Before fully inserting the chassis,
ensure the wiring harness and water hoses cannot
be pinched between the chassis and cabinet (see