—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin    

3

 

 

Table 3: Functions and Settings 

Function 

Description 

Setting Range 

Default 

SI

:

 

Setpoint

 

Primary temperature setpoint at which compressor 

control contacts open on temperature fall 

-40 to 158°F (-40 to 70°C) 

--- 

HY

Hysteresis (Differential)

 

Temperature difference relative to setpoint at which 

compressor control contacts close on temperature rise 

1 to 9 F° (1 to 9 C°) 

LL

Low Setpoint Stop

 

High setpoint adjustment limit 

-40°F (-40°C)

 to 

HL

 

-25 

HL

High Setpoint Stop

 

Low setpoint adjustment limit 

LL

 to 158°F (70°C) 

40 

CC

Anti-short Cycle Delay

 

Minimum time between two compressor On cycles 

0 to 9 minutes 

Co

Deep Freezing Time

 

Time compressor forced On during deep freeze 

0 to 99 minutes 

60 

AH

High Temperature Alarm

 

Temperature above setpoint where alarm is initiated 

0 to 50 F° (0 to 50 C°) 

10 

AL

Low Temperature Alarm

 

Temperature below setpoint where alarm is initiated 

-50 to 0 F° (-50 to 0 C°) 

-10 

Ad

Alarm Differential

 

Temperature difference between alarm On and Off 

1 to 9 F° (1 to 9 C°) 

At

Alarm Time Delay

 

Delay between alarm detection and activation 

0 to 99 minutes 

dF

Defrost Type

 

Select defrost type 

0 = electric heater 
1 = hot gas 

dE

Defrost End Mode

 

Defrost termination type; note that defrost cycle always 
ends after time set for 

dd

 

0 = time  
1 = temperature 

dt

Defrost Termination 
Temperature

 

Only used when 

dE

 = 1; defrost ends when 

temperature reaches 

dt

 

32 to 68°F (0 to 20°C) 

55 

di

Defrost Interval

 

Time between two subsequent defrost cycles; when 

di

=1 hour, 

dd

 

cannot exceed 40 min. 

1 to 99 hours 

dd

Maximum Defrost Duration

 

Defrost ends after this time, even if defrost end 
temperature has not been reached; 0 disables defrost 

0 to 99 minutes 

45 

dC

Dripping Time

 

Time compressor stopped after defrost so evaporator 
can drip 

0 to 99 minutes 

dU

First Defrost After Power Up

 

Time first defrost is delayed after power up 

OF

, 0 to 99 minutes  

OF

 (Off) 

dP

Display During Defrost

 

Temperature displayed during defrost cycle 

0 = last reading  
1 = setpoint 

dr

Display Delay After Defrost

 

Time after defrost before sensed temperature displays  1 to 99 minutes 

20 

iF

Binary Input Function

 

Configuration for normally closed binary input 

0 = none 
1 = compres. off, alarm on 
2 = alarm on 
3 = fan off, alarm on, 

AH

 

and 

AL

 disabled. 

id

Binary Input Time Delay

 

Time between binary input detection and enabling of 
the function set through 

iF

 

0 to 99 minutes 

FF

Fan Operating Function

 

Fan operation; note that the fan is always Off during 
the defrost cycle 

0 = parallel with compres. 
1 = always on 

Fd

Fan Start-up Delay (After 
Defrost)

 

Time after defrost that fan is switched On, even if 
temperature set through 

Fr

 has not been reached 

0 to 99 minutes 

Fr

Fan Start Temperature After 
Defrost End

 

Evaporator sensor temperature at which the fan is 
switched On after a defrost cycle 

-22 to 41°F (-30 to 5°C) 

40 

SF

Sensor Failure Operation

 

Control function after a sensor or sensor wire failure 

0 = compressor on  
1 = compressor off  
2 = based on last  4 cycles 

So

Temperature SensorOffset

 

Compensate for long sensor leads  

-20 to 20 F° (-20 to 20 C°) 

Un

Temperature Units Used

 

Temperature units used  

0 = °C 

1 = °F 

PU

Display Refresh Rate

 

Time after which display is refreshed 

1 to 99 seconds 