2.  Installation

(1)  Attach the duct adaptor to the indoor unit according to the following procedures.

< Procedures >

1

  Cut off the knockouts from the side plate using shears.

2

  Cut off the insulation (Polystyrene) along the notch using a knife or something similar.

3

  Remove burr after the cutting work.  (Be careful not to let swarf enter inside of the indoor unit.)

4

  Remove swarf after cutting off the insulation (Polystyrene).

Refrigerant Pipe
Side

Indoor Unit

Insulation

Side Plate

Knockout

Notch of Insulation 
(Polystyrene)

(Polystyrene)

  Do not insert the knife more than 1-3/16inch 

(30mm) into the insulation (Polystyrene) when 
cutting off the insulation.
Do not cut off the 

A

 part in Fig. 2.

  Do not use any tools which produce a lot of 

swarf such as a saw for the opening work. 
The drain pipe can become clogged and 
cause water leakage.

(2)  Place the insulation A and B to cover the entire gap between the side plate and the insulation (Polystyrene).  

Attach the insulation A to the left and right of the opening and the insulation B to the top and bottom of 
the opening.
Be careful not to cover the screw hole at the indoor unit side during placement.

Indoor Unit

Insulation A

Insulation B

Place the insulations to fit
the corner of the opening.

Insulation B

Insulation A

Perform this work correctly.  Otherwise, condensation may occur when cold air enters any gap left between 
the side plate and the insulation (Polystyrene).

 Fig. 1  Position of Insulation Placement

Insulation A

Insulation B

A

A

B

B

19/32

(15)

Do not cut off this part.  A

Insulation
(Polystyrene)

Side Plate

Insulation B

19/32

(15)

19/32

(15)

Insulation (Polystyrene)

Insulation A

Side Plate

B -B

Place the insulations to cover 
the entire gap between the 
side plate and the insulation 
(Polystyrene).

A - A

 Fig. 2  Cross Section of Insulation Placement

Unit: inch (mm)

3

Summary of Contents for PD-75A

Page 1: ... hazard levels are provided below with their respective signal words Indicates a hazardous situation that if not avoided will result in death or serious injury Indicates a hazardous situation that if not avoided could result in death or serious injury Indicates a hazardous situation that if not avoided could result in minor or moderate injury Indicates information considered important but not haza...

Page 2: ...Side View from A Enlarged View from B B A Install the duct adaptor to the opposite side of the drain piping side Indoor Unit Refrigerant Pipe Side Unit inch mm Accessory Qty Purpose Duct Adaptor 1 Insulation A 2 For Covering Gap between Insulation and Side Plate Insulation B 2 Insulation 1 For Prevention of Condensation Screw M4 x 13 32 10 Truss 4 For Installation 2 ...

Page 3: ... and cause water leakage 2 Place the insulation A and B to cover the entire gap between the side plate and the insulation Polystyrene Attach the insulation A to the left and right of the opening and the insulation B to the top and bottom of the opening Be careful not to cover the screw hole at the indoor unit side during placement Indoor Unit Insulation A Insulation B Place the insulations to fit ...

Page 4: ...parts from the band for the flexible duct to the resin part of the duct adaptor with the insulation Tighten the band to secure the flexible duct Field Supplied Tightening Torque 108 ft lbs 147 N cm Fixing Plate Indoor Unit Screws Four Duct Adaptor Upper Surface Wrap the flexible duct with the insulation so it touches the indoor unit ...

Reviews: