background image

Figure 1: Nurses Station Display Mounting

Wiring

Important: 

Do not apply voltage to the RS-485

output, BACnet

®

 output, analog output, or control

output. Severe damage may occur to the unit if

voltage is applied.

Important: 

Do not connect more than 24 VAC to any

terminal.

Important: 

Use copper conductors only. Make

all wiring in accordance with local, national, and

regional regulations.

Important: 

Do not exceed the unit’s electrical

ratings. Exceeding the unit’s electrical ratings can

result in permanent damage to the modules and void

any warranty.

Important: 

Run all low-voltage wiring and cables

separate from all high-voltage wiring. Shielded

cable is strongly recommended for input (sensor)

and analog output cables that are exposed to high

electromagnetic or radio frequency noise.

Important: 

Electrostatic discharge can damage

the unit. Use proper Electrostatic Discharge (ESD)

precautions during installation and servicing to avoid

damaging the unit.

Important: 

Do not connect supply power to the unit

before checking all wiring connections. Short circuits

or improperly connected wires can result in damage

to the unit and void any warranty.

Wiring Recommendations

Use 18 to 22 AWG (1.0 to 0.6 mm diameter) stranded wire.
Follow good wiring practices:
• Control cables should cross power cables at a 90-degree

angle.

• Use a consistent color code to maintain polarity.

• Use a series configuration (daisy-chain wiring) for

connecting the NSD to room pressure monitors and

controllers.

Wiring Procedure

1. Remove the connectors from the back of the NSD.
2. See Figure 2 for proper wiring installation. If

additional options need to be wired, refer to

building prints for the proper wiring diagram.

Figure 2: Modbus Communications Wiring between

RPM1600 Series Room Pressure Monitors,RPC1611 Room

Pressure Controllers, and NSD1380 Nurses Station Display

Important: 

Wire the NSD exactly as the wiring

diagram shows. Making modifications to the

wiring may severely damage the unit.

Important: 

Use MS-BACEOL-0 end-of-line (EOL)

terminations if the installed device is the last

device in the communications chain. The 100

Ohm reference resistors are optional.

3. Plug the connectors back into the NSD.
4. Carefully push the wires into the electrical box and

mount the NSD. Install four screws to hold the NSD

firmly to the base.

5. Press the cover plate onto the NSD1380 Nurses

Station Display.

Result

If you need assistance installing the system, call Johnson

Controls customer service at 1-800-275-5676.

NSD1380 Nurses Station Display

technical specifications

Table 2: NSD1380 Nurses Station Display

Specification

Description

Communications Protocol

Modbus

®

 RTU 9600 baud

Input Power

24 VAC, 50/60 Hz, 3 VA;

15 to 40 VDC; 5 watt maximum

Pluggable Screw Terminal
Blocks

18 to 22 AWG (1.0 to 0.6 mm diameter)

Maximum Device Monitor
Count

8 Room Monitors/Controllers on Modbus
communications bus

Operating Conditions

32 to 120°F (0 to 50°C), 10 to 90% RH (non-condensing)

Storage Conditions

-22 to 122°F (-30 to 50°C), 95% RH maximum (non-
condensing)

Dimensions

Mounting: triple-gang, standard-depth electrical box

7 in. x 4-7/8 in. x 1-3/4 in. (17.8 cm x 12.4 cm x 4.4 cm)

Protrusion: 5/8 in. (1.6 cm) Weight: 14 oz. (0.40 kg)

LCD Screen: 4.5 in. diagonal color display

Compliance

FCC Part 15, SubPart B: Class AICES-003, Issue 5: 2012:
Class ACE: EN 55011:2009 + A1: 2010 – Group 1EN 61326-1:
2006 – Class A

Metasys 

System

Compatibility

Tested on 

Metasys

 Release 6.5, 7.0, and 8.0

NSD1380 Nurses Station Display Installation Guide

2

Reviews: