Part No. 24-11256-00007, Rev. —
9
NS8000 Series
Technical specifications
Supply voltage
9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus)
Current consumption
Base current draw (all models)
3 mA maximum (non-transmitting)
CO
2
models
25 mA maximum additional current (during measurement)
Display models - backlight on
30 mA additional current
Note:
SA bus applications are limited to a power load of 210 mA. The best practice when configuring
an SA bus is to limit the total available operating power consumption to 120 mA or less. This power
level allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710
Local Controller Display to the bus for commissioning, adjusting, and monitoring.
Terminations
Modular jack and
screw terminal block
Network sensor addressing All models
DIP switch set from 199 to 206; factory set at 199
Wire size
Modular jack models
24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted
pair (six conductors)
Screw terminal block models
18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG
(0.6 mm diameter)
Communication rate
Auto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
Temperature measurement range
32.0°F/0°C to 104°F/40°C
Temperature sensor type
Digital temperature sensor
Humidity sensor type
Thin film capacitive sensor
Ambient conditions
Operating
32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing;
85°F (29°C) maximum dew point
Storage Display models
-40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing
Non-display models
-40°F to 185°F (-40°C to 70°C); 5% to 95% RH, noncondensing
Temperature resolution
±0.5°F/±0.5°C
Temperature accuracy
NS Series Network Zone
Sensor
±1°F/±0.6°C
Temperature element only
±0.36°F/±0.2°C at 70°F/21°C
Humidity element accuracy NSB8BPN24x-0 models
±2% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±4% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F
(10°C to 35°C)
NSB8BHxxxx-0 models
±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F
(10°C to 35°C)
CO
2
sensor accuracy
Accuracy
±30 ppm ±3% of CO
2
reading at 77°F (25°C) and 978 hPa
(1,000 ft/300 m)
Temperature dependence
±1.4 ppm/°F (± 2.5 ppm/°C)
Pressure dependence
See Table 3 for CO
2
altitude compensation.
Time constant
10 minutes nominal at 10 fpm airflow
Default temperature setpoint adjustment range
50°F/10°C to 86°F/30°C in 0.5° increments
CO
2
sensor
Operating
32°F to 122°F (0°C to 50°C)
Compliance
United States
UL Listed, File E107041, CCN PAZX,
Under UL 60730-1, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Canada
cUL Listed, File E107041, CCN PAZX7,
Under CAN/CSA E60730-1, Signal Equipment
Industry Canada, ICES-003
Europe
CE Mark – Johnson Controls declares that this product is in
compliance with the essential requirements and other relevant
provisions of the EMC Directive and RoHS Directive.
Australia and New Zealand
RCM Mark, Australia/NZ Emissions Compliant
China
RoHS2