Replacing a TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless Receiver
Connected to a VMA Controller
To replace a TE-7710-0 Series Wireless Transmitter and
TE-7720-0 Wireless Receiver connected to a VMA
controller, or to convert the wired sensors used with the
VMA18 controller to wireless, complete the following
instructions .
Note:
The TE-7710-0 Series Wireless Transmitter and
TE-7720-0 Wireless Receiver
must both
be
replaced with aWRZ Series Wireless Sensor and
a WRZ7860-0 Series One-to-One Receiver. Refer
to the
WRZ Series Wireless Room Sensors
Product Bulletin (LIT-12011653)
for a complete
list of available WRZ Series Wireless Room
Sensors.
1. Disconnect the 6-foot interface cable connecting the
VMA controller and the TE-7720-0 Wireless Receiver.
2. Plug one end of the 6-foot interface cable into the
VMA18 socket labeled TSTAT.
3. Plug the other end of the 6-foot interface cable into
the 8-pin female socket of the single-socket adapter.
4. Plug the male end of the single-socket adapter directly
into the BTCVT.
5. Complete commissioning of the VMA18 controller and
disconnect the BTCVT.
Note:
Sensor point information such as temperature,
setpoint, and occupancy is not available during
commissioning.
6. Install the WRZ Series Wireless Sensor and a
WRZ7860-0 Series One-to-One Receiver in the same
locations as the previous sensor and receiver. Refer
to the
WRZ Series Wireless Room Sensors
Installation Instructions (Part No. 24-10332-2)
and
the
WRZ-7860-0 Installation Instructions (Part No.
24-10563-47)
.
7. Plug the 6-pin male jack on the adapter into the
WRZ7860-0 receiver.
Note:
When using an WRZ Series Sensor with screw
terminal block terminations, refer to the wiring
diagram in the installation instructions for the
applicable WRZ Series Sensor model.
TE-700 Series Sensor Connected to a VMA
Controller
To replace a TE-700 Series Sensor with a TE-730 Series
Sensor, follow the instructions in
Replacing a TE-700
Series Sensor
.
To reuse a TE-700 Series Sensor connected to a VMA
controller, follow the instructions in
Reusing a TE-700
Series Sensor
.
Replacing a TE-700 Series Sensor
Replace a TE-700 Series Sensor with a TE-730 Series
Sensor. No cable adapters are required for this scenario.
Note:
Refer to the
TE-730 Series Sensor Installation
Instructions (Part No. 24-10674-0)
to install the
TE-730 Series Sensor.
Reusing a TE-700 Series Sensor
See the instructions in this section to reuse a TE-700
Series Sensor when connected to a VMA18 controller.
1. Disconnect the 8-pin male jack plugged into the VMA
controller.
2. Plug the 8-pin male jack on the Y adapter (
Figure 10
)
provided with the VMA controller into the 8-pin female
socket labeled TSTAT on the VMA18 controller.
3. Plug the 8-pin male jack that was plugged into the
VMA controller into the 8-pin female socket of the Y
adapter.
Note:
The 6-pin connection is not used for this
scenario and it should remain unconnected.
4. Refer to the
TE-730 Series Sensor Installation
Instructions (Part No. 24-10674-0)
to install the
TE-730 Series Sensor.
Figure 12: Y Adapter at Controller Location
17