Sensor Replacement and Reuse
Scenarios
This section describes sensor replacement and reuse
scenarios for replacing a VMA1410, VMA1415, VMA1420,
or the VMA controller with VMA18 controllers.
See
Table 3
for a description of the most popular sensor
models used with the VMA1410, VMA1415, VMA1420,
and the VMA controllers, the sensor replacement and
reuse scenarios for that sensor model, and sensor
replacement and reuse instructions.
Important:
Complete all the steps in the
Mounting
section before following the instructions in
this section.
Table 3: Sensor Replacement and Reuse Scenarios
Instructions
Sensor Replacement and Reuse
Scenarios
Sensor Used With VMA1410,
VMA1415, VMA1420, VMA1440
Controller
Replacing a TE-6xxx Series Sensor
Replace a sensor with an NS Series
Sensor
TE-6xxx Series (see
TE-6xxx Series
Sensor Connected to VMA Controller
)
Note:
Replacing a TE-6xxx Series
Sensor is recommended over
reusing the sensor because it
provides a usable port at the
sensor location for
commissioning.
Reusing a TE-6xxx Series Sensor
Reuse a sensor, installing an adapter at
a VMA controller location
Replacing an AP-TMZ1600-0 Sensor
Connected to a VMA Controller
Replace a sensor with an NS Series
Sensor
AP-TMZ1600-0 (see
Replacing an
AP-TMZ1600-0 Sensor Connected to a
VMA Controller
)
Replacing a TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless
Receiver Connected to a VMA Controller
Replace with a WRZ Series Wireless
Sensor and a WRZ7860 Series
One-to-One Receiver
TE-7710-0 Series Wireless Transmitter
and TE-7720-0 Wireless Receiver (see
Replacing a TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless
Receiver Connected to a VMA Controller
)
Replacing a TE-700 Series Sensor
Replace a sensor with a TE-730 Series
Sensor
TE-700 Series (see
TE-700 Series Sensor
Connected to a VMA Controller
)
Reusing a TE-700 Series Sensor
Reuse a sensor
Sensor Replacement Scenario
Descriptions
TE-6xxx Series Sensor Connected to
VMA Controller
To replace a TE-6xxx Series Sensor with a functionally
equivalent NS Series Network Sensor, follow the
instructions in the
Replacing a TE-6xxx Series Sensor
section.
To reuse a TE-6xxx Series Sensor connected to a VMA
controller, follow the instructions in the
Reusing a TE-6xxx
Series Sensor
section.
Replacing the sensor with an NS Series Network
Sensor is preferred to reusing the TE-6xxx Series
Sensor
because the NS sensor allows for easier
controller commissioning. Be sure to use an NS sensor
with similar dimensions as the existing sensor in order to
match the original sensor installation.
Note:
If temporary occupancy is required for the
application on the TE-67xx and TE-68xx Series
Sensors, set the DIP switch positions on the back
of the sensor to down, up, and down. This setting
only applies to single and no setpoint controller
models (not dual setpoint controller models).
Refer to the
NS Series Network Sensors Product Bulletin
(LIT-12011574)
for a complete list of available NS Series
Network Sensors.
14
VMA1826/1832 VAV Controller Installation Instructions