12    Zone Terminal Installation Sheet

Use a large flat-head screwdriver and insert it in the bottom where the ZT
and mounting base come together.  Gently pry the ZT out of the mounting
base.  As you push the screwdriver in, the ZT slides up and then out.

REMOVAL

Figure 11:  Removing Mounted ZT

Removing a
Mounted ZT

Controls Group
507 E. Michigan Street
P.O. Box 423

Issue Date 0495

Milwaukee, WI   53201

Printed in U.S.A

Summary of Contents for METASYS Series

Page 1: ... 94 x 7 44 x 6 00 176 x 189 x 152 mm when mounted on the ENC100 Installation of the Zone Terminal must meet the following standards Ambient operating conditions 32 to 122 F 0 to 50 C 10 to 90 non condensing relative humidity 86 F 30 C maximum dew point Notes Do not mount the Zone Terminal on a vibrating surface The atmosphere must be free of corrosive chemical vapors that may damage electronic equ...

Page 2: ... HVAC PRO Rev 3 0 or later Refer to the HVAC PRO for Windows User s Manual Zone Terminal section If the ZT is connected 50 feet or less from the controller install 24 AWG 6 conductor telephone cable between the controller and the ZT If the ZT is connected up to 500 feet from the controller install 18 AWG wire The ZT requires 24 VAC Common and Zone Bus The Zone Bus and Common should be twisted pair...

Page 3: ...Zone Terminal Installation Sheet 3 Figure 2 Connecting the Zone Terminal FMK 102 AHU103 Controller Remote RLY100 50 conect2 M100C TE 6400 CBLCON 0 ...

Page 4: ...PUTS B INAR Y OU TPU TS BIN ARY INP UT A NA LOG INP U TS 1 2 3 4 5 6 1 2 3 4 ANA LOG INPUT S COM MON 15 VDC TO ZON E STA T B INA R Y OU TP U T 2 4V AC 1 2 3 4 5 6 15 VDC 2 4V AC T RA C S 24 V A C 1 2 3 4 5 6 C OM MO N C OM MO N C OM MO N 0 10V DC A NA LOG OUT P UT CONCT2 Connect ZT here Switch must be in normal position Connect STAT here Connect VAV UNT here Green LED Red LED Figure 3 Connecting R...

Page 5: ... 4 AN ALOG IN PU TS CO MM ON B I N A R YC O M 15 V D C C O M PWR I N 24V AC B IN A R YO U T P U T 2 4 V A C T O LO A D S 1 2 3 4 5 6 1 2 0 1 0 V D C A N A LO G O U TP U T A N A L O G O U T P U T C O M M O N O F F AS UNT101 0 TE 6400 Zone Terminal VAV UNT CONCT3J Figure 4 Remote Connect ZT to VAV UNT through the Zone Sensor CAUTION The ZT must be plugged into a 6 pin telephone type jack Plugging th...

Page 6: ...e Enclosure Kit ENC100 0 to the wall remove the top or bottom rectangular knockouts with a needle nose pliers depending on the end through which the wires will run KNOCKOUT Knock wire passage out on top or bottom Figure 5 Remove Knockouts Physical Installation of Wall Mountings and Bases Enclosure Kit and Base Installation ...

Page 7: ... Kit ENC100 0 to a flat surface or wall for direct connection of the ZT to an application specific controller Pull wire through before attaching standoffs and screws for the plastic base MT BASE Figure 6 Attaching the Enclosure Kit and Utility Mounting Base ...

Page 8: ...tallation Sheet Attach the base pulling the telephone jack type cord through the opening as shown below Plug the cord into the back of the ZT and snap the ZT into position ENCMTBAS Figure 7 Connecting and Mounting the ZT ...

Page 9: ...Zone Terminal Wall Mounting Base on the wall 2 Mark the three mounting hole locations and remove the base 3 Drill three holes for No 6 anchors not included and install the anchors for mounting the base 4 Thread the ZTU cable through the access hole in the back of the base 5 Secure the Wall Mounting Base to the wall with three No 6 screws 6 Plug the ZTU cable in the back of the ZTU and snap the ZTU...

Page 10: ...e Terminal Wall Mounting Base flush on the cover at eye level approximately 65 inches from the floor to top of ZT 2 Mark mounting holes 3 Mark cable hole 4 Drill three size 3 32 inch pilot holes for mounting the base 5 Drill 5 8 to 1 inch hole for cable 6 Mount the base to the UPM cover using three No 6 thread forming or sheet metal screws Use a No 6 x 3 4 inch screw for the top hole and two No 6 ...

Page 11: ...for more information Johnson Controls Panel Unit wires and configures units complete with accessories to your specifications The ZTU internal mounting bracket is also available Contact Panel Unit Poteau 3100 North Broadway P O Box 1088 Poteau OK 74953 918 647 2195 FAX 918 647 4895 Customer Service Bottom View of UPM ALA RM ztin2 ZT UNT Figure 10 Bracket for Mounting the ZTU Internally in the UPM M...

Page 12: ... the ZT and mounting base come together Gently pry the ZT out of the mounting base As you push the screwdriver in the ZT slides up and then out REMOVAL Figure 11 Removing Mounted ZT Removing a Mounted ZT Controls Group 507 E Michigan Street P O Box 423 Issue Date 0495 Milwaukee WI 53201 Printed in U S A ...

Reviews: