Technical specifications

M9300 Series Switch Kits

Product Description

M9300-1 Switch Kit 

with one single-pole,

double-throw (SPDT) switch

M9300-2 Switch Kit

 with two SPDT

switches

Switch Rating

3 (0.5) A, 240 VAC

Electrical Connection

55 in. (1.4 m) halogen-free cable with
three 18 AWG (0.82 mm

2

) conductors and

1/4 in. (6 mm) ferrule ends

55 in. (1.4 m) halogen-free cable with
six 18 AWG (0.82 mm

2

) conductors and

1/4 in. (6 mm) ferrule ends

Ambient Conditions

Operating: 

-22°F to 140°F (-30°C to 60°C), 95% RH, noncondensing

Storage: 

-40°F to 185°F (-40°C to 85°C), 95% RH, noncondensing

Enclosure

NEMA 5/IP54

Compliance

United States:

UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical Controls for Household 

and Similar Use, Part 1; and UL 60730-2-14: Part 2, Particular Requirements for Electric Actuators. 

Plenum Rated (UL 2043). Suitable for use in Other Environmental Air Space (Plenum) in 

accordance with section 300.22 (c) of the National Electrical Code.

Canada:

UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic Electrical Controls for 

Household and Similar Use, Part 1; and CAN/CSA-E60730-2-14, Particular Requirements for 

Electric Actuators.

Europe:

CE Mark—Johnson Controls declares that this product is in compliance with the essential 

requirements and other relevant provisions of the Low Voltage Directive.
IEC 60730-1: Automatic Electrical Controls for Household and Similar Use, Part 1: General 

Requirements and IEC 60730-2-14, Automatic Electrical Controls for Household and Similar Use; 

Part 2—Particular Requirements for Electric Actuators

Australia and New Zealand:

 RCM Mark, Australia/NZ Emissions Compliant

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or 
misuse of its products.

Product warranty

This product is covered by a limited warranty, details of which can be found at
 

www.johnsoncontrols.com/buildingswarranty

.

Summary of Contents for M9300 Series

Page 1: ...0 uniquement pour commander des équipements dans des conditions normales de fonctionnement Lorsqu une défaillance ou un dysfonctionnement du servomoteur électrique risque de provoquer des blessures ou d endommager l équipement contrôlé ou un autre équipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon perm...

Page 2: ...es 5 See Figure 5 Allow a gap no larger than 2 5 mm 0 1 in between the switch kit and the face of the actuator coupler 6 To lock the conduit into the switch kit slide the conduit adaptor 1 over the cable 2 into the switch kit 3 and turn the conduit adaptor clockwise See Figure 6 7 Press down 1 and rotate the cam 2 to the required switch setting then release See Figure 7 Note Use a manual screwdriv...

Page 3: ...igure 3 Rotating the switch kit fully CCW 2 Figure 4 Installing the switch kit extender and switch kit to an M VA 9316 M VA 9320 or M VA 9335 Series Electric Actuator Cutouts Figure 5 Attaching the switch kit to the Electric Actuator 3 4 4 5 3 3 5 4 ...

Page 4: ...M9300 Series Switch Kits Installation Guide 4 Figure 6 Securing the conduit adaptor to the switch kit 3mm 3 2 1 Figure 7 Adjusting the dials for the switch kit 1 2 Figure 8 Attaching the plastic pointer ...

Page 5: ...he actuator 1 and pull back the tab 2 2 Remove the switch kit 3 from the actuator in the direction of the output axis 4 3 To remove the conduit adaptor insert a screwdriver into the slot 5 and turn the conduit adaptor counterclockwise 6 to unlock it Figure 9 Wiring diagrams Figure 10 Removing the switch kit and conduit adaptor 3mm 5 6 3mm 1 3mm 4 2 ...

Page 6: ... Listed CCN XAPX File E27734 to UL 60730 1 Automatic Electrical Controls for Household and Similar Use Part 1 and UL 60730 2 14 Part 2 Particular Requirements for Electric Actuators Plenum Rated UL 2043 Suitable for use in Other Environmental Air Space Plenum in accordance with section 300 22 c of the National Electrical Code Canada UL Listed CCN XAPX7 File E27734 to CAN CSA E60730 1 02 Automatic ...

Reviews: