Commissioning 

M9106-AGx-2N0x 

After wiring is completed, apply power to the controller 
and provide signals to the actuator to drive it at least 
one complete cycle open and closed. 

DPT-2015 

To commission the transmitter: 

1.  Perform the checkout procedure provided in the 

controller installation instructions, 

DPT-2015 

Differential Pressure Transmitter for VAV Box 
Applications Installation Instructions 
(Part No. 24-7547-18)

, to ensure proper operation 

of the transmitter. 

IMPORTANT: 

Perform commissioning when 

the transmitter is permanently mounted and 
operating at normal temperatures. 

2.  Set up and zero using HVAC PRO

 software 

when using a DPT-2015 with a Johnson Controls 
VAV Series controller. Refer to the 

Variable Air 

Volume Controller Technical Bulletin 
(LIT-6363040)

 for details. 

 

 

 

 

 

Troubleshooting 

M9106-AGx-2N0x 

If the actuator is not responding or working properly: 

 

Verify that the actuator assembly is properly 
secured to the duct. 

 

Check that all electrical connections are complete 
and power is applied. 

 

Verify that the damper fully opens and closes, 
using the gear release lever on the actuator. 

 

Check that the actuator stroke is set for the 
desired application. 

DPT-2015 

The DPT-2015 must be auto zeroed by a 
Johnson Controls VAV controller. If the DPT-2015 is 
not operating properly: 

 

Verify that the air lines on the DPT-2015 are 
connected to their respective high and low ports 
with no kinks in the tubing. 

 

Check the supply voltage to ensure it is within the 
14.5 to 17 VDC range and the polarity is correct. 

 

Disconnect the air lines from the high and low 
ports, and place a voltmeter across the OUT and 
GND terminals on the DPT-2015. If the output is 
not between 0.4 and 0.6 volts with power applied 
to the DPT-2015 in the vertical position, the 
transmitter is defective and should be replaced. 

Note: 

Voltage readings may vary by 0.1 volt if the 

transmitter is in the horizontal position. 

Repairs and Replacement 

Field repairs must not be made. For a replacement 
product or an accessory, refer to the 

M9106-AGx-2N0x 

Series Electric Non-Spring Return Actuators Product 
Bulletin (LIT-2681126).

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions

    5

 

Summary of Contents for M9106-AG 2N0 Series

Page 1: ...e sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuators The actuator may be mounted in any convenient orientation When installing the DPT 2015 Differential Pressure Transmitter on the actuator mount it so the tubing connecting the flow pick up device to the DPT 2015 creates a moisture trap This will prevent condensa...

Page 2: ...aft as shown in Figure 4 Figure 4 Damper Position Icons To set the actuator stroke proceed as follows 1 Grasp the damper shaft firmly with pliers and rotate the damper fully closed See Figure 5 Damper Shaft CCW to Close CW to Close Damper Blade Damper Figure 5 Damper Rotation 2 Press and hold the gear release lever shown in Figure 2 and rotate the actuator coupler to the fully closed position 3 Ma...

Page 3: ...upler to the minimum rotation position for the minimum ventilation flow required 2 Release the gear release lever 3 Use a Phillips screwdriver to loosen the end stop set screw that is closest to the stop gear Move the end stop set screw in its slot until it is tight against the stop gear See Figure 6 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operat...

Page 4: ...the end of rotation stall The 20 in 0 5 m CBL 2000 1 Wiring Harness accepted by Underwriters Laboratories Inc UL for plenum use is pre wired with the M9106 AGS 2N02 or may be ordered separately The plenum rated 20 in 0 5 m CBL 2000 2 and 72 in 1 8 m CBL 2000 3 Wiring Harnesses are also available See Table 1 Setup and Adjustments Air Pressure M9106 AGS 2N02 The flow pickup device provided with the ...

Page 5: ...power is applied Verify that the damper fully opens and closes using the gear release lever on the actuator Check that the actuator stroke is set for the desired application DPT 2015 The DPT 2015 must be auto zeroed by a Johnson Controls VAV controller If the DPT 2015 is not operating properly Verify that the air lines on the DPT 2015 are connected to their respective high and low ports with no ki...

Page 6: ...itions M9106 AGA 2N0x 32 to 125 F 0 to 52 C 90 RH maximum non condensing M9106 AGS 2N02 32 to 125 F 0 to 52 C 90 RH maximum non condensing 60 to 100 F 16 to 38 C 90 RH maximum non condensing For DPT rated accuracy see DPT 2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions Part No 24 7547 18 Ambient Storage Conditions 20 to 150 F 29 to 66 C 90 RH maximum non c...

Reviews: