Coupler Set

Screw

45°

Damper

Shaft

End-stop

Set Screws on

End Stops

(2 each)

90°

30°

Stop Gear

60°

10°

 

Figure 6: Setting the Rotation Range 

3.  Keeping the actuator parallel to the mounting 

surface, continue tightening the coupler set screw 

approximately 1/2 turn to achieve 150 to 180 lb∙in 

(17 to 20 N∙m) torque. 

4.  Press and hold the gear release lever, and turn the 

coupler by hand to ensure the damper rotates from 
end to end. 

Proceed to the 

DPT-2015 

section if needed. 

Less Than 90 Degrees 

If the damper shaft rotation is less than 90°, the stroke 
of the actuator has to be adjusted using the scale on 
the actuator. (See Figure 6.) 

Use the center of the coupler set screw as a pointer to 
observe the position on the scale when rotating the 
coupler from one side to the other. 

Examples: 

 

For a rotation range of 90°, set both end-stop 
set screws fully up as shown in Figure 6. 

 

For a rotation range of 60°, leave one end-stop 
set screw fully up, and adjust the other one, so the 
coupler rotates between the 30 and 90° indicator 
marks on the scale. 

 

For a rotation range of 45°, adjust both end-stop 
set screws, so the coupler rotates between 30 and 
75°. 

 

For a rotation range of 30°, move both end-stop 
set screws, so the coupler rotates between the 
30 and 60° indicator marks on the scale. 

To accurately set the end-stops: 

1.  Press and hold the gear release lever, and turn the 

actuator coupler to the minimum rotation position 
for the minimum ventilation flow required. 

2.  Release the gear release lever. 

3.  Use a Phillips screwdriver to loosen the end-stop 

set screw that is closest to the stop gear. Move the 
end-stop set screw in its slot until it is tight against 
the stop gear. (See Figure 6.) 

IMPORTANT: 

Do not remove the end-stop 

set screws, as this could interfere with the actuator’s 
operation. 

4.  Hand tighten the set screw so it remains in this 

position. 

5.  Secure the coupler to the shaft by using a crescent 

wrench or one of the tools from the Special Tools 
Needed section to tighten the coupler set screw 
against the damper shaft. (See Figure 6.) 

6.  Keeping the actuator parallel to the mounting 

surface, continue tightening the coupler set screw 

approximately 1/2 turn to achieve 150 to 180 lb∙in 

(17 to 20 N∙m) torque. 

7.  Repeat Steps 1 through 3 to set the desired 

maximum rotation position. 

8.  Use the Phillips screwdriver to tighten both 

end-

stop set screws to a minimum of 25 lb∙in 

(2.8 

N∙m). 

9.  Press and hold the gear release lever, and turn the 

coupler by hand to ensure the damper rotates from 
end to end. 

DPT-2015 

The M9106-AGx-2N housing has two mounting bosses 
for the DPT-2015. (See Figure 7.) Follow the 
procedure in the installation instructions included with 
the DPT-2015,

 DPT-2015 Differential Pressure 

Transmitter for VAV Box Applications Installation 
Instructions (Part No. 24-7547-18)

COM

CW

CCW

Mounting

Bosses

 

Figure 7: Location of the Mounting Bosses 

 

 

 

 

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions

    3

 

Summary of Contents for M9106-AG 2N0 Series

Page 1: ...e sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuators The actuator may be mounted in any convenient orientation When installing the DPT 2015 Differential Pressure Transmitter on the actuator mount it so the tubing connecting the flow pick up device to the DPT 2015 creates a moisture trap This will prevent condensa...

Page 2: ...aft as shown in Figure 4 Figure 4 Damper Position Icons To set the actuator stroke proceed as follows 1 Grasp the damper shaft firmly with pliers and rotate the damper fully closed See Figure 5 Damper Shaft CCW to Close CW to Close Damper Blade Damper Figure 5 Damper Rotation 2 Press and hold the gear release lever shown in Figure 2 and rotate the actuator coupler to the fully closed position 3 Ma...

Page 3: ...upler to the minimum rotation position for the minimum ventilation flow required 2 Release the gear release lever 3 Use a Phillips screwdriver to loosen the end stop set screw that is closest to the stop gear Move the end stop set screw in its slot until it is tight against the stop gear See Figure 6 IMPORTANT Do not remove the end stop set screws as this could interfere with the actuator s operat...

Page 4: ...the end of rotation stall The 20 in 0 5 m CBL 2000 1 Wiring Harness accepted by Underwriters Laboratories Inc UL for plenum use is pre wired with the M9106 AGS 2N02 or may be ordered separately The plenum rated 20 in 0 5 m CBL 2000 2 and 72 in 1 8 m CBL 2000 3 Wiring Harnesses are also available See Table 1 Setup and Adjustments Air Pressure M9106 AGS 2N02 The flow pickup device provided with the ...

Page 5: ...power is applied Verify that the damper fully opens and closes using the gear release lever on the actuator Check that the actuator stroke is set for the desired application DPT 2015 The DPT 2015 must be auto zeroed by a Johnson Controls VAV controller If the DPT 2015 is not operating properly Verify that the air lines on the DPT 2015 are connected to their respective high and low ports with no ki...

Page 6: ...itions M9106 AGA 2N0x 32 to 125 F 0 to 52 C 90 RH maximum non condensing M9106 AGS 2N02 32 to 125 F 0 to 52 C 90 RH maximum non condensing 60 to 100 F 16 to 38 C 90 RH maximum non condensing For DPT rated accuracy see DPT 2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions Part No 24 7547 18 Ambient Storage Conditions 20 to 150 F 29 to 66 C 90 RH maximum non c...