M9102-AGA-2S and M9104-xGA-2S Series Electric Non-Spring Return Actuators Installation Instructions 

5

M9104-GGA-2S

The M9104-GGA Series Electric Non-Spring Return 
valve actuators require AC 24 V power and a DC 0(2) 
to 10 V or 0(4) to 20 mA controller input signal. These 
electric actuators include an integrated 48 in. (1.2 m) 
long cable. See Figure 10 for proper wiring.

M9104-GGA actuators are factory set for Direct Acting 
(DA) mode and for a DC 0 to 10 V input control signal. 
In DA mode, a minimum control signal drives the 
actuator to the full Counterclockwise (CCW) position, 
and a maximum control signal drives the actuator to the 
full Clockwise (CW) position.

For Reverse Acting (RA) operation, a minimum control 
signal drives the actuator to the full CW position and a 
maximum signal drives the actuator to the full CCW 
position.

To change the factory settings (DA, 0-10 V), remove 
the actuator cover and adjust the switches on the 
circuit board as shown in Figure 12.                  

Figure 10: M9104-GGA-2S Control Wiring 

Diagram

U

+

+

U

DC 0(4)...20 mA Control with

External Resistor

+

AC

 24 V

Y

DC 0(2)...10 V Control

DC 0(2)...10 V

~

2

BLK

AC 24 V

0(2)...10 V

3

4

1

RED GRY ORN

DC 0(4)...20 mA

AC

 24 V

Y

~

+

2

BLK

AC 24 V

0(2)...10 V

3

4

1

RED GRY ORN

DC 0(2)...10 V

DC 0(2)...10 V

!

CAUTION: Risk of Electric Shock. 

Disconnect power supply before making 
electrical connections to avoid electric 
shock.

!

CAUTION: Risk of Property Damage. 

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

IMPORTANT:

Make all wiring connections in 

accordance with local, national, and regional 
regulations. Do not exceed the electrical ratings of 
the M9102 or M9104 Series Electric Non-Spring 
Return Valve Actuator.

Figure 11: Feedback Signal Relative to the 

Rotation Range

90°

90°

0.0V

2.0V

10.0V

8.7V  7.3V 6.0V 4.7V 3.3V

10.0V

8.3V 6.7V 5.0V 3.3V 1.7V

75°

75°

60°

60°

45°

45°

30°

30°

15°

15°

Rotation Range

2-10V

Feedback

0-10V

Feedback

Direct

Acting

2-10V

Feedback

Reverse

Acting

0-10V

Feedback

0.0V 1.7V 3.3V 5.0V 6.7V 8.3V 10.0V

10.0V

8.7V

7.3V

6.0V

4.7V

3.3V

2.0V

F

IG

:f

d

b

k

Figure 12: M9104-GGA Factory Switch Setting

Summary of Contents for M9102-AGA-2S

Page 1: ...ator with an integrated 48 in 1 2 m long cable one No 10 self drilling sheet metal screw Special Tools Needed 5 16 in 8 mm square socket 2 Phillips screwdriver 3 8 in 10 mm 12 point socket drill with a 5 16 in 8 mm hex nut driver digital voltmeter or M9000 200 Commissioning Tool IMPORTANT Use this M9102 or M9104 Series Electric Non Spring Return Actuator only to control equipment under normal oper...

Page 2: ...1 13 32 36 1 3 32 28 2 13 16 71 4 3 32 104 5 5 32 131 2 1 4 57 2 1 16 52 1 1 4 32 25 32 20 Set Screw Radius Clearance Table 1 Accessories Order Separately Code Number Description DMPR KC003 7 in 178 mm Blade Pin Extension without Bracket for Johnson Controls Direct Mount Damper Applications DMPR KR003 Sleeve Pin Kit for Johnson Controls Round Dampers with a 5 16 in 8 mm Diameter Shaft M9000 200 Co...

Page 3: ...t and insert the No 10 self drilling sheet metal screw through the shoulder washer as illustrated in Figure 6 8 Place a 5 16 in 8 mm socket on the screw and use a drill and extension to drill the screw into the mounting surface Drive the screw until it is tight against the washer 9 Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to ...

Page 4: ...stall to avoid excessive wear or drive time on the actuator motor M9104 IGA 2S The M9104 IGA Series Electric Non Spring Return valve actuators require an AC 24 V input signal and work with a variety of controllers These electric actuators include an integrated 48 in 1 2 m long cable and have an auto shutoff feature to prevent excessive wear or drive time on the motor See Figure 8 and Figure 9 for ...

Page 5: ...04 GGA 2S Control Wiring Diagram U U DC 0 4 20 mA Control with External Resistor AC 24 V Y DC 0 2 10 V Control DC 0 2 10 V 2 BLK AC 24 V 0 2 10 V 3 4 1 RED GRY ORN DC 0 4 20 mA AC 24 V Y 2 BLK AC 24 V 0 2 10 V 3 4 1 RED GRY ORN DC 0 2 10 V DC 0 2 10 V CAUTION Risk of Electric Shock Disconnect power supply before making electrical connections to avoid electric shock CAUTION Risk of Property Damage ...

Page 6: ...GGA 2S AC 24 V 25 20 at 50 60 Hz 3 6 VA Class 2 SELV Class III Control Type M910x AGA 2S Floating Control without Timeout M9104 IGA 2S Floating or On Off Control with Timeout M9104 GGA 2S Proportional Control Input Signal M9102 AGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV M9104 AGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV without Timeout M9104 IGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV with T...

Page 7: ... Canada Actuator housing is Plenum Rated per CSA C22 2 No 236 UL 1995 Heating and Cooling Equipment European Union CE Mark EMC Directive 89 336 EEC Australia and New Zealand C Tick Mark Australia NZ Emissions Compliant Shipping Weight 1 0 lb 0 5 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these speciications consul...

Reviews: