M9102-AGA-2S and M9104-xGA-2S Series Electric Non-Spring Return Actuators Installation Instructions

2

Accessories

Mounting

To mount the actuator to a damper:

1.

Check that the damper blade is visually accessible, 
or its position is permanently marked on the end of 
the damper shaft, as illustrated in Figure 2.

2.

Grasp the damper shaft firmly with pliers and rotate 
the damper fully closed, as illustrated in Figure 3.

Figure 1: M9102 and M9104 Series Electric Non-Spring Return Actuator Dimensions, in. (mm)

F

IG

:a

ct

_

d

im

3/16

(5)

9/16

(14)

1-13/32

(36)

1-3/32

(28)

2-13/16

(71)

4-3/32

(104)

5-5/32

(131)

2-1/4

(57)

2-1/16

(52)

1-1/4

(32)

25/32

(20)

Set Screw

Radius

Clearance

Table 1:  Accessories (Order Separately)

Code Number

Description

DMPR-KC003

7 in. (178 mm) Blade Pin Extension 
without Bracket for Johnson Controls® 
Direct-Mount Damper Applications

DMPR-KR003

Sleeve Pin Kit for Johnson Controls 
Round Dampers with a 5/16 in. (8 mm) 
Diameter Shaft

M9000-200

Commissioning Tool that Provides a 
Control Signal to Drive 24 V On/Off, 
Floating, Proportional, and/or Resistive 
Electric Actuators

M9104-100

Connector for 3/8 in. (10 mm) flexible 
metal conduit

F

IG

:d

m

p

_

p

o

s

Figure 2: Damper Position Icons

Damper

Shaft

CCW to

Close

CW to

Close

Damper

Blade

Damper

F

IG

:d

m

p

_

ro

ta

t

Figure 3: Damper Rotation

Summary of Contents for M9102-AGA-2S

Page 1: ...ator with an integrated 48 in 1 2 m long cable one No 10 self drilling sheet metal screw Special Tools Needed 5 16 in 8 mm square socket 2 Phillips screwdriver 3 8 in 10 mm 12 point socket drill with a 5 16 in 8 mm hex nut driver digital voltmeter or M9000 200 Commissioning Tool IMPORTANT Use this M9102 or M9104 Series Electric Non Spring Return Actuator only to control equipment under normal oper...

Page 2: ...1 13 32 36 1 3 32 28 2 13 16 71 4 3 32 104 5 5 32 131 2 1 4 57 2 1 16 52 1 1 4 32 25 32 20 Set Screw Radius Clearance Table 1 Accessories Order Separately Code Number Description DMPR KC003 7 in 178 mm Blade Pin Extension without Bracket for Johnson Controls Direct Mount Damper Applications DMPR KR003 Sleeve Pin Kit for Johnson Controls Round Dampers with a 5 16 in 8 mm Diameter Shaft M9000 200 Co...

Page 3: ...t and insert the No 10 self drilling sheet metal screw through the shoulder washer as illustrated in Figure 6 8 Place a 5 16 in 8 mm socket on the screw and use a drill and extension to drill the screw into the mounting surface Drive the screw until it is tight against the washer 9 Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to ...

Page 4: ...stall to avoid excessive wear or drive time on the actuator motor M9104 IGA 2S The M9104 IGA Series Electric Non Spring Return valve actuators require an AC 24 V input signal and work with a variety of controllers These electric actuators include an integrated 48 in 1 2 m long cable and have an auto shutoff feature to prevent excessive wear or drive time on the motor See Figure 8 and Figure 9 for ...

Page 5: ...04 GGA 2S Control Wiring Diagram U U DC 0 4 20 mA Control with External Resistor AC 24 V Y DC 0 2 10 V Control DC 0 2 10 V 2 BLK AC 24 V 0 2 10 V 3 4 1 RED GRY ORN DC 0 4 20 mA AC 24 V Y 2 BLK AC 24 V 0 2 10 V 3 4 1 RED GRY ORN DC 0 2 10 V DC 0 2 10 V CAUTION Risk of Electric Shock Disconnect power supply before making electrical connections to avoid electric shock CAUTION Risk of Property Damage ...

Page 6: ...GGA 2S AC 24 V 25 20 at 50 60 Hz 3 6 VA Class 2 SELV Class III Control Type M910x AGA 2S Floating Control without Timeout M9104 IGA 2S Floating or On Off Control with Timeout M9104 GGA 2S Proportional Control Input Signal M9102 AGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV M9104 AGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV without Timeout M9104 IGA 2S AC 24 V 25 20 at 50 60 Hz Class 2 SELV with T...

Page 7: ... Canada Actuator housing is Plenum Rated per CSA C22 2 No 236 UL 1995 Heating and Cooling Equipment European Union CE Mark EMC Directive 89 336 EEC Australia and New Zealand C Tick Mark Australia NZ Emissions Compliant Shipping Weight 1 0 lb 0 5 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these speciications consul...