Johnson Controls LP-FXVMA Series Installation Instructions Manual Download Page 7

FXVMA Installation Instructions 

7

Setting the BACnet MS/TP MAC Address

The BACnet MS/TP MAC address switch sets a unique 
address for the FXVMA on the BACnet MS/TP bus. 

Set the BACnet MS/TP MAC address using the DIP 
switches on the face of the FXVMA. The address 
equals the sum of the numbers set to ON. For 
example, if the first (1), the third (4), and the fifth (16) 
DIP switches are set to ON, the device address is 21 
(1 + 4 + 16 = 21). Use addresses 1-128. See Figure 16.

Setting the End-of-Line (EOL) Switch

Move the End-of-Line (EOL) termination switch to its 
On position when the FXVMA is at the end of the 
daisy-chain of devices on the N2 or BACnet MS/TP 
bus; otherwise, leave it at its default Off position. See 
Figure 17

Troubleshooting

Use Table 5 to troubleshoot the FXVMA.  

Repair Information

If the FXVMA Variable Air Volume Box Controller fails 
to operate within its specifications, refer to the 

FXVMA 

VAV Box Controller Technical Bulletin (LIT-12011249)

 

for a list of repair parts available. 

Figure 17: EOL Switch

1

O
N

1

O
N

ON Position

OFF Position

E

O

L

_

S

w

it

c

h

.c

d

r

Table 5:  FXVMA Light-Emitting Diode (LED) 

Codes

LED

Description

Power

Green
On when powered
Off when not powered

Fault

Red
On during a reset 
Off when the application is loaded and 
operating correctly
Flashing when application is not 
operating correctly or when the 
application is in test mode

R/T 
(Supervisory)

Green
Flashes when FXVMA transmits data to 
a supervisor.
Turns off when the FXVMA receives 
data.

Summary of Contents for LP-FXVMA Series

Page 1: ...edded communication capability that enables the FXVMA to integrate into an N2 or BACnet Master Slave Token Passing MS TP depending on model network of a building automation system North American Emissions Compliance United States Canada Figure 1 FXVMA VAV Box Controller This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Ru...

Page 2: ...al Override button and turn the FXVMA coupler until it contacts the mechanical end stop at either the fully closed 90 boxes or fully open 45 and 60 boxes position Table 1 FXVMA Accessories Ordering Information Product Code Number Description Y64T15 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 1...

Page 3: ... assignments for the inputs and outputs vary according to the control application configuration Obtain the actual I O channel assignments from FX Builder Express or FX Builder The wiring connections for the inputs and outputs vary depending on the FXVMA application Universal Input Wiring Details The FXVMA features one Universal Input UI that you can configure to accept either a passive sensor an a...

Page 4: ... SENSOR Figure 5 Active Sensor Connection Powered by the FXVMA Ground Common Power Output ACTIVE SENSOR 15 IN ICOM UNIVERSAL FXVMA FIG ActiveSensorVMA Figure 6 Dry Contact Maintained Switch Connection MAINTAINED SWITCH DRY CONTACT N O or N C as required 15 IN ICOM UNIVERSAL FXVMA FIG dry contact Table 3 FXVMA Binary Output Description Terminal Label Function and Electrical Ratings Specifications O...

Page 5: ...ired 10 mA maximum output current or Binary Output 24 VAC triac When the binary output is activated OUTX is connected to OCOMX 30 VAC maximum output voltage 0 5 A maximum output current 40 mA minimum load current OCOMX Analog Output common Provides the signal common for Configurable Output terminals when the CO is configured for analog output operation Isolated from all other terminal commons or B...

Page 6: ... Bus Technical Bulletin LIT 12011034 Use Figure 14 to make the BACnet MS TP bus connections to the FXVMA BACnet MS TP devices including the FXVMA are networked together in a daisy chain configuration For runs up to 1 220 m 4 000 ft we recommend you use stranded 22 AWG twisted 3 conductor wire Avoid using solid wire when possible as it is prone to break when pulled Power Wiring Details The FXVMA re...

Page 7: ... BACnet MS TP bus otherwise leave it at its default Off position See Figure 17 Troubleshooting Use Table 5 to troubleshoot the FXVMA Repair Information If the FXVMA Variable Air Volume Box Controller fails to operate within its specifications refer to the FXVMA VAV Box Controller Technical Bulletin LIT 12011249 for a list of repair parts available Figure 17 EOL Switch 1 O N 1 O N ON Position OFF P...

Page 8: ...box damper shaft using single set screw and to duct with single mounting screw Actuator Rating 4 N m 35 lb in minimum Minimum shaft length 44 mm 1 3 4 in Dimensions Width 182 mm 7 2 in Length 182 mm 7 2 in Height 64 mm 2 5 in Center of Output Hub to Center of Anti Rotation Slot 160 mm 6 3 in Weight 0 86 kg 1 9 lb Compliance United States UL Listed File E107041 CCN PAZX UL 916 Energy Management Equ...

Reviews: