Johnson Controls LP-FXVMA Series Installation Instructions Manual Download Page 6

FXVMA Installation Instructions

6

Network Room Module (NRM) Wiring Details

The NRM connects to the Remote Display Bus of the 
FXVMA at the 4-terminal connection marked SENSOR. 
You can connect the NRM up to 30.5 m (100 ft) from 
the FXVMA.

Use Figure 13 to make the wiring connections between 
the FXVMA and the NRM. 

Supervisory Link Wiring Details

N2 Bus Wiring Details

The N2 bus is a communications network consisting of 
three wires carrying RT+, RT-, and REF signals. For 
more information on the N2 bus, refer to the

 N2 

Communication Bus Technical Bulletin (LIT-636018)

.

N2 devices, including the FXVMA, are networked 
together in a daisy-chain configuration. For runs up to 
1,520 m (5,000 ft), we recommend you use stranded 
22 AWG, twisted 3-conductor wire. Avoid using solid 
wire when possible, as it is prone to break when pulled. 
The N2 bus may be extended to a maximum length of 
4,568 m (15,000 ft) using two repeaters.

Use Figure 14 to make the N2 bus connections to the 
FXVMA.

BACnet MS/TP Bus Wiring Details

The BACnet MS/TP bus is a communications network 
consisting of three wires carrying RT+, RT-, and REF 
signals. For more information on the rules of the MS/TP 
Communications Bus, refer to the 

MS/TP 

Communications Bus Technical Bulletin 
(LIT-12011034)

Use Figure 14 to make the BACnet MS/TP bus 
connections to the FXVMA. 

BACnet MS/TP devices, including the FXVMA, are 
networked together in a daisy-chain configuration. For 
runs up to 1,220 m (4,000 ft), we recommend you use 
stranded 22 AWG, twisted 3-conductor wire.  Avoid 
using solid wire when possible as it is prone to break 
when pulled.

Power Wiring Details

The FXVMA requires 24 VAC power. Use Figure 15 to 
make power wiring connections.   

Setup and Adjustments

Setting the N2 Address

The N2 address switch sets a unique address for the 
FXVMA on the N2 bus.

Set the N2 address using the DIP switches on the face 
of the FXVMA. The address equals the sum of the 
numbers set to ON. For example, if the first (1), the 
third (4), and the fifth (16) DIP switches are set to ON, 
the device address is 21 (1 + 4 + 16 = 21). Use 
addresses 3-255. See Figure 16. 

Figure 13: NRM Connection

RT+

RT- COM

PWR

LL -

LL +

SE
NS
O

R

COM

NETWORK ROOM 

MODULE

PWR

FXVMA

FI

G

: n

rm

c

o

n

n

e

c

ti

o

n

Figure 14: N2 or BACnet MS/TP Bus Wiring

SHLD

RT -

RT +

S

U

PER

VI
SOR

Y

 LI
N

K

TO NEXT N2 OR 

BACNET DEVICE

FROM LAST N2 OR 

BACNET DEVICE

COM

FXVMA

Figure 15: Power Wiring Connections 

HOT

COM

24

~

GROUND

480/277/240/
208/120/24/
24VAC

WHERE 2 OR MORE DEVICES

SHARE A SINGLE

TRANSFORMER, MAINTAIN

POLARITY (COM TO COM)

BETWEEN DEVICES

FXVMA

F

IG

: w

ir

ingc

on

ne

c

tio

n

s

Figure 16: Setting the DIP Switches to Address 21

128

 64

 32

 16

  8

  4

  2

  1

  

 O

N

F

IG:

F

XVMA

 Ad

d

re

ss

Summary of Contents for LP-FXVMA Series

Page 1: ...edded communication capability that enables the FXVMA to integrate into an N2 or BACnet Master Slave Token Passing MS TP depending on model network of a building automation system North American Emissions Compliance United States Canada Figure 1 FXVMA VAV Box Controller This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Ru...

Page 2: ...al Override button and turn the FXVMA coupler until it contacts the mechanical end stop at either the fully closed 90 boxes or fully open 45 and 60 boxes position Table 1 FXVMA Accessories Ordering Information Product Code Number Description Y64T15 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 1...

Page 3: ... assignments for the inputs and outputs vary according to the control application configuration Obtain the actual I O channel assignments from FX Builder Express or FX Builder The wiring connections for the inputs and outputs vary depending on the FXVMA application Universal Input Wiring Details The FXVMA features one Universal Input UI that you can configure to accept either a passive sensor an a...

Page 4: ... SENSOR Figure 5 Active Sensor Connection Powered by the FXVMA Ground Common Power Output ACTIVE SENSOR 15 IN ICOM UNIVERSAL FXVMA FIG ActiveSensorVMA Figure 6 Dry Contact Maintained Switch Connection MAINTAINED SWITCH DRY CONTACT N O or N C as required 15 IN ICOM UNIVERSAL FXVMA FIG dry contact Table 3 FXVMA Binary Output Description Terminal Label Function and Electrical Ratings Specifications O...

Page 5: ...ired 10 mA maximum output current or Binary Output 24 VAC triac When the binary output is activated OUTX is connected to OCOMX 30 VAC maximum output voltage 0 5 A maximum output current 40 mA minimum load current OCOMX Analog Output common Provides the signal common for Configurable Output terminals when the CO is configured for analog output operation Isolated from all other terminal commons or B...

Page 6: ... Bus Technical Bulletin LIT 12011034 Use Figure 14 to make the BACnet MS TP bus connections to the FXVMA BACnet MS TP devices including the FXVMA are networked together in a daisy chain configuration For runs up to 1 220 m 4 000 ft we recommend you use stranded 22 AWG twisted 3 conductor wire Avoid using solid wire when possible as it is prone to break when pulled Power Wiring Details The FXVMA re...

Page 7: ... BACnet MS TP bus otherwise leave it at its default Off position See Figure 17 Troubleshooting Use Table 5 to troubleshoot the FXVMA Repair Information If the FXVMA Variable Air Volume Box Controller fails to operate within its specifications refer to the FXVMA VAV Box Controller Technical Bulletin LIT 12011249 for a list of repair parts available Figure 17 EOL Switch 1 O N 1 O N ON Position OFF P...

Page 8: ...box damper shaft using single set screw and to duct with single mounting screw Actuator Rating 4 N m 35 lb in minimum Minimum shaft length 44 mm 1 3 4 in Dimensions Width 182 mm 7 2 in Length 182 mm 7 2 in Height 64 mm 2 5 in Center of Output Hub to Center of Anti Rotation Slot 160 mm 6 3 in Weight 0 86 kg 1 9 lb Compliance United States UL Listed File E107041 CCN PAZX UL 916 Energy Management Equ...

Reviews: