Releasing Applications
Abort Switches
B.3.1 ULI Abort Switch
A ULI Abort Switch has a standard UL-type delay timer that complies with UL Standard 864.
When an alarm initiates in the programmed releasing zone, the abort switch can be pressed while
the delay timer continues to count down, and held for as long as necessary. (If the abort switch is
pressed after the delay timer has expired, the abort switch has no effect.) Releasing the abort switch
starts a countdown by a 10-second ULI timer. When the 10-second ULI timer expires, the control
panel activates the releasing zone outputs.
Figure B.3 ULI Abort Switch
Release the Abort
Switch; the 10-second
ULI timer begins
Delay Time=15 sec.
Press and hold the
Abort Switch for 15
seconds
When the
10-seconds ULI
timer expires, the
10 sec
Program selections for this releasing zone
Total time from alarm initiation to
release:
5 + 15 + 10 = 30 seconds
Alarm
Delay Time: 15 seconds
Abort Switch: ULI
Cross Zone: N
Soak Time: 0
15 sec
15 sec
20 sec
5 sec
30 sec
5 sec
0 sec
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...