46
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Point Program
Module Point Programming (Control Module)
Pressing the
MORE
soft key at the Module Point Programming screen will display this screen if the
module type was control.
Figure 3.33 Module Point Programming Screen 2 (Control)
Soft Keys
ZONE MAP:
Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.33), with the exception of control modules
with the following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST:
This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default:
OFF
.
SWITCH INHIBIT:
This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default:
NO
SILENCEABLE:
This field determines whether the user can manually silence an activated output.
Values are as follows:
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 5 0
Z O N E M A P :
Z 0 0 0
, Z 1 0 4
, Z 1 0 5
, Z 1 0 6
, Z 1 0 7
Z 1 1 0
, Z 1 1 4
, Z 1 1 5
, Z 1 1 6
, Z 1 1 7
W A L K T E S T : O F F
L O C A L M O D E : O N
S W I T C H I N H I B I T : Y E S
A C C E P T
S I L E N C E A B L E : N O
B A C K
Zone Map Position 1 - Use for group zone
disable participation.
NOTE:
The following Type ID codes do not participate in Walk Test, and the
WALK
TEST
soft key will
not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL. FORM
C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET. The
M300MJmodule with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate in
Walk Test.
NO
Not manually silenceable
YES
-
RESOUND FIRE
Silenceable, resound on fire alarm events
Network and Local Resound
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...