background image

835966-UIM-A-0112

2

Johnson Controls Unitary Products

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle POE oils, and the higher pressures
of R-410A.

Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side restart.

All hoses must have a 700 PSIG service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

A liquid-line filter drier is required on every unit.

LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1. Limitations for the indoor unit, coil and appropriate accessories must

also be observed.

2. The outdoor unit must not be installed with any duct work in the air

stream. The outdoor fan is the propeller type and is not designed to
operate against any additional external static pressure.

3. The maximum and minimum conditions for operation must be

observed to assure a system that will give maximum performance
with minimum service.

4. This unit is not designed to operate with a low ambient kit. Do not

modify the control system to operate with any kind of low ambient
kit.

5. The maximum allowable line length for this product is 75 feet.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge and for service access. See Figure 1.

If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit.

Provide an adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended. 

1. Change-out of the indoor coil to an approved R-410A coil/ condens-

ing unit combination with the appropriate metering device.

2. Change-out of the line-set when replacing an R-22 unit with an

R410-A unit is highly recommended to reduce cross-contamination
of oils and refrigerants. 

3. If change-out of the line set is not practical, then the following pre-

cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots which might be serving as
oil traps. 

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possi-
ble. 

Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation. 

4. If the outdoor unit is being replaced due to a compressor burnout,

then installation of a 100% activated alumina suction-line filter drier
in the suction-line is required, in addition to the factory installed liq-
uid-line drier. Operate the system for 10 hours. Monitor the suction
drier pressure drop. If the pressure drop exceeds 3 psig, replace
both the suction-line and liquid-line driers. After a total of 10 hours
run time where the suction-line pressure drop has not exceeded 3
psig, replace the liquid line drier, and remove the suction-line drier.
Never leave a suction-line drier in the system longer than 50 hours
of run time.

Air Temperature DB 

at Outdoor Coil, °F

Air Temperature DB 

at Indoor Coil, °F

Min.

Max.

Min.

Max.

Cool

Heat

Cool

Heat

WB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

50

-10

115

75

57

50

1

1. Operation below this temperature is permissible for a short period of 

time, during morning warm-up.

72

80

For multiple unit installations, units must be spaced a minimum of 24
inches apart. (Coil face to coil face.)

NOTICE

 FIGURE 1: 

Typical Installation with Required Clearances

THERMOSTAT

NEC CLASS 1

WIRING

TO INDOOR
BLOWER

NEC CLASS 2
WIRING

TO COIL

WEATHERPROOF

DISCONNECT

SWITCH

24” SERVICE

ACCESS

CLEARANCE

NOTE:

ALL OUTDOOR WIRING MUST BE WEATHERPROOF

SEAL OPENINGS WITH
PERMAGUM OR EQUIVALENT

60” OVERHEAD
CLEARANCE

10” CLEARANCE
AROUND PERIMETER

Summary of Contents for HC8B Series

Page 1: ...ENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units are factory charged with refrigerant for the smallest rated indoor coil plus 15 feet of field supplied lines Matching indoor coils are available with a thermal expansion valve or an orifice liquid feed sized for the most common usage The orifice size and or refrigerant charg...

Page 2: ...o the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoor unit indoor coil and metering device all be replaced The following steps should be performed in order to insure proper system operation and performance Line set change out is also recommended 1 Change out of the indoor ...

Page 3: ...s to the coil air handling system or filter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rub ber insulation Armaflex or equivalent Liquid lines that will be exposed to direct sunlight and or high temperatures must also be insulated 5 Tape and suspend the re...

Page 4: ...r to the Tabular Data Sheet for proper vapor line siz ing 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the vapor service port connection After this connection has cooled remove the nitrogen source from the liquid fitting service port 7 Replace the Schrader core in the liquid and vapor valves 8 ...

Page 5: ... tighten and turn an additional 1 4 turn to seal Do not overtighten fittings 5 Install the liquid line to the top of the thermal expansion valve with fitting supplied with the liquid line Hand modify the liquid line to align with casing opening Hand tighten the liquid line and an addi tional 1 4 turn to seal 6 Install the TXV equalizer line into the vapor line as follows a Hand tighten the 1 4 SAE...

Page 6: ...Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge using the tabular data sheet if line length is greater than 15 feet 4 6 m 4 Total system charge item 1 item 2 item 3 5 Permanently stamp the unit data plate with the total amount of refrigerant in the system Use the following charging method whenever additional refrigerant is required for the system charge If a ca...

Page 7: ...over and service access panel removed in Steps 2 and 4 of the Field Connections Power Wiring section 4 All field wiring to be in accordance with national electrical codes NEC and or local city codes 5 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room air circulation Do not place it on an outside wall or where it is exposed to the radiant effect from exposed gl...

Page 8: ...n control is installed it is recommended that a mini mum air flow of 325 cfm ton be supplied at all times INDOOR CFM CONFIGURATION For proper system operation the indoor CFM must be set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions for the air handler...

Page 9: ...7 3803 KDQJH XHO MXPSHU RQ WKH KHDW SXPS FRQWURO WR 21 RQQHW 6HQVRU LW 2SWLRQDO 6 3DUW 1XPEHUV 6 3 XPSHU PXVW EH VHW WR 2 LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH HDW 2 LUVW 6WDJH HDW 80 DQ 6 7 68 3 E 7 50267 7 7KLUG 6WDJH HDW 5 9ROW RW 6HFRQG 6WDJH RPSUHVVRU 80 DXOW 9ROW RPPRQ XPSHU PXVW EH VHW WR 6 XPSHU PXVW EH VHW WR 73803 6XJJHVWLRQ 6HW VHWXS VWHS QG 6WDJH HDGEDQG DQG VWHS 0LQXWHV HWZHHQ VW DQG QG W...

Page 10: ...HW 6HQVRU 25 8 5 9 21752 6 1 67 7 3803 KDQJH XHO MXPSHU RQ WKH KHDW SXPS FRQWURO WR 21 RQQHW 6HQVRU LW 2SWLRQDO 6 3DUW 1XPEHUV 6 3 XPSHU PXVW EH VHW WR 2 LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH HDW 2 LUVW 6WDJH HDW 80 DQ 6 7 68 3 E 7 50267 7 7KLUG 6WDJH HDW 5 9ROW RW 6HFRQG 6WDJH RPSUHVVRU 80 DXOW 9ROW RPPRQ XPSHU PXVW EH VHW WR 6 XPSHU PXVW EH VHW WR 73803 6XJJHVWLRQ 6HW VHWXS VWHS QG 6WDJH HDGEDQG DQG...

Page 11: ...ompressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise HUM OUT 24 VAC out Humidifier EAC 24 VAC out Electronic Air Cleaner Jumper 1 must be set to HEAT PUMP Jumper 2 must be set to O Jumper 3 must be set to ELEC Setup Step 24 NUMBER Of Compressor Stages must be set 1 24VAC Humidifier Optional 24VAC Electrontic Air Cleaner Optional Part Number ...

Page 12: ...essor X L Malfunction Light O Reversing Valve Energized in Cool W1 OUT First Stage Heat Y2 OUT Second Stage Compressor R 24 Volt Hot C 24 Volt Common 24VAC Humidifier Optional 24VAC Electrontic Air Cleaner Optional Jumper 1 must be set to HEAT PUMP Jumper 2 must be set to O Jumper 3 must be set to ELEC Move the HUM STAT jumper to YES if humidistat is to be used Refer to AH documentation for W1 and...

Page 13: ...ch Open on Humidity Rise HUM OUT 24 VAC out Humidifier EAC 24 VAC out Electronic Air Cleaner 24VAC Humidifier Optional 24VAC Electrontic Air Cleaner Optional Move the HUM STAT jumper to YES if humidistat is to be used Refer to AH documentation for W1 and W2 electric heat staging options Jumper 1 must be set to HEAT PUMP Jumper 2 must be set to O Jumper 3 must be set to ELEC Change FFuel jumper on ...

Page 14: ...sing Valve Energized in Cool Change FFuel jumper on the heat pump control to ON Part Numbers SAP Legacy 126768 031 09137 18395 031 01996 340512 031 09178 1 1 Part Numbers SAP Legacy 265904 031 09169 2 C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor TWO STAGE VARIABLE SPEED FURNACE CONTROL G Fan TWO STAGE VARIABLE SPEED FURNACE W W1 First Stage Heat Y Y2 Second or Full Stage Compressor W2...

Page 15: ... jumper to YES if humidistat is to be used PV 8 9 ID MODELS F L 8 9 V YORKGUARD VI CONTROL G L 8 9 V YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve Energized in Cool L Malfunction Light Y2 Second Stage Compressor G Fan DN22H00124 DP22U70124 THERMOSTAT E W1 First Stage Aux Heat W2 Second Stage Aux Heat C 24 Volt Common Y First Stage Compressor O...

Page 16: ...gacy 159481 031 09157 2 COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Dehumidification Open on Humidity Rise VARIABLE SPEED AIR HANDLER CONTROL G Fan Move the MODE jumper to HP Move the HUM STAT jumper to YES if humidistat is to be used V...

Page 17: ...stem Type must be set to 12 3 Heat 2 Heat Pump Thermostat Installer Setup 0190 Changeover Valve must be set to 0 O B terminal Energized in Cooling Thermostat Installer Setup 0200 Backup Heat Source must be set to 0 Heat Pump Backup Heat Source is Electric AUX Auxiliary Heat 1 24VAC Humidifier Optional Part Numbers SAP Legacy 159481 031 09157 2 COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux He...

Page 18: ...d Stage Aux Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Modulating Heat Change FFuel jumper on the heat pump control to ON 1 Part Numbers SAP Legacy 1...

Page 19: ...8395 031 01996 340512 031 09178 1 PC 8 9 ID MODELS FC 8 9 C FL 8 9 C YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve Energized in Cool L Malfunction Light Y2 Second Stage Compressor G Fan DN22H00124 DP22U70124 THERMOSTAT E W1 First Stage Aux Heat W2 Second Stage Aux Heat C 24 Volt Common Y First Stage Compressor O B Reversing Valve L Malfunction...

Page 20: ... the OFF position Close the line power disconnect to the unit WITH POWER TO UNIT AND THERMOSTAT IN COOLING POSITION 1 In the cooling cycle discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evaporator 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous blower operation 3 With fan switch in AUTO position a circuit is ...

Page 21: ...ith Calgon Coilclean mix one part Coilclean to seven parts water Allow solu tion to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted surfaces 4 Refer to the furnace or air handler instructions for filter and blower motor maintenance 5 The indoor coil and drain pan should be inspected and cleaned reg ularly to prevent odo...

Page 22: ...835966 UIM A 0112 22 Johnson Controls Unitary Products SECTION XI WIRING DIAGRAM FIGURE 22 Wiring Diagram Single Stage ...

Page 23: ...835966 UIM A 0112 Johnson Controls Unitary Products 23 FIGURE 23 Wiring Diagram 2 Stage with PSC Outdoor Fan Motor ...

Page 24: ...d in U S A 835966 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 573328 UIM B 0311 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 24 Wiring Diagram 2 Stage with ECM Outdoor Fan Motor ...

Reviews: