SELECTION DATA
4-2
TC-16004-rev.2
4.2.2 Heating Capacity
■ Ducted Medium Static (EconoFresh): (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E
and (H,Y,C)IDM048B21E
Indoor Air Temp
(
o
F DB)
63
66
68
70
74
77
Outdoor Air
Temp (
o
F WB)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
21
26.7
26.7
26.8
26.8
26.5
26.3
25
28.1
28.1
28.1
28.1
27.7
27.4
29
29.4
29.4
29.4
29.4
28.9
28.5
33
30.7
30.7
30.7
30.7
30.1
29.5
37
32.1
32.1
32.0
32.0
31.2
30.6
41
33.4
33.4
33.4
33.3
32.4
31.7
43
34.1
34.0
34.0
34.0
33.0
32.3
47
35.4
35.4
35.3
35.3
34.0
32.3
51
36.8
36.7
36.7
36.3
34.0
32.3
55
38.6
38.1
37.2
36.3
34.0
32.3
59
38.6
38.1
37.2
36.3
34.0
32.3
21
31.4
31.4
31.5
31.5
31.2
30.9
25
33.0
33.0
33.0
33.1
32.6
32.2
29
34.6
34.6
34.6
34.6
34.0
33.5
33
36.2
36.1
36.1
36.1
35.4
34.7
37
37.8
37.7
37.7
37.7
36.7
36.0
41
39.3
39.3
39.2
39.2
38.1
37.3
43
40.1
40.1
40.0
40.0
38.8
38.0
47
41.7
41.6
41.6
41.5
40.0
38.0
51
43.3
43.2
43.1
42.7
40.0
38.0
55
45.4
44.8
43.8
42.7
40.0
38.0
59
45.4
44.8
43.8
42.7
40.0
38.0
21
42.4
42.4
42.5
42.6
42.1
41.7
25
44.6
44.6
44.6
44.6
44.0
43.5
29
46.7
46.7
46.7
46.7
45.8
45.2
33
48.8
48.8
48.8
48.8
47.7
46.9
37
51.0
50.9
50.9
50.9
49.6
48.6
41
53.1
53.0
53.0
53.0
51.5
50.4
43
54.2
54.1
54.0
54.0
52.4
51.2
47
56.3
56.2
56.1
56.1
54.0
51.2
51
58.4
58.3
58.2
57.7
54.0
51.2
55
61.2
60.5
59.1
57.7
54.0
51.2
59
61.2
60.5
59.1
57.7
54.0
51.2
Indoor
Unit
Model
030
036
048
TC: Total Capacity
NOTE:
Above values for (H,Y,C)IDM-B21E series indicates when unit’s air inlet is indoor air only.
Refer to Outdoor Unit Capacity Tables as actual performance data affected by indoor and outdoor unit
combination.
Summary of Contents for (H,Y,C)IDM030B21E
Page 2: ......
Page 10: ......
Page 49: ......
Page 50: ... 2016 Johnson Controls Inc TC 16004 rev 2 Code No LIT 12012293 Revised February 2018 ...