background image

 

 

 

 

Johnson Controls 

 

 

 

 

d.  7 RED FLASHES: This fault code indicates that the flame could not be established during 

three trials for ignition. The furnace will lock out for one hour and then restart. 

 

e.  8 RED FLASHES: This fault is indicated if the flame is lost five times (four recycles) during the 

heating cycle. The furnace will lock out for one hour and then restart. 

 

f.  9 RED FLASHES: Indicates reversed line voltage polarity, grounding problem, or reversed 

low voltage transformer wires. Both heating and cooling operations will be affected. The 

furnace will not start the ignition sequence until this problem is corrected. 

 

Diagnostics and Trouble Shooting Guide.

  This fault may be caused by one or more of the 

following, and each should be verified as to being either a potential cause or not: 

 

a.  Malfunctioning Gas Valve - Check for a leaking or slow-closing gas valve.  Correct for 

leaks and/or replace as necessary. 

b.  Gas supply irregularities such as momentary loss of gas supply, flame blowout– these 

failures result in a disruption in the flame and are typically sensed within 1.0 s. The gas 

valve de-energizes and the control begins a recycle operation. A normal ignition sequence 

begins after a 15 s inter-purge. If during the five recycles the gas supply does not return, 

or the fault condition is not corrected, the ignition control locks out for 60 min.

 

Check that 

the gas valve switch is in the ON position. Check for low or no gas pressure, faulty gas 

valve, dirty or faulty flame sensor, faulty hot surface ignitor, loose wires, or a burner 

problem. Verify natural gas input rate by clocking meter.  If clocked rate does not match 

the input rate from the unit nameplate, follow steps in the manual to adjust the manifold 

pressure.  In addition, examine the burner flames to make sure they are in good 

adjustment. Look to a pure blue flame with a light blue cone at its center that burns full, 

steady, and straight.  If yellow or orange, partial, diverted, or unsteady flame is detected 

then turn off gas valve and clean any debris from nozzles and burners.  If condition still 

exists then check airflow, venting, gas pressure, etc. If condition still exists, contact the 

Johnson Controls Field Service Support staff for further information and directions.   

c.  A momentary loss of power for 50 ms or longer during burner operation, - this will typically 

de-energize the gas valve. When the power is restored, the gas valve will remain de-

energized, and the ignition sequence will immediately restart.  Check the IGNITION 

CONTROL FLAME SENSE LEVELS.  Normal flame sense current is approximately 3.7 

microamps DC (

μ

a), Low flame signal warning starts at 1.5 microamps on most models. 

Low flame signal control lockout point is 0.5 to 0.1 microamps DC (

μ

a) depending on 

furnace model.   

d.  A faulty flame probe or flame probe circuit

 - 

verify field wiring to the unit is properly 

grounded, re-verify ground wires and conductor connectors are tight and secure.  Check 

polarity at furnace and branch.  Check that the flame probe exhibits proper electrical 

continuity and is not shorted to chassis.  Only clean flame sensor using 0000 fine steel 

wool.   

e.  Obstructions in the heat exchanger/exhaust venting system – Examine the heat 

exchanger, vent pipe, combustion air passages, vent connectors, and chimney to be sure 

they are clear and free of obstructions.  Note: proper orientation on the heat exchanger is 

for the compressed heat transfer blade portion to be up and away from the burner section 

(as shown in the image above) and if applicable, towards the add-on indoor coil cabinet.  

Summary of Contents for GG8S

Page 1: ...ls takes product safety seriously We provide safe and reliable products designed and manufactured to applicable quality and safety standards As an effort to improve consistency in diagnosing and resolving failures or faults related to Safety Controls and specifically to the high temperature limit controls as well as the flame proving sensor controls the following troubleshooting guide is being pro...

Page 2: ...ouble Shooting Guide This fault may be caused by one or more of the following and each should be verified as to being either a potential cause or not a A dirty filter check and replace as necessary b Improperly sized duct system or too many supply or return registers closed or blocked off check and open or balance supply and return airflow as necessary c Improper indoor blower motor speed selectio...

Page 3: ...to ensure proper combustion It helps protect the burner from buildup of gas without flame If the flame is not detected within 7 s of the gas valve opening the gas valve is shut off and a retry operation begins Also if the flame is lost for 2 s during the 10 s stabilization period the gas valve is shut off and a retry operation begins During a retry operation the vent motor starts a 15 s inter purg...

Page 4: ...ollow steps in the manual to adjust the manifold pressure In addition examine the burner flames to make sure they are in good adjustment Look to a pure blue flame with a light blue cone at its center that burns full steady and straight If yellow or orange partial diverted or unsteady flame is detected then turn off gas valve and clean any debris from nozzles and burners If condition still exists t...

Page 5: ... supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned E PRESSURE SWITCH This furnace is equipped with a pressure sensor in the burner compartment near the combustion blower This sensor monitors combustion airflow through furnace and piping systems If any of the conditions listed below are detected by the pressure sensor the contr...

Reviews: