background image

 

 

 

 

Johnson Controls 

 

 

 

f.  Obstructions in the heat exchanger / exhaust venting system – Examine the heat 

exchanger, vent pipe, combustion air passages, vent connectors, and chimney to be sure 

they are clear and free of obstructions.  Note: proper orientation on the heat exchanger is 

for the compressed heat transfer blade portion 

to be up and away from the burner section and 

if applicable, towards the add-on indoor coil 

cabinet.  If there are questions regarding the 

heat exchanger orientation, contact the 

Johnson Controls Field Service Support staff 

for further information and directions. 

g.  Incorrect firing rate - Verify natural gas input 

rate by clocking meter.  If clocked rate does not 

match the input rate from the unit nameplate, 

follow the steps in the manual to adjust the 

manifold pressure.  In addition, examine the 

burner flames to make sure they are in good 

adjustment. Look to a pure blue flame with a 

light blue cone at its center that burns full, 

steady, and straight.  If yellow or orange, 

partial, diverted, or unsteady flame is detected 

then turn off gas valve and clean any debris 

from nozzles and burners.  If condition still 

exists then check airflow, venting, gas pressure, etc. If condition still exists, contact the 

Johnson Controls Field Service Support staff for further information and directions.   

 

 

B. 

FLAME PROVING SENSOR

 – This sensor validates that there is flame present in the burner 

(flame allows for current flow) to ensure proper combustion.  It helps protect the burner from 

buildup of gas without flame.  If the flame is not detected within 7 s of the gas valve opening, the 

gas valve is shut off and a retry operation begins. Also, if the flame is lost for 2 s during the 10 s 

stabilization period, the gas valve is shut off and a retry operation begins. During a retry 

operation, the vent motor starts a 15 s inter-purge, and the ignitor warm-up time is extended to 27 

s. If the flame is established for more than 10 s after ignition during a retry, the control clears the 

ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace shuts down 

for 1 h. If at the end of the 1 h shut down there is a call for heat, the furnace initiates a normal 

start cycle. If the problem has not been corrected, the furnace locks out after three retries. 

Associated status/fault codes are CONTINUOUS / RAPID AMBER FLASH (not the same on all 

furnace models), 1 RED FLASH, 7 RED FLASHES, 8 RED FLASHES, or 9 RED FLASHES. 

 

a.  CONTINUOUS AMBER FLASH: Flame sense current is below .28 microamps. Check and 

clean flame sensor. Check for proper gas flow. Verify that current is greater than .28 

microamps at flame current test pad. 

 

b.  RAPID AMBER FLASH:  Flame sense current is below 1.5 microamps for more than 4.25 s 

after a successful trial for ignition. Check and clean flame sensor. Check for proper gas flow. 

Verify that current is greater than 1.5 microamps at flame current test pad. 

 

c.  1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. The 

control will turn on both the inducer motor and supply air blower.  

Summary of Contents for GG8S

Page 1: ...ls takes product safety seriously We provide safe and reliable products designed and manufactured to applicable quality and safety standards As an effort to improve consistency in diagnosing and resolving failures or faults related to Safety Controls and specifically to the high temperature limit controls as well as the flame proving sensor controls the following troubleshooting guide is being pro...

Page 2: ...ouble Shooting Guide This fault may be caused by one or more of the following and each should be verified as to being either a potential cause or not a A dirty filter check and replace as necessary b Improperly sized duct system or too many supply or return registers closed or blocked off check and open or balance supply and return airflow as necessary c Improper indoor blower motor speed selectio...

Page 3: ...to ensure proper combustion It helps protect the burner from buildup of gas without flame If the flame is not detected within 7 s of the gas valve opening the gas valve is shut off and a retry operation begins Also if the flame is lost for 2 s during the 10 s stabilization period the gas valve is shut off and a retry operation begins During a retry operation the vent motor starts a 15 s inter purg...

Page 4: ...ollow steps in the manual to adjust the manifold pressure In addition examine the burner flames to make sure they are in good adjustment Look to a pure blue flame with a light blue cone at its center that burns full steady and straight If yellow or orange partial diverted or unsteady flame is detected then turn off gas valve and clean any debris from nozzles and burners If condition still exists t...

Page 5: ... supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned E PRESSURE SWITCH This furnace is equipped with a pressure sensor in the burner compartment near the combustion blower This sensor monitors combustion airflow through furnace and piping systems If any of the conditions listed below are detected by the pressure sensor the contr...

Reviews: