FX70 Supervisory Controller Installation Instructions
19
Non-replaceable Parts
The controller contains a non-replaceable 2.5 A
slow-blow fuse, soldered on the main circuit board.
This fuse provides protection from internal shorts or
connection to incorrect power supplies. If the fuse
circuitry is suspect, contact technical support for
assistance.
Standard Replacement Parts
Table 5 lists the standard replacement parts. Standard
replacement parts cannot be returned for credit and
should be disposed of in an appropriate manner.
New Replacement Unit
To replace a faulty FX70, order a new one. To ensure
proper credit for a FX70 still under warranty, contact
the Johnson Controls Product Sales Operations Team
for return authorization.
Note:
Before ordering a new controller, it is strongly
recommended that you contact your normal technical
support resource to eliminate the possibility of a
software issue or mis-configuration problem.
Replacing the FX70 Supervisory Controller
To replace an FX70 with a new replacement unit,
proceed as follows:
1.
Use FX Workbench to back up the FX70
configuration to your computer.
2.
Remove power to the controller, including any
external 12 V battery. The unit should power down
automatically. Wait for all LEDs to remain off.
3.
Remove the front cover. See
4.
Note positions of all communications and other
wiring cables going to the controller. If necessary,
label connectors and accessory modules to avoid
mis-connection later, after the controller is
replaced.
5.
Unplug all Ethernet, serial, L
ON
W
ORKS
, modem,
and I/O connectors from the controller. Note the
position of installed option cards, if any. You must
transfer them to the replacement FX70.
6.
Remove the controller from its mounting (DIN rail,
panel mount tabs, or other).
7.
Remove any option cards from the old controller
and install them into the replacement FX70, if
applicable. See
9 for more details.
8.
Mount the replacement controller as it was
previously, using the same DIN rail location and/or
screws.
Table 5: FX70 Standard Replacement Parts
Part Number
Description
LP-KITFX7BAT-0
NiMH Battery Pack (see
LP-FX70EX1GB-0
1 GB DDR-2 333MHz Small Outline
Dual In-line Memory Module
(SODIMM) RAM (replacement part)
LP-KITFX7HW-0
Hardware Bag for FX70, containing
screw terminal connector plugs (two
6-position, one 2-position, earth
grounding wire).
!
WARNING: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections. Contact
with components carrying hazardous
voltage can cause electric shock and
may result in severe personal injury or
death.
AVERTISSEMENT: Risque de
décharge électrique.
Débrancher
l'alimentation avant de réaliser tout
branchement électrique. Tout contact
avec des composants conducteurs de
tensions dangereuses risque d'entraîner
une décharge électrique et de provoquer
des blessures graves, voire mortelles.
IMPORTANT:
Before handling circuit boards,
discharge any accumulated static by touching a
nearby earth ground. For details, see the