2. Set the DIP switches located on the back of the 

transmitter.  

For a 

mesh network application using an 

FX-ZFR1811 Router 

(Figure 5), set the 

DIP switches as indicated. Refer to the 

FX-ZFR Series Wireless Field Bus System 
Technical Bulletin (LIT-12011660) 

for information 

on commissioning multiple FX-WRZRMT10K-0 
Wireless Remote Temperature Transmitters in an 
FX-ZFR1800 Series Wireless Field Bus System.

a. Set the 

POWER

 switch to 

OFF

.

b. Set the 

MODE

 switch to 

Mesh

.

c. Set the 

PAN OFFSET

 switches according to 

the job or system plans. 

 

d. Set the 

ZONE

 DIP switches to match the 

Zone Number in the Facility Explorer Controller 
Configuration Tool (CCT) software. Each Zone 
Number corresponds to the SA Bus Address 
as shown in Table 1.  

e. Set the 

MSTP ADDRESS

 DIP switches to 

match the MS/TP address of the controller with 
which the transmitter is intended to 
communicate.

f.

Set the 

TRANSMIT LEVEL

 switch to 

10mW

.

For a 

non-mesh network, One-to-One 

application using an FX-WRZ7850-0 Receiver

 

(Figure 6), set the DIP switches as indicated, 
ensuring that the 

AREA

 and 

TRANSMITTER ID

 

switches on the FX-WRZ7850-0 Receiver and the 
FX-WRZRMT10K-0 Wireless Remote Temperature 
Transmitter(s) are set to the same value.

a. Set the 

POWER

 switch to 

OFF

.

b. Set the 

MODE

 switch to 

1 to 1

.

c. Set the 

SENSOR #

 to 

199

 for applications with 

only one transmitter per controller. Use the 
other settings for additional transmitters in 
applications with a single controller. Refer to 
the 

One-to-One Wireless Sensing System 

Technical Bulletin (LIT-12011663)

 for 

information on commissioning multiple 
FX-WRZRMT10K-0 Wireless Remote 
Temperature Transmitters in an 
FX-WRZ7850-0 One-to-One Wireless Room 
Temperature Sensing System.

d. Set the 

AREA

 switches to match the 

AREA

switch on the FX-WRZ7850-0 Receiver.

e. Set the 

TRANSMITTER ID

 switches to match 

the 

TRANSMITTER ID

 on the FX-WRZ7850-0 

Receiver.

3. Install two AA alkaline batteries (supplied) into the 

battery compartment on the back of the transmitter. 
Ensure that the batteries are installed in the proper 
polarity (Figure 7).

IMPORTANT:

Ensure that the 

PAN OFFSET

 is 

the same for each FX-ZFR1810 Coordinator, 
FX-FR1811 Router, and FX-WRZRMT10K-0 
Wireless Remote Temperature Transmitter in a 
mesh network.

Figure 7:  Back of FX-WRZRMT10K-0 Wireless 

Remote Temperature Transmitter Showing 

DIP Switches and Batteries

AA Alkaline Battery

AA A

lkalin

e Bat

tery

Insert two AA alkaline
batteries in battery
compartment.

F

IG

:b

ck_w

rz

_s

tr

00

00_

0

Place 
DIP switch 
overlay  
here.

Table 1:  Setting the ZONE DIP Switches

Zone Number

SA Bus Address

0

199

1

200

2

201

3

202

4

203

5

204

6

205

7

206

8

207

Summary of Contents for FX-WRZRMT10K-0

Page 1: ...ter or receiver The FX WRZRMT10K 0 Transmitter and associated TE 6300 Series Temperature Sensor are designed for indoor intra building applications only IMPORTANT The FX WRZRMT10K 0 Wireless Remote Temperature Transmitter is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to personal injury or property damage to...

Page 2: ...RMT10K 0 Wireless Remote Temperature Transmitter and the associated TE 6300 Series Temperature Sensor Special Tools Needed 1 16 in 1 6 mm Allen head adjustment tool Johnson Controls T 4000 119 order separately for the tamper resistant set screw that secures the transmitter to the mounting base 1 8 in 3 mm blade screwdriver for making wiring connections to the terminal block on the transmitter Comp...

Page 3: ...ent rooms and elevator shafts and concrete or brick walls between the transmitter and the FX ZFR1811 Router or FX WRZ7850 0 Receiver Do not mount the transmitter closer than 2 ft 0 61 m or farther than 100 ft 30 m from the FX ZFR1811 Router or 150 ft 45 m from the FX WRZ7850 0 Receiver The recommended indoor line of sight transmission range between the transmitter and the FX ZFR1811 Router is 50 f...

Page 4: ...he mounting surface by carefully twisting the base off of the surface 3 Remove the adhesive foam tape from the mounting base and clean the mounting base to remove any leftover adhesive Note New double sided adhesive foam tape is required to remount the base on the surface use Can Do National Tape Code No 99116 adhesive foam tape or its equivalent Connecting the TE 6300 Series Temperature Sensor to...

Page 5: ...ousing on its mounting base 1 Place the appropriate DIP switch overlay based on the application over the DIP switches See Figure 5 through Figure 7 IMPORTANT Do not power up the FX WRZRMT10K 0 Wireless Remote Temperature Transmitter until a receiver or controller is installed and operating within the same Radio Frequency RF range If this condition is not met the transmitter uses a higher than norm...

Page 6: ...Transmitter s are set to the same value a Set the POWER switch to OFF b Set the MODE switch to 1 to 1 c Set the SENSOR to 199 for applications with only one transmitter per controller Use the other settings for additional transmitters in applications with a single controller Refer to the One to One Wireless Sensing System Technical Bulletin LIT 12011663 for information on commissioning multiple FX...

Page 7: ...structions Part No 24 10563 20 for more information on testing signal strength Additional Product Information Table 2 includes Negative Temperature Coefficient NTC thermistor sensor temperature resistance response characteristics for the TE 6300 Series Temperature Sensor The values included in this table can be used to verify the accuracy of the temperature sensor in the field Note If another manu...

Page 8: ...he points based on the selections made in the Controller Selection screen The Zone temperature input point does not appear on the Point Assignment screen because this point is assigned to the SA Bus 10 Assign your points if needed Use the right arrow to assign a point to an object Use the left arrow to unassign a point from an object Use drag and drop functionality to move a point up and down the ...

Page 9: ... Probe Adjustable Enclosure TE 6361V 2 Johnson Controls 10k ohm Type II Thermistor Sensor 8 in 203 mm Duct Probe Flange Mount Enclosure TE 636GV 2 Johnson Controls 10k ohm Type II Thermistor Sensor 4 in 102 mm Duct Probe Flange Mount Enclosure TE 636S 1 Johnson Controls 10k ohm Type II Thermistor Sensor Strap Mount Probe FX WRZSST 110 Wireless Sensing System Tool For Use with an FX WRZRMT10K 0 Wir...

Page 10: ...ure Sensors Sensor Type 10k ohm Johnson Controls Type II Thermistor Sensor Sensor Thermal Characteristics See Table 2 Sensor Temperature Coefficient Nonlinear 10k ohm NTC Thermistor Electrical Connections 22 AWG 0 6 mm Diameter x 10 ft 3 m Long Plenum Rated Cable White Leads Probe Materials Stainless Steel Mounting Mount within 10 ft 3 m of the FX WRZRMT10K 0 Wireless Remote Temperature Transmitte...

Reviews: