Johnson Controls FX-PCX37 Installation Instructions Manual Download Page 9

Table 1: Termination Details

Termination Diagrams

Type of
Input/Output

Type of Field Device

UO

4–20 mA Output to Actuator

UO

Analog Output (Current)

UO

4–20 mA Output to Actuator

Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and Output Wiring Guidelines

Table 2

provides information and guidelines about the

functions, ratings, and requirements for the controller
input and output terminals; and references guidelines for
determining proper wire sizes and cable lengths.

In addition to the wiring guidelines in

Table 2

, observe

these guidelines when wiring controller inputs and
outputs:

Run

all

low-voltage wiring and cables separate from

high-voltage wiring.

All input and output cables, regardless of wire size or
number of wires, should consist of stranded, insulated,
and twisted copper wires.

Shielded cable is not required for input or output
cables.

Shielded cable is recommended for input and output
cables that are exposed to high electromagnetic or
radio frequency noise.

Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup.
Cable runs over 30 m (100 ft) may require an offset
in the input/output software setup.

9

FX-PCX37 Expansion Input/Output Module Installation Instructions

Summary of Contents for FX-PCX37

Page 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Page 2: ...el on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remove the cont...

Page 3: ...Figure 3 FX PCX3711 Physical Features 3 FX PCX37 Expansion Input Output Module Installation Instructions...

Page 4: ...ic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on config...

Page 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Page 6: ...iguration refer to the FX ZFR Wireless Field Bus Router Installations Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outp...

Page 7: ...2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 100 UI Dry Contact Binary Input UO or RO 24 VAC Binary Output Switch Low External Source U...

Page 8: ...iagrams Type of Input Output Type of Field Device UO 0 20 VDC Output to Actuator External Source UO 0 10 VDC Output to Actuator Internal Source UO UO UO Voltage Analog Output 8 FX PCX37 Expansion Inpu...

Page 9: ...in Table 2 observe these guidelines when wiring controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire siz...

Page 10: ...e B in Table 3 Analog Input Current Mode 4 20 mA Internal 100 ohm load impedance See Guideline A in Table 3 Analog Input Resistive Mode 0 600k ohm Internal 12 V 15k ohm pull up Qualified Sensors 0 2k...

Page 11: ...al national or regional electrical codes Normally Open Contact Connects OCOM to OUT NO when activated UL Listed 0 model only 1 4 hp 120 VAC 1 2 hp 240 VAC 360 VA Pilot Duty at 120 240 VAC B300 3 A Non...

Page 12: ...Current Mode 4 20 mA Requires an external load between 0 300 ohm Note The AO operates in Current Mode when connected to devices with impedances less than 300 ohm Devices that exceed 300 ohm may not op...

Page 13: ...37 m 450 ft twisted wire 0 8 mm 20 AWG stranded copper 91 m 300 ft twisted wire 0 6 mm 22 AWG stranded copper 61 m 200 ft twisted wire N A 24 AWG stranded copper N A See Figure 8 to determine cable le...

Page 14: ...d cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FCBUS 2 or SABUS 2 Signal Reference Com...

Page 15: ...h 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure t...

Page 16: ...ils under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of t...

Page 17: ...unication ring Blink 2 Hz Green SA FC BUS On Steady EOL switch in ON position Off Steady EOL switch in Off position Off Except on terminating devices Amber EOL Repair Information If a controller fails...

Page 18: ...nnected to Binary Outputs BOs or Configurable Outputs COs which can consume up to 12 VA for each BO or CO for a possible total consumption of an additional 48 VA maximum Power Consumption Operating 0...

Page 19: ...this product is in compliance with the EMC Directive and Low Voltage Directive Declared as Independently Mounted Intended for Panel Mounting Operating Control Type 1 B 4kV rated impulse voltage 100 7...

Page 20: ...nson Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc www johnsoncontrols com Published in U S A 20...

Reviews: