Table 7: FX-PCV1656 Controller Accessories (Order Separately)
Description
Product Code Number
3-position Screw Terminal that Plugs onto FX-PCV Output Point Spade Lugs
AP-TBK1003-0
Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown, Bulk Pack
AP-TBK4SA-0
Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk Pack
AP-TBK4FC-0
Replacement Power Terminal, 2-Position Connector, Gray, Bulk Pack
AP-TBK2PW-0
Bluetooth Commissioning Converter
FX-BTCVT-1
Cable Replacement Set for the FX-BTCVT-1 or the NS-ATV7003-0; Includes One 5 ft (1.5 m)
Retractable Cable
FX-BTCVTCBL-700
Local Controller Display
FX-DIS1710-0
Wireless Field Bus Coordinator, 10 mW Transmission Power. Functions with FX Supervisory
Controllers.
FX-ZFR1810-1
Wireless Field Bus Router, 10 mW Transmission Power. Functions with FX-PC Series Programmable
Controllers and FX-WRZ Wireless Sensors.
FX-ZFR1811-1
Portable BACnet IP to MS/TP Router
TL-BRTRP-0
One-to-One ZigBee Wireless Receiver for Wireless Sensor Only Applications
FX-WRZ7860-0
Wireless Sensing System Tool Kit
FX-WRZSST-120
USB Dongle with ZFR Driver provides a wireless connection through FX-PCT to allow wireless
commissioning of the wirelessly enabled FX-PCG, FX-PCA, FX-PCX, and FX-PCV controllers. Also
allows use of the FX-ZFR Checkout Tool (FX-ZCT) in FX-PCT.
Note:
The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle. For additional
information on the ZFR-USBHA-0 ZigBee dongle, refer to the
FX-ZFR Series Wireless Field
Bus System Technical Bulletin (LIT-12011660)
or
FX-ZFR Series Wireless Field Bus System
Quick Reference Guide (LIT-12011696).
ZFR-USBHA-0
Refer to the
FX-PC Series Programmable Controllers and Related Products Product Bulletin
(LIT-12011657)
for a complete list of available FX-PCX Expansion I/O Modules.
FX-PCX Series
Expansion Input/Output
Modules
Refer to the
NS Series Network Sensors Product Bulletin (LIT-12011574)
for a complete list of
available NS Series Sensors.
NS Series Sensors
Refer to the
FX-WRZ Series Wireless Room Sensors Product Bulletin (LIT-12011687)
for a complete
list of available FX-WRZ Series Wireless Sensors.
FX-WRZ Series Wireless
Sensors
Technical Specifications
Table 8: FX-PCV1656 Technical Specifications
FX-PCV1656-0:
Integrated Controller, Actuator,and Ball Valve Linkage: 3 UI, 2 BO,
24 VAC; FC and SA Bus
Product Code Numbers
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply
Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
Supply Voltage
10 VA typical, 14 VA maximum
Note:
The VA rating does not include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can
consume up to 12 VA for each BO or CO, for a possible total consumption of
an additional 60 VA (maximum).
Power Consumption
Operating:
0 to 50°C (32 to 122°F)
Storage:
-40 to 70°C (-40 to 158°F)
Ambient Conditions
11