Table 3: FX-PCA2611-0 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
Function, Ratings, Requirements
Terminal
Label
Terminal Block
Label
See Guideline
C
in
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Note:
The Analog Output (AO) operates in the Voltage
Mode when connected to devices with impedances
greater than 1,000 ohm. Devices that drop below
1,000 ohm may not operate as intended for Voltage
Mode applications.
OUTn
ANALOG
(Outputs)
Analog Output - Current Mode (4–20 mA)
Requires and external load between 0 and 300 ohm.
Note:
The Analog Output (AO) operates in the Current
Mode when connected to devices with impedances
less than 300 ohm. Devices with impedances
greater than 300 may not operate as intended for
Current Mode applications.
Analog Output Signal Common
for all Analog OUT
terminals.
Note:
All Analog Output Common terminals (OCOM
n
)
share a common, which is isolated from all other
commons.
OCOMn
See Guideline
C
in
Binary Output - 24 VAC Triac
(External Power Source)
Connects OUT
n
to OCOM
n
when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current
OUTn
BINARY
(Output)
Power Selection
Jumper positioned to
External (
EXT
) power.
Binary Output Common
(for OUT
n
terminal)
Note:
Each Binary Output Common terminal (OCOM
n
)
is isolated from
all
other commons, including other
Binary Output Common terminals.
OCOMn
15