Technical specifications
Table 9: FAC3613 Advanced Application Field Equipment Controller
Product Code Numbers
MS-FAC3613-0 Advanced Application Field Equipment Controller with Fast Persistence
Power Requirement
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Power Consumption
14 VA maximum
Note:
The VA rating does
not
include any power supplied to the peripheral devices
connected to binary outputs (BOs) or configurable outputs (COs), which can
consume up to 12 VA for each BO or CO; for a possible total consumption of an
additional 72 VA (maximum).
Power Source
+15 VDC power source terminals provide 100 mA total current. Quantity 2 located in
Universal IN terminals - for active (3-wire) input devices
Ambient Conditions
Operating:
0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing
Storage:
-40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
Controller Addressing for BACnet MS/TP
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255
are reserved and not valid controller addresses.)
Controller Addressing for N2
DIP switch set; valid control device addresses 1-254
Communications Bus
Selectable N2 or BACnet
®
MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and field controllers
4-wire SA Bus between field controller, network sensors and other sensor/actuator
devices, includes a lead to source 15 VDC supply power (from field controller) to bus
devices.
Processor
RX631 32-Bit Renesas
®
microcontroller
Memory
16 MB flash memory and 8 MB RAM
Real-Time Clock Backup Power Supply
Super capacitor maintains power to the onboard real-time clock for a minimum of 72
hours when supply power to the controller is disconnected.
Input and Output Capabilities
8 - Universal Inputs:
Defined as 0–10 VDC, 4–20 mA, 0–600k ohms, or Binary Dry Contact
6 - Binary Inputs:
Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
6 - Binary Outputs:
Defined as 24 VAC Triac (external power source only)
6 - Analog Outputs:
Defined as 0–10 VDC or 4–20 mA
Analog Input/Analog Output Resolution
and Accuracy
Input:
15-bit resolution
Output:
15-bit resolution, +/- 200 mV accuracy in 0–10 VDC applications
Terminations
Input/Output:
Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power:
4-Wire and 3-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port:
RJ-12 6-Pin Modular Jacks
Mounting
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on controller
Housing
Enclosure material:
ABS and polycarbonate UL94 5VB; Self-extinguishing
Protection Class: IP20 (IEC529)
Dimensions (Height x Width x Depth)
150 mm x 220 mm x 57.5 mm (5-7/8 in. x 8-3/4 in. x 2-3/8 in.) including terminals and
mounting clips
Note:
Mounting space requires an additional 50 mm (2 in.) space on top,
bottom, and front face of controller for easy cover removal, ventilation, and wire
terminations.
Weight
0.5 kg (1.1 lb)
FAC3613 Advanced Application Field Equipment Controller Installation Guide
23