To make use of this feature, ensure the DIP switches

are set to the desired address and wire the input

and output terminals. Apply power to the FAC

controller and connect to the device with either a

MAP Gateway or MS-DIS1710-0 Local Display to view

the points in the controller. The FAC controller will

report an Operational status even though there is

no true application loaded. CCT will not be able to

commission or upload the device as a result until

a true application is downloaded. The application

name displayed will be the address of the controller

followed by the model of the controller and “Default

State”.
For example, a FAC3613 controller whose DIP

switches are set to 8 would have the default state

application name of “8-FAC3613 Default State”.
The default state creates I/O points for all

connections on the input and output terminals.

It assumes all Universal Inputs (UIs) are Nickel

temperature sensors. The default state also takes

input from a Network Sensor at address 199. If there

is no connected Network Sensor, the startup of this

default state will be delayed by 30 seconds as the

controller attempts to establish connection with the

sensor.

Commissioning Controllers

You commission BACnet MS/TP controllers with the

(Controller Configuration Tool ) CCT software. The

controller can be connected using NxE Passthru,

Bluetooth (using BTCVT), or through MAP 4.2+/

BACnet Router (Mobile Access Portal (MAP) Gateway

at version 4.2 or above). Refer to 

Controller Tool

Help (LIT-12011147)

 for detailed information on

commissioning field controllers. Beginning at

CCT Release 13, the firmware package files are

orderable separately; they are not included with

CCT. They are obtained from the Metasys software

licensing portal, and are loaded and licensed on the

computer/server that is running CCT. .

Note: 

The MAP Gateway serves as a

replacement for the BTCVT, which is no longer

available for purchase, but continues to be

supported.

Firmware Package File

The MS-FCP-0 equipment controller firmware

package files are required for CCT to configure and

commission the controllers. The firmware package

files also allow you to upgrade an existing controller

to the latest firmware release available for that

controller.
Beginning at CCT Release 13, the firmware package

files are orderable separately; they are not included

with CCT. They are obtained from the 

Metasys 

software licensing portal, and are loaded and

licensed on the computer/server that is running

CCT.
For additional information about the firmware

package files, refer to the 

CCT Installation Instructions

(LIT-12011259)

.

Troubleshooting Controllers

Observe the Status LEDs on the front of the field

controller and see the table below to troubleshoot

the controller. To troubleshoot an integral or

local controller display, refer to the 

DIS1710 Local

Controller Display Technical Bulletin (LIT-12011270)

.

FAC3613 Advanced Application Field Equipment Controller Installation Guide

20

Summary of Contents for FAC3613

Page 1: ...nications The FAC3613 field controller can also be installed in a wireless application using a ZFR ZFR Pro Wireless Field Bus Router To configure these controllers to communicate using the wireless communications protocol see Configuring Wireless Communications Fast persistence The FAC3613 model has been significantly upgraded and now includes a fast persistence feature that allows you to retain d...

Page 2: ...ing surface M4 screws or 8 screws One 23 cm 9 125 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver for securing wires in the terminal blocks FAC3613 physical features Figure 1 FAC3613 Physical Features Table 1 Physical features Physical feature description and references 1 Analog Output AO Terminal Block Can be defined as Voltag...

Page 3: ...ely and evenly on the mounting surface Mount the controller in an area free of corrosive vapors and observe the ambient conditions requirements in Technical specifications Provide sufficient space around the controller for cable and wire connections easy cover removal and good ventilation through the controller 50 mm 2 in minimum on the top bottom and front of the controller Do not mount the contr...

Page 4: ...ns through the mounting clips 3 Drill holes in the wall or surface at the marked locations and insert appropriate wall anchors in the holes if necessary 4 Hold the controller in place and insert the screws through the mounting clips and into the holes or anchors Carefully tighten all of the screws Important Do not overtighten the mounting screws Overtightening the screws may damage the mounting cl...

Page 5: ... the FC Bus terminal function requirements and ratings see Figure 4 FC bus terminal block wiring Note The FC bus Shield SHLD terminal is isolated and can be used to connect daisy chain the shields for FC bus wiring SA bus terminal block The SA Bus terminal block is a brown removable 4 terminal plug that fits into a board mounted jack Wire the removable SA Bus terminal block plugs on the controller...

Page 6: ...dle terminal on the supply power terminal block See for more information about the Supply Power Terminal Block Figure 7 24 VAC supply power terminal block wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wiring details Important Connect 24 VAC supply powe...

Page 7: ...o maintain a closed 4 to 20 mA current loop See UI current loop jumpers See Guideline B in Table 3 Analog Input Resistive Mode 60 600k ohms Internal 12 V 15k ohms pull up Qualified Sensors 0 2k ohms potentiometer RTD 1k Nickel Johnson Controls sensor 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor See Guideline A in Table 3 INn Binary Input Dry Contact M...

Page 8: ...ote All Analog Output Common terminals OCOMn share a common which is isolated from all other commons One common screw terminal point is provided for every two output screw terminal points See Guideline C in Table 3 OUTn Binary Output 24 VAC Triac Class 2 24 V 500 mA External Power Source Connects OUTn to OCOMn when activated External Power Source Requirements 30 VAC maximum output voltage 0 5 A ma...

Page 9: ...hen wiring inputs and outputs Note Figure 8 applies to low voltage 30 V inputs and outputs only Figure 8 Maximum wire length for low voltage 30 V Inputs and Outputs by current and wire size Communications bus and supply power wiring guidelines The provides information about the functions ratings and requirements for the communication bus and supply power terminals The table also provides guideline...

Page 10: ...le or above SA Bus Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS SA PWR 15 VDC Supply Power for Devices on the SA Bus Maximum total current draw for SA Bus is 240 mA 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires Sensor Port SENSOR RJ 12 6 Position Modu...

Page 11: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI FAC3613 Advanced Application Field Equipment Controller Installation Guide 11 ...

Page 12: ...ion diagrams Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI FAC3613 Advanced Application Field Equipment Controller Installation Guide 12 ...

Page 13: ...y Contact Binary Input UI or BI 0 10 VDC Output to Actuator External Source CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO Current Output CO or AO 24 VAC Triac Output Switch Low External Source CO or AO FAC3613 Advanced Application Field Equipment Controller Installation Guide 13 ...

Page 14: ...grams Analog Output Current AO 4 20 mA Output to Actuator AO 4 20 mA Output to Actuator AO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Externally Sourced BO FAC3613 Advanced Application Field Equipment Controller Installation Guide 14 ...

Page 15: ...mental Control to Actuator Switch High Externally Sourced BO Network Stat with Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus FAC3613 Advanced Application Field Equipment Controller Installation Guide 15 ...

Page 16: ...Cnet MS TP To switch controller operating in N2 mode back into BACnet MS TP mode complete the following steps 1 Disconnect the 24 VAC supply from the controller 2 Set the address switches to the desired BACnet MS TP address For details about setting a device address see Setting the device address 3 Ensure the DIP switch 128 is set to OFF 4 Reconnect the 24 VAC supply to the controller 5 Using an S...

Page 17: ...eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address switches Switch 128 must be set to OFF for all hard wired SA and FC bus applications Figure 9 Device address DIP switch block set to address 21 Note Metasys field controllers ship with switch 128 ON and the remainining adress switches off rendering the controllers wired subordinate devices which do not operat...

Page 18: ...p into slots on the inside of the housing cover To remove the controller cover complete the following steps 1 Place your fingertips under the two cover lift tabs FAC3613 physical features on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the cover further to release it from the lower two latch...

Page 19: ...urrent loop jumper positions Set the current loop jumper to the Enabled position Figure 12 to connect an internal 100 ohms resistor across the UI terminals which maintains the 4 20 mA current loop circuit even when power to the controller is interrupted or off Important Current loop jumpers must be in the Disabled default position for all UIs that are not set up to operate as 4 20 mA analog inputs...

Page 20: ... MAP 4 2 BACnet Router Mobile Access Portal MAP Gateway at version 4 2 or above Refer to Controller Tool Help LIT 12011147 for detailed information on commissioning field controllers Beginning at CCT Release 13 the firmware package files are orderable separately they are not included with CCT They are obtained from the Metasys software licensing portal and are loaded and licensed on the computer s...

Page 21: ...and the ZFR1811 Wireless Field Bus Router Blink 2 Hz Download or Startup in progress not ready for normal operation SA BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Communication lost waiting to join communication ring FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady N...

Page 22: ...are also available Refer to the Series Y63 Y64 Y65 Y66 and Y69 Transformers Product Bulletin LIT 125755 AS XFR050 0 for more information Power transformer Class 2 24 VAC 50 VA maximum output no enclosure for more information AS CBLTSTAT 0 Cable adapter for connecting to 8 pin TE 6700 Series sensors AP TBK4SA 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack of 10 AP TBK4FC 0 Replacem...

Page 23: ... lead to source 15 VDC supply power from field controller to bus devices Processor RX631 32 Bit Renesas microcontroller Memory 16 MB flash memory and 8 MB RAM Real Time Clock Backup Power Supply Super capacitor maintains power to the onboard real time clock for a minimum of 72 hours when supply power to the controller is disconnected Input and Output Capabilities 8 Universal Inputs Defined as 0 10...

Page 24: ...ations are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswar...

Reviews: