FACTORY DEFAULT RESET

Follow the steps below to reset the EMCOMMS meter to factory default settings.  

Caution: Restoring factory default settings will reset 

all manual configurations, including customized address.

To Restore Factory Default Settings

1. Hold setup button down until all LEDs blink red (approximately 30 seconds) and release.
2. Momentarily press the setup button again within 5 seconds of the first release.
3. The LEDs will stop blinking and remain solid red for about 1 second.
4. Meter is now reset to factory default settings.

SPECIFICATIONS

(1) One side of transformer secondary is connected to signal common.  Dedicated transformer is recommended.
(2) CVT Accuracy based on reading, not full scale.

Power Supply Input

12-30VDC/24VAC

 (1)

, 1.5W max,100mA max.

Output

RS-485 2-wire, BACnet MS/TP, Modbus RTU, Modbus ASCII

Baud Rates 9600, 19200, 38400, 57600, 76800, 115200

RS-485 Loading 1/4 unit

Wiring Requirements

Conductor gauge 14-26 AWG

Terminal torque rating 0.4 ft-lb (0.55 N-m)

Pulse Inputs

Input Rating 3.5 +/- 0.5 VDC, short circuit current is 10mA max

Pulse Rate 50 Hz (default), configurable up to 500 Hz

Pulse Active <100 ohms

Pulse Undefined  100-1000 ohms

Pulse Idle >1000 ohms

Service Types

Configurations 1Ph, 2Ph, 3Ph Wye (4-Wire), 3Ph Delta (3-Wire)

Voltages 90VL-N through 600VL-L

Frequency 45-65 Hz

System Performance

Accuracy 1% for V, A, kW, kVAR, kVA

Current/Voltage Transducer

Accuracy

 (2)

300A Rating

800A Rating

1500A Rating

2400A Rating

6000A Rating

+/-1% 30-300A  (+/-3% >10A)

+/-1% 30-800A  (+/-3% >10A)

+/-1% 30-1500A  (+/-3% >10A)

+/-1% 50-2400A  (+/-3% >15A)

+/-1% 120-6000A  (+/-3% >40A)

Operating Environment

Temperature -4 to 140F (-20 to 60C)

Humidity 0-95% non-condensing

EMCOMMS Enclosure

Material Polycarbonate/ABS

Dimensions 4.1”h x 1.8”w x 0.9”d

CVT

 

Enclosure

Material Polycarbonate/ABS

Enclosure Dimensions 3.5”h x 1.6”w x 0.8”d

Small Rope Circumference

Medium Rope Circumference

Large Rope Circumference

Grande Rope Circumference

9”

15”

24”

36”

Compliance

U.S.A. UL Listed, File E501430

Canada UL Listed, File E501430

EMCOMMS Series Meter - Installation Instructions 

5

Building Efficiency

507 E Michigan Street, Milwaukee, WI 53202

Johnson Controls® is a registered trademark of Johnson Controls.

All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.

BACnet® is a registered trademark of ASHRAE

www.johnsoncontrols.com

Published in U.S.A.

Summary of Contents for EMCOMMS Series

Page 1: ...eding specified working voltage to prevent device failure which can result in personal injury or property damage WARNING Risk of Personal Injury Read understand and follow the instructions before installing this product All NFPA 70E requirements for safe work practices and for Personal Protective Equipment USA and other applicable local codes must be followed when installing this product Only qual...

Page 2: ... in mounting tabs Magnetic mount no drilling BIASING AND TERMINATION Use the jumpers to select the 120 ohm EOL resistor if EMCOMMS meter is the last device in your network If the meter is being installed within a network of other existing RS485 devices it may be necessary to use the 511 ohm biasing resistors based on your network or hardware requirments See Figure 4 EMCOMMS Meter Wiring for locati...

Page 3: ...reference point 12 to 30 VDC 1 5 W Typ 24 VAC Class 2 130 mA Max Isolated 1500 V rms Read instructions before installing 60 C Max on off P WER PRINT with technology address Pulse Inputs Johnson Controls ROG sensors only EMCOMMS 120 511 Ro Se Ba Se Ba R L1 L2 L3 A B C S T Device Status Line Status Setup RS485 Status Termination 4 3 5 C D Figure 12 EMCOMMS Meter Address Label BACNET NETWORK CONNECTI...

Page 4: ...LED RS485 Status LED EMCOMMS CVT Status LEDs R S T 2 1 Setup Bu on Line Status LED Device Status LED CVT Status LEDs RS485 Status LED R S T EMCOMMS DIAGNOSTIC CODES Diagnostic codes are presented one at at time using LED location color andsequencetoindicateaninstallationconcern A diagnostic code will repeat every 3 seconds until the user proceeds to the next diagnostic code or the meter returns to...

Page 5: ...e Rate 50 Hz default configurable up to 500 Hz Pulse Active 100 ohms Pulse Undefined 100 1000 ohms Pulse Idle 1000 ohms Service Types Configurations 1Ph 2Ph 3Ph Wye 4 Wire 3Ph Delta 3 Wire Voltages 90VL N through 600VL L Frequency 45 65 Hz System Performance Accuracy 1 for V A kW kVAR kVA Current Voltage Transducer Accuracy 2 300A Rating 800A Rating 1500A Rating 2400A Rating 6000A Rating 1 30 300A...

Reviews: