Installation and Maintenance
(4) Communication malfunction (E6)
Poor contact of any line
may lead to communication
malfuntion.
Is there incorrect match
between the main board and the
display panel or between the indoor
and outdoor boards?
Is there
incorrect connection?
Note:
1.Before replacing mainboard of indoor unit, make sure the
correct replacement is on hand
. The following tests
should
be done:
a.Check if protective tube FUSE 1 has open circuit. If so, replace it with a protective tube of the same model.
b.Energize the unit and check buzzer sound
s
. If not, the mainboard of indoor unit can’t be used.
c.Energize the unit with display and check if all icons are displayed after energization and if the display is normal. If not, the main board can’t
be used.
2.The mainboard for replacement shall has the same model with the original mainboard, so do the jumper cap.
3.The wiring and assembly methods shall also be the same with that of the original mainboard when replacing the mainboard.