1
6
Installation and Maintenance
NO. Malfunction
Name
Display Method of Indoor Unit
Display Method of
Outdoor Unit
(Indicator has 3 kinds
of display status and
they will be displayed
circularly every 5s.)
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
□OFF
■Illuminated
ƿ
Blink
Operation
Indicator
Cool
Indicator
Heating
Indicator
D5
(D40)
D6
(D41)
D16
(D42)
D30
(D43)
11
Indoor
evaporator
temperature
sensor is
open/short
circuited
F2
OFF 3S
and
blink
twice
AC stops operation once
reaches the setting
temperature. Cooling, drying:
internal fan motor stops
operation while other loads
stop operation; heating: AC
stop operation
1. Loosening or bad contact of
Indoor
evaporator temp. sensor and
mainboard terminal.
2. Components on the mainboard
fall
down leads short circuit.
3. Indoor evaporator temp. sensor
damaged.(check temp. sensor
value
chart for testing)
4. Mainboard damaged.
12
Outdoor
ambient
temperature
sensor is
open/short
circuited
F3
OFF 3S
and
blink
3 times
ƶ
ƶ
ƿ
Ƶ
During cooling and drying
operating, compressor stops
while indoor fan operates;
During heating operation, the
complete unit will stop operation
Outdoor temperature sensor
hasnt been connected well or
is damaged. Please check it by
referring to the resistance table for
temperature sensor)
13
Outdoor
condenser
temperature
sensor is
open/short
circuited
F4
OFF 3S
and
blink
4 times
ƶ
ƶ
ƿ
ƶ
During cooling and drying
operation, compressor stops
while indoor fan will operate;
During heating operation,
the complete unit will stop
operation.
Outdoor temperature sensor
hasnt been connected well or
is damaged. Please check it by
referring to the resistance table for
temperature sensor)
14
Outdoor
discharge
temperature
sensor is
open/short
circuited
F5
OFF 3S
and
blink
5 times
ƶ
ƶ
ƿ
ƿ
During cooling and drying
operation, compressor will sop
after operating for about 3 mins,
while indoor fan will operate;
During heating operation, the
complete unit will stop after
operating for about 3 mins.
1.Outdoor temperature sensor
hasnt been connected well or is
damaged. Please check it by
referring to the resistance table for
temperature sensor)
2.The head of temperature sensor
hasnt been inserted into the
copper tube
15
Limit/
decrease
frequency
due to
overload
F6
OFF 3S
and
blink
for 6
times
Ƶ
ƶ
ƿ
ƿ
All loads operate normally, while
operation frequency for
compressor is decreased
Refer to the malfunction analysis
(overload, high temperature
resistant)
16
Decrease
frequency
due to
overcurrent
F8
OFF 3S
and
blink
8 times
Ƶ
Ƶ
ƶ
Ƶ
All loads operate normally, while
operation frequency for
compressor is decreased
The input supply voltage is too
low;
System pressure is too high and
overload
17
Decrease
frequency
due to
high air
discharge
F9
OFF 3S
and
blink
9 times
Ƶ
Ƶ
ƶ
ƶ
All loads operate normally, while
operation frequency for
compressor is decreased
Overload or temperature is too
high;
Malfunction of electric expansion
valve (EKV)
18
Voltage for
DC bus-bar
is too high
PH
OFF 3S
and
blink
11 times
ƶ
Ƶ
ƶ
ƿ
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
operation.
1. Measure the voltage of position
L and N on wiring board (XT), if
the voltage is higher than 265VAC,
turn on the unit after the supply
voltage is increased to the normal
range.
2.If the AC input is normal,
measure the voltage of electrolytic
capacitor C on control panel (AP1),
if its normal, theres malfunction
for the circuit, please replace the
control panel (AP1)
19
Malfunction
of complete
units current
detection
U5
OFF 3S
and
blink
13 times
ƶ
Ƶ
ƿ
Ƶ
During cooling and drying
operation, the compressor will
stop while indoor fan will operate;
During heating operating,
the complete unit will stop
operation.
Theres circuit malfunction on
outdoor units control panel AP1,
please replace the outdoor units
control panel AP1.