background image

Figure 11. System Wiring Diagram for DH300PL Duct 
Smoke Detector with RTS451/RTS451KEY

TEST

RA400Z

RT

S451

KEY

COMMON

COM(+

)

COM(-)

RA400Z

COMMON

TEST

R

TS451

KEY

COM(+)

COM(-)

4

5

6

1

2

3

FIELD INSTALLED

   JUMPER

COMMON TEST

LED

RESET

FOR RTS451, TERMINAL 3 IS NOT USED.

(RTS451 DOES NOT HAVE A TERMINAL 6.)

FOR RTS451KEY, TERMINALS 3 AND 6

ARE NOT USED.

H0104-00

DH300PL

RTS451/RTS451KEY

J500-42-00 

I56-2198-003R

©2004 Johnson Controls, Inc.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this 

device must accept any interference received, including interference that may cause undesired operation.

Note:  This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 

provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if 

not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference 

will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the 

equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, 

the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local 

manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component 

of that system which fails shall be repaired or replaced as soon as possible.

Please refer to insert for the Limitations of Fire Alarm Systems

[10] Board Replacement
[10.1] Sensor Board Replacement

1.  Remove the two sensor board mounting screws.
2.  Pull gently on the board to remove it. 
3.  To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
4.  Secure board with the two mounting screws.

[10.2] Power Board Replacement

1.  Disconnect wiring from the terminal block.
2.  Remove the two power board mounting screws.
3.  Pull gently on the board to remove it. 
4.  To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
5.  Secure board with the two mounting screws.
6.  Re-connect wiring to terminal block.

[11] Model DH300PL Air Duct Smoke Detector Specifications 

Operating Voltage Range 

15 to 32 VDC

Standby Current 

300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Operating Temperature 

+32° to +131°F (0° to +55°C)

Storage Temperature 

–22° to 158°F (–30° to +70°C)

Humidity Range 

10% to 93% (non-condensing)

Air Velocity 

100 to 4000 ft/min (2.54 to 20.32 m/sec)

Dimensions 

14

3

⁄ 8

  L x 5

1

⁄ 2

 W x 2

3

⁄4

 D (37 cm L x 14 cm W x 7 cm D)

Programming Specifications/Requirements for Intelligent System Control Panels
There are a limited number of devices that can have their LEDs programmed to illuminate. The actual number of devices is determined by the control 
panel and its ability to supply LED current. Refer to the Control Panel Installation Manual for details.

 

Accessories 

 

 

 

 

 

Part No.

 

Remote LED 

 

 

 

 

 

RA400Z

 

Magnetic Remote Test  

 

 

 

 

RTS451

 

Key-Activated Remote Test   

 

 

 

RTS451KEY

 

Replacement Filters  

 

 

 

F36-09-11

 

Replacement Test Magnet 

 

 

 

 

M02-04-00

 

Replacement Photo Insect Screen 

 

 

 

S08-39-01

 

Replacement End Cap for Plastic Sampling Tube   

 

P48-61-00

 

Replacement End Cap for Metal Sampling Tubes   

 

P48-21-00 

 

Replacement Photoelectric Sensor Board 

 

 

A5053JCI

 

Replacement Power Board (w/o relay)   

 

 

A5067

Summary of Contents for DH300PL

Page 1: ...also a remote alarm output for use with auxiliary devices The DH300PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT The DH300PL Duct Smoke Detector consists of the following items See Figure 1 DH300PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Figu...

Page 2: ...emplate supplied Affix the template to the duct at the desired mounting location Make sure the tem plate lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 2 1 Sampling Tube Installation for Ducts Less Than 11 2 Feet Wide see Figure 2 1 Remove the front cover 2 Slide the plastic sampling tube into the housing bushing and extend it the full widt...

Page 3: ...12 ft 2 4 to 3 7 m ST 10 Must extend a minimum of 2 3 the duct width J500 42 00 3 I56 2198 003R SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK Figure 3 Installation of foam gaskets over sampling tube bushings Figure 5 Tube mounting configurations with varying air flow direction SAMPLING TUBE END CAP AIR HOLES ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Figure 4 Air duct detector sampli...

Page 4: ...ate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in the housing Solid conduit con nections may be used if desired Smoke detectors and alarm system control panels have specifications for Signaling Line Circuit SLC wiring Consult the control panel man...

Page 5: ...sing Aerosol Smoke This test is intended for low flow systems 100 500 FPM If the air speed is greater than 500 FPM use a conventional manometer to measure differ ential pressure between the sampling tubes as described in 9 1 1 Drill a 1 4 hole 3 feet upstream from the duct smoke detector With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray ae...

Page 6: ...nce exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests 9 2 1 Standby And Trouble Standby If programmed by the system control panel look for the presence of the flashing LEDs through the transparent housing cover The LED will flash with each communication Trouble If programmed by the system control pan...

Page 7: ...tion facilitates test of the alarm capability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The detector is self restoring when the accessory test stimulus is removed Verify that the system control panel has reset 9 2 3 Sensitivity Tests Notify the proper authorities that the smoke detector system is undergoing maintenance and that...

Page 8: ... Any smoke detector fire alarm equipment or any component of that system which fails shall be repaired or replaced as soon as possible Please refer to insert for the Limitations of Fire Alarm Systems 10 Board Replacement 10 1 Sensor Board Replacement 1 Remove the two sensor board mounting screws 2 Pull gently on the board to remove it 3 To replace the board align the board mounting features holes ...

Reviews: