background image

NOTE:

  Some panels support extended addressing. In order to

 

set the sensor above address number 99 on compatible

 

systems, carefully remove the stop on the left hand rotary

 

switch with pliers as shown in Figure 7.

[7] Perform Detector Check

 

1.  Perform STANDBY AND TROUBLE TEST per Section [9.2.1].
2.  Perform MAGNET TEST per Section [9.2.2.1]. The RTS451 
 

test of Section [9.2.2.2] may substitute for this requirement. 

3.  Perform AIR FLOW TEST per Section [9.1].
4.  Perform SMOKE RESPONSE TEST per Section [9.1.1].

[8] Install The Cover 

Install the cover using the six screws that are captured in the housing cover. Be certain filters are installed as specified in Section [5]. Make sure that 
the cover fits into the base groove and that all gaskets are in their proper positions. Tighten the six screws.

[9] Duct Smoke Detector Maintenance and Test Procedures

Test and maintain duct smoke detectors as recommended in NFPA 72. The tests contained in this manual were devised to assist maintenance person-
nel in verification of proper detector operation. 

Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of service. Disable the device or 
system under test to prevent unwanted alarms.

9.1] Smoke Entry Tests

[9.1.1] Air Flow

This product is designed to operate over an extended air speed range of 100 to 4000 FPM. To verify sufficient sampling of ducted air, turn the air handler 
on and use a manometer to measure the differential pressure between the two sampling tubes. The differential pressure should measure at least 0.0015 
inches of water and no more than 1.2 inches of water. 

Because most commercially available manometers cannot accurately measure very low pressure differentials, applications with less than 500 FPM of 
duct air speed may require one of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer Series 607) per Section 9.1.4 or; 2) the 
use of aerosol smoke per section 9.1.2.

[9.1.2] Air Flow Test using Aerosol Smoke

This test is intended for low-flow systems (100-500 FPM). If the air speed is greater than 500 FPM, use a conventional manometer to measure differ-
ential pressure between the sampling tubes, as described in 9.1.1.

Drill  a 

1⁄4

  hole  3  feet  upstream  from  the  duct  smoke  detector.  With  the  air  handler  on,  measure  the  air  velocity  with  an  anemometer. Air  speed 

must  be  at  least  100  FPM.  Spray  aerosol  smoke*  into  the  duct  through  the 

1⁄4

  hole  for  five  seconds.  Wait  two  minutes  for  the  duct  smoke 

detector  to  alarm.  If  the  duct  smoke  detector  alarms,  air  is  flowing  through  the  detector.  Remove  the  duct  smoke  detector  cover  and  blow 
out  the  residual  aerosol  smoke  from  the  chamber  and  reset  the  duct  smoke  detector.  Use  duct  tape  to  seal  the  aerosol  smoke  entry  hole. 
*Aerosol smoke can be purchased from Home Safeguard Industries, Malibu, CA. Phone: 310/457-5813.

[9.1.3] Smoke Entry Test

To  determine  if  smoke  is  capable  of  entering  the  sensing  chamber,  visually  identify  any  obstructions.  Plug  the  exhaust  and  sampling  tube  holes 
to  prevent  ducted  air  from  carrying  smoke  away  from  the  detector  head,  then  blow  smoke  such  as  cigarette,  cotton  wick,  or  punk  directly  at  the 
head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.

 

 

[9.1.4] Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter

Verify the air speed of the duct using an anemometer. Air speed must be at least 100 FPM. Wire the Dwyer transmitter as shown in Figure 8. Connect 
the leads of the meter to either side of the 1000

Ω

 resistor. Allow unit to warm up for 15 seconds. With both HIGH and LOW pressure ports open to 

ambient air, measure and record the voltage drop across the 1000

Ω

 resistor (measurement 1), 4.00 volts is typical. Using flexible tubing and rubber 

stoppers, connect the HIGH side of the transmitter to the sampling tube of the duct smoke detector housing, and the LOW side of the transmitter to 
the exhaust tube of the duct smoke detector housing. Measure and record the voltage drop across the 1000

Ω

 resistor (measurement 2). Subtract the 

J500-42-00 

I56-2198-003R

Figure 7. Rotary Address Switches

BREAKAWAY STOP

H0112-00

Summary of Contents for DH300PL

Page 1: ...also a remote alarm output for use with auxiliary devices The DH300PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT The DH300PL Duct Smoke Detector consists of the following items See Figure 1 DH300PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Figu...

Page 2: ...emplate supplied Affix the template to the duct at the desired mounting location Make sure the tem plate lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 2 1 Sampling Tube Installation for Ducts Less Than 11 2 Feet Wide see Figure 2 1 Remove the front cover 2 Slide the plastic sampling tube into the housing bushing and extend it the full widt...

Page 3: ...12 ft 2 4 to 3 7 m ST 10 Must extend a minimum of 2 3 the duct width J500 42 00 3 I56 2198 003R SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK Figure 3 Installation of foam gaskets over sampling tube bushings Figure 5 Tube mounting configurations with varying air flow direction SAMPLING TUBE END CAP AIR HOLES ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Figure 4 Air duct detector sampli...

Page 4: ...ate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in the housing Solid conduit con nections may be used if desired Smoke detectors and alarm system control panels have specifications for Signaling Line Circuit SLC wiring Consult the control panel man...

Page 5: ...sing Aerosol Smoke This test is intended for low flow systems 100 500 FPM If the air speed is greater than 500 FPM use a conventional manometer to measure differ ential pressure between the sampling tubes as described in 9 1 1 Drill a 1 4 hole 3 feet upstream from the duct smoke detector With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray ae...

Page 6: ...nce exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests 9 2 1 Standby And Trouble Standby If programmed by the system control panel look for the presence of the flashing LEDs through the transparent housing cover The LED will flash with each communication Trouble If programmed by the system control pan...

Page 7: ...tion facilitates test of the alarm capability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The detector is self restoring when the accessory test stimulus is removed Verify that the system control panel has reset 9 2 3 Sensitivity Tests Notify the proper authorities that the smoke detector system is undergoing maintenance and that...

Page 8: ... Any smoke detector fire alarm equipment or any component of that system which fails shall be repaired or replaced as soon as possible Please refer to insert for the Limitations of Fire Alarm Systems 10 Board Replacement 10 1 Sensor Board Replacement 1 Remove the two sensor board mounting screws 2 Pull gently on the board to remove it 3 To replace the board align the board mounting features holes ...

Reviews: