![Johnson Controls DCP09CSB21S Service Manual Download Page 46](http://html.mh-extra.com/html/johnson-controls/dcp09csb21s/dcp09csb21s_service-manual_2023298046.webp)
3
8
(4) Start-up failure (following AP1 for outdoor unit control board)
0DLQO\GHWHFW
Ɣ:KHWKHUWKHFRPSUHVVRUZLULQJLVFRQQHFWHGFRUUHFW"
Ɣ,VFRPSUHVVRUEURNHQ"
Ɣ,VWLPHIRUFRPSUHVVRUVWRSSLQJHQRXJK"
)DXOWGLDJQRVLVSURFHVV
Y
N
Y
N
N
Y
Y
N
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Restart it up after
3 minutes
Does startup fail?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Connect the wires as
per the connection
diagram
Replace the control panel AP1
If the fault is eliminated?
Replace the
compressor
End
Summary of Contents for DCP09CSB21S
Page 68: ...60 ...