background image

4.  Utilization in Cold Area

(1)  In a snow area, water from the heat exchanger may be frozen on the surface of the bottom base.  This 

may lead to poor drainage.  Therefore, do not use the drain adaptor in this type of area.

(2)  In the drainage method according to this manual, some of the defrost drain water dripped from the inlet 

protection grille may 

fl

 ow out over the bottom base of the product.   

To prevent this, provide a drain pan larger than the bottom surface of the product.  Secure the drain pan 
and the discharge pipe between the bottom part of the product and the foundation prior to discharge.

 < Installation Position >
  [ Example ] Capacity: 72,000 Btu/h

3.1  Installation of Drain Adaptor

The drain adaptor is for the drain pipe connection so as to use the 
outdoor unit bottom base as a drain pan.
(1) Put the 

2

 rubber cap in the 

1

 drain adaptor (to the upper part 

of the drain adaptor projection) in the direction of the arrow.

(2)  Put the drain adaptor in the hole for the drain adaptor of the 

outdoor unit bottom base until it is securely 

fi

 xed. (approx. 40

o

)

 

(The drain adaptor can be 

fi

 t into the bottom base until it stops.)

3.2  Installation of Drain Cap

The drain cap is a component to cover a hole.  
(1) Put the 

2

 rubber cap in the 

3

 drain cap (to the upper part of 

the drain adaptor projection) in the direction of the arrow.

(2)  Put the drain cap in the hole for the drain adaptor of the 

outdoor unit bottom base until it is securely 

fi

 xed. (approx. 40

o

)

 

(The drain cap can be 

fi

 t into the bottom base until it stops.)

Do not use the drain adaptor in an area where drain water may be frozen.     
(The drain water in the drain pipe may be frozen and then the drain pipe may crack.)

Use a rubber cap when 

fi

 xing the drain adaptor and drain cap.  (No rubber cap may lead to water leakage.)  

After 

fi

 xing, ensure that there is no water leakage from the drain cap by pouring water into the bottom base 

and then draining it from the drain adaptor.

Securely 

fi

 x the drain adaptor, rubber cap and drain cap at the bottom base so it desn’t become loose when 

connecting the drain pipe. 

Drain Adaptor

Rubber Cap

Projection

1

2

Drain Adaptor

Hole for
Drain Adaptor

1

2

,

(

)

Drain Cap

Rubber Cap

Projection

3

2

Drain Cap

Hole for
Drain Adaptor

2

3

,

(

)

Drain Cap Position (2 places)

Drain Pipe
(Field-Supplied)

Drain Adaptor Position (2 Places)

Drain Adaptor

Drain Cap

Bottom Base

(Front Side)

(Rear Side)

< Side View >

Unit: inch [mm]

(4-1/8 [105])

(10-5/16 [262])

(1-7/8 [48])

3-15/16

[100]

2-1/16 [52]

2 3

1 2

1 2

2 3

(Outdoor Unit Rear Side)

© 2015 Johnson Controls, Inc.

Code No. LIT-12012092

Issued June, 2015

P5415539