background image

  Connecting Serial Controllers to the P2000 Comark Server Running Software Version 3.11 

 

Preliminary – This information may change. 

One PC232-S4-X Unit 

This kit is used for the installation of one PC232-S4-X board. The cable connections of the 

kit complete the interface of the serial controllers to the server. 

Table 2: Connector Kit (supplied with one PC232-S4-X unit) 

Type 

Quantity  Mating Connector/Function 

Conn., 25-pin, MTA-100 

Ports 1, 2, 3, and 4 on connector box 

DB-25 Backshell 

Covers for DB-25 connectors 

Conn., 2-pin, MTA-100 

J1 to tamper switch connector on current loop converter board 

Conn., 4-pin, MTA-100 

J3, J4, J5 on first or only current loop 

converter board

 

Conn., 5-pin, MTA-100 

J2 on first current loop converter board 

Conn., 8-pin, MTA-100 

J7, J8, J9, J10 on first or only current loop converter board. (The 

other sides of the cables made with these connectors plug into 

the serial controllers.) 

Screw, 6-32x7/8 inch 

Used to mount current loop converter board to enclosure wall 

Screw, 6-32x1/2 inch 

Used to ground wire shields to enclosure wall 

Two PC232-S4-X Units 

This kit is used for the installation of two PC232-S4-X boards. The cable connections of the 

kit complete the interface of the serial controllers to the server. 

Table 3: Connector Kit (supplied with two PC232-S4-X units) 

Type 

Quantity  Mating Connector/Function 

Conn., 25-pin, MTA-100 

Ports 1 through 8 on connector box 

DB-25 Backshell 

Covers for DB-25 connectors 

Conn., 2-pin, MTA-100 

J1 to tamper switch connector on current loop converter board 

Conn., 4-pin, MTA-100 

J3, J4, J5 on both current loop converter boards 

Conn., 5-pin, MTA-100 

J2 on both current loop converter boards 

Conn., 8-pin, MTA-100 

J7, J8, J9, J10 on both current loop converter boards (The other 

sides of the cables made with these connectors plug into the 

serial controllers.) 

Screw, 6-32x7/8 inch 

Used to mount current loop converter board to enclosure 

Screw, 6-32x1/2 inch 

12 

Used to ground wire shields to enclosure wall 

The connectors supplied are mass termination type; attaching the cable wires to the 

connectors requires special tools. The recommended tools are listed in Table 4. 
 

Summary of Contents for D600-AP

Page 1: ...u may need the following equipment Digi AccelePort serial adapter board installed at the P2000 server PC232 converter S321 DIN and P900 controllers excluded B B Electronics RS 232 to RS 485 converter model 485OT9L S321 DIN controllers using serial communications only Note The S321 DIN can use serial communications with the RS 232 to RS 485 converter or it can communicate via IP using the Digi One ...

Page 2: ...0 and P900 including how to connect the controllers to the system and establish communications These components are not supplied and must be purchased separately Note This section does not include instructions for installing S321 DIN controllers For information on connecting these controllers see Connecting S321 DIN Controllers on page 13 Note The sections on the current loop converter do not appl...

Page 3: ...ons on installing the board Note When configuring the AccelePort name your devices as COM1 COM2 and so on The AccelePort does not support other names AccelePort to PC232 Installation The AccelePort module provides additional RS 232 serial ports The module is connected to the AccelePort PCI board in the server by a DB44 RS 232 cable Connect one end of the DB44 cable to the AccelePort COM port and t...

Page 4: ...ld Panel Interface board are the same as for the computers The specifications of the current loop converter are listed in Table 1 Table 1 Current Loop Converter Specifications Item Specification Number of Channels per PCBA 4 Input Output RS 232 to current loop and current loop to RS 232 Number of Serial Controllers per Channel 16 Ambient Temperature 32 to 122 F 0 to 50 C Relative Humidity 0 to 95 ...

Page 5: ...move the PC232 S4 X board from the enclosure by disconnecting the power cable from J6 and the tamper switch cable from J1 Then remove the four screws securing the PC232 S4 X board to the enclosure 2 Set aside the screws in a safe place so you can use them to replace the board into the enclosure 3 Hold the enclosure in the desired location on the mounting surface and use as a template to mark the l...

Page 6: ...tors and plug them into the mating connectors For Canadian installations refer to the Canadian Electric Code C22 1 Take into account the following requirements for cable routing Route power lines separately from data lines These lines can be a standard 3 wire stranded 16 AWG UL listed CSA approved line cord used with UL listed CSA approved strain relief All low level input cables system data alarm...

Page 7: ...r board to enclosure wall Screw 6 32x1 2 inch 6 Used to ground wire shields to enclosure wall Two PC232 S4 X Units This kit is used for the installation of two PC232 S4 X boards The cable connections of the kit complete the interface of the serial controllers to the server Table 3 Connector Kit supplied with two PC232 S4 X units Type Quantity Mating Connector Function Conn 25 pin MTA 100 8 Ports 1...

Page 8: ...wiring diagram For systems with two PC232 S4 X converter boards use 4 conductor cable to connect ports 2 through 8 of the FPI connector box to both PC232 S4 X PCB connectors J3 J4 and J5 respectively Use the 25 pin connectors supplied with the kit on ports 2 through 8 of the connector box Use the red 4 pin connectors supplied with the kit on both PC232 S4 X PCB ends Use a red 5 pin connector for c...

Page 9: ...ty of the grounding circuit periodically Testing Communications This test assumes that all hardware and software is installed Refer to the P2000 Server Workstation Software Installation Manual Part No 24 10618 120 for instructions Monitor the status of loops controllers and terminals by using the P2000 System Status window located in the System menu Refer to the P2000 Software User Manual Part No ...

Page 10: ...Connecting Serial Controllers to the P2000 Comark Server Running Software Version 3 11 Preliminary This information may change 10 Figure 4 Interconnect I O Converter to Current Loop Converter ...

Page 11: ...assis connected to a verified electrical ground earth In all cases the pertinent national wiring codes apply National Electrical Code NFPA 70 must be followed for installations in the USA Canadian Electrical Code C22 1 must be followed for installations in Canada BSI Standard BS7671 latest edition must be followed for installations in Great Britain Additional information is given in the Johnson Co...

Page 12: ... a lug to the end of the wire and screw securely to the wall of the enclosure or the nearest stud 4 All internal ground earth bonding straps must be left intact after installation 5 Check that grounding points are clean and free from paint or corrosion D Type Connectors All D type connectors must use an Electromagnetic Interference EMI shielded shroud Verify good contact occurs when connecting D t...

Page 13: ...orithm Two door access control input output interface One general purpose input and output per terminal The S321 DIN can communicate with the P2000 server in one of the following configurations Serial communications using a B B Electronics RS 232 to RS 485 converter model 485OT9L IP network communications using the Digi One SP serial to Ethernet converter The following subsections provide instruct...

Page 14: ...d Switch 1 Switch 2 Switch 3 Switch 4 R21 Time out ms 1200 OFF OFF OFF OFF 820k Ω 9 0 2400 OFF OFF OFF OFF 410k Ω 4 5 4800 ON OFF OFF OFF Not Used 2 2 9600 1 OFF ON OFF OFF Not Used 1 1 19 200 OFF OFF ON OFF Not Used 0 6 38 400 OFF OFF OFF ON Not Used 0 3 1 Default setting 2 Set the remaining switch positions for RS 485 Half Duplex operation and termination according to Table 6 Table 6 Remaining S...

Page 15: ...er to connect to an IP network via the controller s serial port See Figure 8 Figure 8 S321 DIN Controller in an IP Network Configuration To install the converter 1 Change the DIP switch settings on the bottom of the Digi One SP converter according to Figure 9 and Table 7 Figure 9 Digi One SP Converter DIP Switch Settings Table 7 Digi One SP Converter DIP Switch Positions DIP Switch Position 1 Down...

Page 16: ...onnect the DB 9F connector to the Digi One SP s DB 9M connector 4 Run an Ethernet cable from the Digi One SP to your network connection 5 Connect the power cable to the Digi One SP and run to an appropriate 110 240 VAC power source To install the driver for the Digi One SP and configure the device download the driver and configure the software according to the screen captures located at ftp cardke...

Page 17: ...nning Software Version 3 11 17 Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2012 Johnson Controls Inc ...

Reviews: