background image

Figure 2: Controller mounting positions

To mount the CVM controllers, complete the following

steps:

1.  Set all the switches on the equipment controller to

their known settings.

2.  Place the CVM controller in the proper mounting

position on the damper shaft so that the wiring

connections are easily accessible. Make sure

the controller base is parallel to the VAV box

(perpendicular to the damper shaft). If needed, use

a spacer to offset tipping of the controller caused by

the shaft bushings.

Note: 

Use the alignment marks to center

the captive spacer to ensure sufficient CVM

movement in either direction.

3.  Secure the self-drilling No.10 screw through

the captive spacer (see Figure 1) with a power

screwdriver and 100mm (4in.) extension socket.

Otherwise, use a punch to mark the position of

the shoulder washer, and then drill a hole into the

VAV box using a 3.5mm (9/64in.) drill bit. Insert the

mounting screw and tighten against the spacer.

Important: 

Do not overtighten the screw, or

the threads may strip. If mounting to the VAV

box, make sure the screws do not interfere with

damper blade movement.

4.  Locate the damper position using the typical marking

on the end of the damper shaft as shown in the

figure below.

Figure 3: Typical damper end shaft icons

5.  Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with pliers,

and either manually close the damper for 90° boxes

or manually open the damper for 45° or 60° boxes.

6.  Push down and hold the 

Manual Override

 button

(see Figure 1) and turn the CVM controller coupler

until it contacts the mechanical end-stop at either

the full-closed (90° boxes) or full-open (45° and 60°

boxes) position.

7.  If the damper for a 90° box closes CCW, rotate the

coupler to the CCW mechanical limit. If the damper

for a 90° box closes CW, rotate the coupler to the CW

mechanical limit. The open end-stop is automatically

set for 90° boxes. For 45° and 60° boxes, you must

provide hard stops at both full-closed and full-open

damper positions. If you install the CVM controller

at the full-open position, the controller provides the

open stop for 45° and 60° boxes. The closed damper

seal provides the full-closed stop.

Note: 

The integrated actuator has a stroke

time of 60 seconds for 90° of travel. The stroke

time is the amount of time (in seconds) that it

takes the actuator to move from the fully closed

to fully opened position or from fully open to

fully closed position. For proper operation, the

actuator stroke time must be configured in the

CCT application based on the actual time it takes

the actuator to drive the damper. The default

setting is 60 seconds (for 90° VAV boxes). For

45° and 60° VAV boxes, the actuator stroke time

must be adjusted. Refer to

 Controller Tool Help

(LIT-12011147)

 for instructions on setting the

actuator stroke time in the application.

8.  All models are compact in size and are easily installed

on VAV boxes. The models have either a round shaft

up to 13 mm in diameter or a 10 mm square shaft.

Tighten the square coupler bolt to the shaft using an

8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point

socket. Tighten to 10.5 to 11.5 N·m (95 to 105 lb·in).

9.  Loop the pneumatic tubing (supplied by field

personnel) to include a trap for condensation. Attach

the needed length of tubing (supplied and installed

by field personnel) to the dual port fitting on the CVM

controller and the other ends of the tubing to the

pressure transducer in the VAV box application (see

Figure 1).

Note: 

 The CVM uses a digital pressure sensor

with bidirectional flow operation, which allows

you to connect the high- and low-pressure

DP tubes to either barbed fitting on the CVM

controller. You do not need to make a specific

high- or low-side connection when you attach

the tubing to the barbed fittings on the CVM.

10.  Push the 

Manual Override

 button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

11.  Complete the mounting by rotating the damper to

the full-open position.

M4-CVM VAV Box Controllers Installation Guide

3

Summary of Contents for CVM03050

Page 1: ...e and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N...

Page 2: ...al block or N2 protocol as required 13 EOL End of Line Switch See Setting the End of Line EOL switch 14 SA Bus Port RJ 12 6 Pin Modular Jack See Modular ports 15 FC Bus Port RJ 12 6 Pin Modular Jack S...

Page 3: ...you must provide hard stops at both full closed and full open damper positions If you install the CVM controller at the full open position the controller provides the open stop for 45 and 60 boxes The...

Page 4: ...ons Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detai...

Page 5: ...A bus Note Stranded 4 wire 2 twisted pair shielded cable One twisted pair is the and leads The second pair is COM and POWER Note Do not use the modular SA Bus port and the terminal block SA Bus simult...

Page 6: ...avant d avoir v rifi toutes les connexions du c blage Le c blage inad quat de cette borne peut causer un court circuit sur l alimentation lectrique de 24 V c Un court circuit peut causer le d clenche...

Page 7: ...ings and requirements To determine wire size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal UI n terminals Provides 35 mA total current Sa...

Page 8: ...INARY Outputs BO C Binary Output 24 VAC Triac Internal Power Connects BO n to 24 BO C when activated Internal Power Source 30 VAC maximum voltage to load 0 5 A maximum output current 1 3 A at 25 duty...

Page 9: ...and the load current in mA when wiring inputs and outputs Note Figure 9 applies to low voltage 30 V inputs and outputs only Figure 9 Maximum wire length for low voltage 30 V Inputs and Outputs by curr...

Page 10: ...Common SA BUS 1 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wires are one twisted pair and the COM and POW...

Page 11: ...on for the applicable termination diagrams Table 8 Termination details Type of Field Device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI...

Page 12: ...xternal Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch...

Page 13: ...AC supply from the controller 2 Set the address switches to the desired N2 address For details about setting a device address see Setting the device address 3 Reconnect the 24 VAC supply to the contro...

Page 14: ...ommunication 1 254 Note Addresses 0 and 255 are reserved and not for use on equipment controllers The device address is a decimal address set using three rotary switches located at the top of the cont...

Page 15: ...the CVM03050 controller use the following procedure 1 With the desired application loaded in the controller commission the VAV Box Refer to the Controller Tool Help LIT 12011147 2 Perform airflow bal...

Page 16: ...Elec Reheat Series Fan W C Adj Single Duct SCR Electric Reheat Proportional Heating Valve Single Speed Series Fan Warm Cool Adjust SCR Elec Reheat Parallel Fan W C Adj Single Duct SCR Electric Reheat...

Page 17: ...ration SA Bus devices offline such as netsensors Rapid blink SA Bus communications issue Off Steady No faults On Steady Device fault or no application loaded FC BUS Green Blink 2 Hz Blink 2 Hz Data tr...

Page 18: ...COM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not s...

Page 19: ...ontroller Display NS ATV7003 0 Handheld VAV Balancing Tool NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin LIT 12011574 for specific sensor model descriptions AS CBLT...

Page 20: ...cks 30 terminal blocks in total MS FIT100 0 The Field Inspection Tool FIT is a portable handheld device with a user interface that is used to test and troubleshoot the BACnet protocol MS TP RS 485 com...

Page 21: ...er and equipment controllers 4 wire SA Bus between equipment controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from equipment controller to bus...

Page 22: ...e of its products Repair information If the CVM03050 equipment controller fails to operate within its specifications replace the unit For a replacement unit contact the nearest Johnson Controls repres...

Reviews: