Checking superheat and subcooling
R-410A temperature charts list the associated saturation temperature in one column and the
associated pressure in another column. See Table 15.
Subcooling
When the refrigerant charge is correct, there is no vapor in the liquid sight glass with the system
operating under full load conditions.
The subcooling temperature of each system can be calculated:
1. Record the temperature of the liquid line at the outlet of the condenser.
2. Subtract it from the saturation temperature listed in Table 15 for the corresponding
discharge pressure.
3. If the unit lacks an access port for liquid access, subtract the condenser coil pressure drop
value from Table 15 from the discharge pressure to determine the equivalent saturation
temperature.
For example, when the discharge pressure is 388 psig and the liquid line temperature is 95.0°F:
•
Liquid Pressure = Discharge Pressure (388 psig) minus 33 psig = 355 psig
•
Saturation Temperature for 355 psig = 108.0°FLiquid Line Subcooling = Saturation
Temperature (108.0°F) minus Liquid Line Temperature (95.0°) = 13.0°F
Subcooling should be 12.0–15.0°F at design conditions.
Table 15: R-410A pressure and temperature chart
PSIG
Temp ˚F
PSIG
Temp ˚F
0
-60
78
20
2
-58
80
21
4
-54
85
24
6
-50
90
26
8
-46
95
29
10
-42
100
32
12
-39
105
34
14
-36
110
36
16
-33
115
39
18
-30
120
41
20
-28
125
43
22
-26
130
45
24
-24
135
47
26
-20
140
49
28
-18
145
51
30
-16
150
53
32
-14
160
57
34
-12
170
60
36
-10
180
64
38
-8
190
67
40
-6
200
70
42
-4
210
73
44
-3
220
76
46
-2
225
78
48
0
235
80
50
1
245
83
52
3
255
85
63
C-Series Vertical (CSV) Water-Cooled Self-Contained Units, B Generation, R-410A Installation, Operation, and
Maintenance Manual