* Blower performance includes evaporator coil and 2" filters.
Table 8: CSV180B supply air blower performance
Available external static pressure - inches W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 3HP
Optional hi- 3.5HP
4800
634 1.20 697 1.42 757 1.62 813 1.84 867 2.06 918 2.30 968 2.52 1015 2.76 1065 3.02 1109 3.32
5400
701 1.66 758 1.90 812 2.14 864 2.38 914 2.62 962 2.88 1009 3.12 1053 3.38 1097 3.66 1139 3.92
6000
765 2.22 817 2.48 867 2.74 916 3.00 962 3.28 1007 3.54 1051 3.82 1093 4.10 1134 4.38 1174 4.68
6600
832 2.90 880 3.20 927 3.48 972 3.76 1015 4.06 1057 4.34 1099 4.64 1139 4.96
~
~
~
~
7200
900 3.72 945 4.02 988 4.34 1030 4.64 1070 4.96
~
~
~
~
~
~
~
~
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 9: CSV240B supply air blower performance
Available external static pressure - inches W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied low static drive
Standard drive + 5HP
Optional hi-
7.5HP
6400
705 1.96 760 2.22 812 2.48 862 2.72 910 3.02 956 3.28 1001 3.56 1043 3.84 1085 4.12 1125 4.42
7200
788 2.76 837 3.06 884 3.34 930 3.64 952 3.78 995 4.08 1037 4.38 1078 4.70 1118 5.00 1156 5.32
8000
861 3.70 906 4.02 950 4.34 992 4.66 1033 4.98 1073 5.32 1111 5.66 1149 5.98 1186 6.32 1222 6.68
8800
949 4.94 970 5.12 1010 5.46 1049 5.82 1087 6.18 1125 6.52 1161 6.90 1197 7.26
~
~
~
~
9600 1028 6.34 1066 6.72 1103 7.10 1139 7.48
~
~
~
~
~
~
~
~
~
~
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 10: CSV300B supply air blower performance
Available external static pressure - inches W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied low static drive
Standard drive + 7.5HP
Optional hi- 2.5HP
8200
581 1.80 647 2.16 707 2.49 765 2.85 819 3.24 870 3.60 920 3.99 967 4.38 1012 4.80 1056 5.19
8800
639 2.31 6.99 2.70 755 3.06 809 3.45 860 3.84 910 4.26 957 4.65 1002 5.07 1045 5.49 1087 5.94
9200
676 2.70 733 3.09 787 3.48 839 3.87 888 4.29 935 4.71 981 5.13 1025 5.58 1068 6.00 1109 6.45
9600
716 3.15 771 3.54 822 3.96 872 4.38 920 4.80 965 5.25 1010 5.70 1052 6.15 1093 6.60 1113 7.05
10000 755 3.63 807 4.05 856 4.47 904 4.92 950 5.37 994 5.82 1037 6.27 1079 6.75 1119 7.20
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
C-Series Vertical (CSV) Water-Cooled Self-Contained Units, B Generation, R-410A Installation, Operation, and
Maintenance Manual
58