10
PMGB0374
Air Outlet Direction Change (Floor Concealed Model)
The air outlet direction of the unit can be changed from upward to front by following the procedures below.
(1) Remove the securing screws of the air outlet flange. Then, remove the air outlet flange.
(2) Turn the air outlet on itself until it is opposite its initial position.
(3) Tilt the air outlet so that the nozzle is facing forwards.
(4) Secure the air outlet flange.
Optional Location for CIW01 (Floor Exposed Type)
In an instance of a floor exposed model unit, it is possible to install the CIW01 under the plastic cover as
shown in the following figure.
Provide a field-supplied service access cover which is secured by screws so that the fan wheel is not directly
touched (only floor concealed model).
The air outlet grille of the floor concealed model unit cannot be used in a highly humid place such as a
kitchen, because condensation may occur on the grille surface.
NOTICE
Air Outlet Grille
Absorbent Plate for Water
Polyurethane Foam for Thermal
Insulation (Field-Supplied)
Air Outlet Duct (Field-Supplied)
Floor Concealed
Unit
4
1
2
3
2
Air Outlet Flange
RUN/STOP
TEMP
Secure CIW01 using two screws
(Factory-Supplied)
(3) Adjust the flat level of the unit by adjusting bolts for installation which are attached in the unit. Make the
condensate pipe side lower than the opposite side for smooth drainage.
(4) Secure the base plate and back plate of the unit with field-supplied bolts and screws. When attaching
the adjusting bolts for installation, remove the electrical wiring box.
(5) Install the field-supplied air outlet grille of the floor concealed type unit as shown in the following figure.
If installed in a comparatively high humid place, condensation may occur. Therefore, attach a plate
which can absorb water around the grille.