I/O terminal blocks, ratings and requirements
Table 2: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal Block label
Terminal
label
Function, ratings, requirements
Determine wire size and
maximum cable length
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 10k ohm Pull-down
See Guideline
A
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[ Johnson Controls
®
sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient (NTC)
Sensor
See Guideline
A
IN
n
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
See Guideline
A
UNIVERSAL
(Inputs)
ICOM
n
Universal Input Common
for all Universal Input terminals
Note:
All Universal ICOM
n
terminals share
a common, which is isolated from all other
commons.
Same as (Universal)
IN
n
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 18 V. 3k ohm pull up
IN
n
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3k ohm pull up
BINARY
(Inputs)
ICOM
n
Binary Input Common
for all Binary Input (IN) terminals
Note:
All Binary ICOM
n
terminals share a
common, which is isolated from all other
commons, except the Configurable Output
(CO) common (OCOM
n
) when the CO is
defined as an Analog Output.
See Guideline
A
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
See Guideline
A
OUT
n
Binary Output - 24 VAC Triac
(External Power Source only)
Connects OUT
n
to OCOM
n
when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current
See Guideline
C
CONFIGURABLE
(Outputs)
OCOM
n
Analog Output Signal Common
All Configurable Outputs
(COs) defined as Analog Outputs (AOs) share a common,
which is isolated from all other commons except the Binary
Input common.
Binary Output Signal Common
All Configurable Outputs
(COs) defined as Binary Outputs are isolated from all other
commons, including other CO commons.
Same as (Configurable)
OUT
n
.
ATC1510 Advanced Terminal Unit Controller Installation Guide