background image

Figure  2: SA Bus Terminal Block Wiring

3. The SA Bus port on the controller is an RJ-12, 6-

position modular jack that provides a connection

for the Mobile Access Portal (MAP) Gateway, the

VAV Balancing Tool, specified network sensors, or

other SA Bus devices with RJ-12 plugs. Wire the SA

Bus port as shown in Figure 3.

Note: 

The SA port is connected internally to

the SA Bus terminal block.

Figure  3: Pin Number Assignments for SA Bus

Ports

4. Wire the Power Supply Terminal Block. The ATC

uses a 240 VAC, +/-10% supply power terminal

two-pin, three-position, red connector.

a. Connect the supply wires to the red plug-

in terminal block as shown in Figure 4.

b. Insert the plug-in terminal block into the

ATC. For the location of the ATC power

input, see Figure 6.

Figure  4: Power Supply Wiring

A: Line

B: Neutral

Maximum Cable Length versus Load Current

For this system to operate correctly, the maximum

wire length is 137.2 m (450 ft) and the wire cross-
sectional area is 1.5 mm

2

 (16 AWG) to 0.5 mm

2

 (22

AWG).

Input and Output wiring guidelines

Table 2 and Table 3 provide information and guidelines

about the functions, ratings, and requirements for the

controller input and output terminals, and guidelines

for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 2 and Table

3, observe these guidelines when wiring controller

inputs and outputs:
• Run all low-voltage wiring and cables separate from

high-voltage wiring.

• All input and output cables, regardless of wire size

or number of wires, should consist of stranded,

insulated, and twisted copper wires.

• Shielded cable is not required for input or output

cables.

• Shielded cable is recommended for input

and output cables that are exposed to high

electromagnetic or radio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)

typically do not require an offset in the software

setup. Cable runs over 30 m (100 ft) may require an

offset in the input/output software setup.

ATC1510 Advanced Terminal Unit Controller Installation Guide

4

Summary of Contents for ATC1510

Page 1: ...dio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area ma...

Page 2: ...the back of the controller extend the two mounting clips as illustrated 3 Position the controller so that the two extended mounting clips are facing downwards and place the controller on the DIN rail...

Page 3: ...fa on incor recte risquent d endommager irr m diablement l quipement 1 Wire the FC Bus Terminal Block The ATC features a blue removable 4 terminal FC Bus block that fits into a board mounted jack Wire...

Page 4: ...450 ft and the wire cross sectional area is 1 5 mm 2 16 AWG to 0 5 mm 2 22 AWG Input and Output wiring guidelines Table 2 and Table 3 provide information and guidelines about the functions ratings an...

Page 5: ...Accumulator Mode 0 01 second minimum pulse width 50 Hz at 50 duty cycle Internal 18 V 3k ohm pull up BINARY Inputs ICOMn Binary Input Common for all Binary Input IN terminals Note All Binary ICOMn ter...

Page 6: ...240 VAC 0 66FLA 4LRA 50k cycles BINARY RELAY 5A Output OCOMn Binary Relay Output Common for OUTn terminal Note Each Binary Relay Output Common terminal OCOMn is isolated from all other commons includi...

Page 7: ...wire 137 m 450 ft twisted wire 0 5 mm 2 22 AWG stranded copper 183 m 600 ft twisted wire 91 m 300 ft twisted wire B 0 25 mm 2 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire...

Page 8: ...s COM Signal Reference Common for Bus communications FC BUS 2 SHIELD Isolated terminal optional shield drain connection 0 5 mm 2 22 AWG stranded 3 wire twisted shielded cable recommended SA Bus Commun...

Page 9: ...le termination diagrams Table 5 Termination diagrams Type of Field Device Type of Input Output Termination Diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Self Powered UI...

Page 10: ...t Output CO 24 VAC Triac Output Switch Low External Source CO Incremental Control to Actuator Switch Low Externally Sourced Triac Jumpers where applicable BO 24 VAC Binary Output Switch Low Externally...

Page 11: ...he TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus Network Stat with Terminals Fixed Address 199 SA Bus The following...

Page 12: ...rs Accessory Kit all wiring must be secured to the stress brackets as illustrated below The following procedure describes how to install the IP20 Covers Accessory Kit to the ATC 1 Attach the IP20 cove...

Page 13: ...ential device address for each of the equipment controllers connected on the FC or SA Bus 2 To ensure the best bus performance set sequential device addresses with no gaps in the device address range...

Page 14: ...commission the controller but you cannot use the Bluetooth connection to Transfer to Device Download The MAP Gateway serves as a replacement for the BTCVT which is no longer available for purchase but...

Page 15: ...d required if controller is in Boot mode Blink 2 Hz Download or Startup in progress not ready for normal operation Rapid blink SA Bus communications issue SA BUS Green Blink 2 Hz Blink 2 Hz Data Trans...

Page 16: ...ical Features The following section describes the physical features of the ATC Figure 6 Advanced Terminal Unit Controller Physical Features ATC1510 Advanced Terminal Unit Controller Installation Guide...

Page 17: ...outputs C 24 VAC out D 5 A relay outputs E DIN clips F Triac outputs G 10 A relay output H 240 VAC power input I FC Bus J FC Bus EOL switch K SA Bus L SA Bus RJ12 M USB N Universal inputs O Binary inp...

Page 18: ...and not valid field controller addresses N2 Valid field controller device addresses 1 to 254 Device address 255 is reserved for the broadcast address and not a valid field controller address Communica...

Page 19: ...d common terminal between all 5A ROs Binary Output Triac BO 24 VAC or 240 VAC 500 mA Resistive Externally powered Shared common terminal between all BO Triacs 10 A Relay Output 10A RO K8 Single Pole S...

Page 20: ...E VOLTAGE 4000 V Ball Pressure temperature 90 C BINARY RELAY Outputs Reference all relay commons to the same pole of the supply circuit BINARY Triacs Outputs Reference all triac commons to the same po...

Reviews: