background image

10

    A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 

Product/Technical Bulletin

2.  Check for proper sensor operation.

Disconnect all power sources to control.

a. 

Take a temperature reading at the sensor
location, using an accurate thermometer.

b. 

Disconnect the sensor from the control.

c. 

Use a reliable ohmmeter, to measure the
resistance across the two sensor leads while
the sensor is at the temperature taken in
Step b.

d. 

Refer to Figure 15 to verify that the measured
temperature and resistance conform to
established temperature and resistance
values.

e. 

If the measured values conform to the values
in Figure 15, proceed to Step 3.

f. If the sensor’s measured resistance value is

substantially different from the expected value
for that temperature, check the sensor wiring.
If sensor wiring is okay, replace the sensor.

-40

-20

0

20

40

60

80

100

120

140

160

180

200

220

240

260

500

700

900 1100 1300 1500 1700 1900 2100

Resistance in Ohms

Temperature (°F)

-40

-20

0

20

40

60

80

100

120

Temperature (°C)

Figure 15: Nominal Temperature vs.

Sensor Resistance

3.  Check the A419 for proper operation.

a. Perform 

Troubleshooting

 Steps 1 and 2 before

performing this step.

b.  Disconnect the load from the output relay

terminals.

c.  Ensure that the Touchpad Lock jumper is

installed, so that the touchpad is unlocked.

d.  Reconnect the sensor leads and supply power

to the control.

e.  Replace the cover.

f. 

Check the control settings for proper values.

g.  Press and hold the 

MENU

 button until Setpoint

appears (occurs in about 2 seconds).

h. Use 

the 

Up

 and 

Down

 buttons to change the

Setpoint temperature above and below the
current sensor temperature until the output
relay energizes and de-energizes as shown in
Table 4.

If the anti-short cycle delay has a time greater
than 0 minutes, the relay will not energize until
the timed delay has elapsed.

i. 

If the output relay does 

not

 perform as

indicated in Table 4, replace the A419 control.

j. 

If proper operation of the A419 control is
verified, reconnect the load and consult the
equipment manufacturer’s instructions for
troubleshooting the controlled equipment.

Table 4: A419 Output Relay Operation

Setpoint
Mode

Operating
Mode

Output
Relay
Energized
at…

Output Relay
De-energized
at…

Cooling

Setpoint
plus
differential

Setpoint

Cutout

Heating

Setpoint
minus
differential

Setpoint

Cooling

Setpoint

Setpoint
minus
differential

Cut-in

Heating

Setpoint

Setpoint plus
differential

Note:

When the relay is energized, the N.O. contacts

are closed and the LED is illuminated.

Summary of Contents for A419 Series

Page 1: ...Temperature Sensor Features and Benefits Easy to Read Front Panel Liquid Crystal Display Displays the sensed temperature and control function status clearly custom icons on the display indicate the control and system status at a glance Wide Temperature Differential Adjustment Range 1 to 30F or C Allows the user to set a precise 1F or C temperature differential from 1 to 30F or C providing a much t...

Page 2: ...e harmful interference and 2 this device must accept any interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment gen...

Page 3: ...n to adjust the control setting Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the SPDT output relay is energized and the Normally Open N O contacts are closed See Figure 5 A419 Control Definitions Cut in is the temperature at which the N O contacts on the SPDT output relay close Cutout is the temperature at which the N O contacts on the SPDT output rel...

Page 4: ...ue set in Temperature Offset The BIN and COM terminals may be connected to a user supplied external switching device such as a time clock that has a set of Single Pole Single Throw SPST contacts Closing a circuit between the BIN and COM terminals activates the Temperature Offset See Wiring This function enables the control to alternate between two temperature setpoints based on the position of the...

Page 5: ...n A419 control has either a standard high impact plastic NEMA 1 or a NEMA 4X corrosion resistant watertight enclosure The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment Note When mounting the control to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure The mounting hole pattern of the NEMA 1 enclosure is ...

Page 6: ...igure 10 and Figure 11 Keep the leads between the control and sensor as short as possible practical in your application The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature Refer to Table 1 when extending sensor leads Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15...

Page 7: ...pers to set Cooling Heating Setpoint and Touchpad Lock functions 4 Replace the cover and fasten in place with the four screws 5 Restore power to the control IMPORTANT Verify that the Cooling Heating jumper is positioned properly before powering the A419 control to ensure that the relay operates as intended See Figure 13 and Table 2 Jumper Pins Removed Jumper Positioned on One Pin Installed Jumper ...

Page 8: ...everts to the previously saved setpoint value Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Table 3 Function Ranges and Settings Function Range Factory Setting SP Setpoint 30 to 212 F 34 to 100 C 30 dIF Differential 1 to 30 F or C 5 ASd Anti short Cycle Delay 0 to 12 minutes 1 OFS Temperature Offset 0 to 50 F or C 0 SF Sensor F...

Page 9: ...sly saved value for that function Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Checkout Before applying power make sure installation and wiring connections are according to job specifications After necessary adjustments and electrical connections have been made put the system in operation and observe the control for at least t...

Page 10: ...s 1 and 2 before performing this step b Disconnect the load from the output relay terminals c Ensure that the Touchpad Lock jumper is installed so that the touchpad is unlocked d Reconnect the sensor leads and supply power to the control e Replace the cover f Check the control settings for proper values g Press and hold the MENU button until Setpoint appears occurs in about 2 seconds h Use the Up ...

Page 11: ...he control Ordering Information Refer to Table 6 to order controls and accessories Table 6 Ordering Information Product Code Number Item Description A419ABC 1C Line Voltage NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included A419AEC 1C Line Voltage NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included Supply Voltage 1...

Page 12: ...hp Full Load Amperes N O N C 16 5 8 A 9 2 4 0 A 8 0 4 9 A Locked Rotor Amperes N O N C 96 34 8 A 55 2 24 A 48 29 4 A Non inductive Amperes N O N C 15 10 A 10 10 A 10 10 A Pilot Duty 125 VA N O contacts 24 to 240 VAC 125 VA N C contacts 120 to 240 VAC 50 VA N C contacts 24 VAC Sensor Type A99BB Type PTC Sensor See Table 6 Control Ambient Temperature Operating 26 to 140 F 32 to 60 C Shipping 40 to 1...

Reviews: